Features and technical data
14
1
1.7
TECHNICAL DATA
Table 1.1
GA ACF technical data
ACF 60-00 ACF 60-00
HR
ACF 60-00
TK
ACF 60-00
HT
ACF 60-00
LB
Operation in cooling mode
Cooling capacity
nominal
Btu/hr
60500 (1)
58400 (1) 45400 (2)
Gas input (HHV)
nominal
Btu/hr
94900
GUE
nominal
%
71
68
53
Cold water outlet temperature
minimum
°F
37.4
41
14
Cold water inlet temperature
maximum
°F
113
Water flow rate
maximum
GPM
14.1
12.8
nominal
GPM
12.2
11.8
11.4
minimum
GPM
11.0
10.1
ΔT
nominal
°F
10
9
Internal pressure drop
at nominal water flow
Feet of Head
psig
9.7
4.2
9.1
3.9
14.1
6.1
Ambient operating temperature
maximum
°F
120
131
120
minimum
°F
32
10.4
32
10.4
Condenser air flow (3)
nominal
CFM
6000
minimum
CFM
2000
Operating recovery circuit
Cooling capacity with heat recovery
nominal
Btu/hr
61240 (4)
Recovery unit heat capacity
nominal
Btu/hr
-
86400 (5)
-
GUE
nominal (recovery)
%
-
155
-
Hot water flow rate (ΔT = 18 °F)
maximum
GPM
-
11.0
-
minimum
GPM
-
0
-
nominal
GPM
-
9.6
-
Internal recovery circuit pressure drop
at nominal water flow
Feet of Head
psig
4.34
3
Electrical specifications
Power supply
voltage
V
208-230
type
-
single-phase
frequency
Hz
60
Condenser fan motor (variable speed)
HP
-
1/2
nominal ampacity full load / locked rotor
A
3.1 / 6.2
Oil pump motor
HP
-
0.35
nominal ampacity full load / locked rotor
A
2.03 / 7.7
Premix blower motor
HP
-
1/50
nominal ampacity full load / locked rotor
A
0.55 / 0.75
Total electrical operating consumption (6)
unit only
kW
0.75
Minimum circuit ampacity (MCA)
unit only
A
8.0
Maximum over current protection (MOCP)
A
10.9
Installation data
Gas consumption
natural gas (nominal)
CFM
1.58 (7)
Water content inside the apparatus
hot side
gallons
-
0.79
-
cold side
gallons
0.79
Water fitting
thread
FPT
1 1/4
Gas connection
thread
FPT
1/2
Dimensions
width
"
33 1/2
depth
"
48 1/2
height
"
50 3/4
Weight
in operation
pounds
750
815
816
shipping
pounds
795
860
860
General information
Cooling fluid
ammonia R717
pounds
15.0
15.9
17.4
15.7
15.9
water H
2
O
pounds
22.0
22.7
22.0
23.1
(1)
Cooling capacity at standard conditions of 95 °F ambient temperature. Chilled water outlet temperature 45 °F, inlet 55 °F.
(2)
Cooling capacity at standard conditions of 95 °F ambient temperature. Chilled water outlet temperature 23 °F (with 40% ethylene glycol), inlet 32 °F.
(3)
Fan speed is reduced when external temperature is less than 91.4 °F.
(4)
Cooling capacity at standard conditions (with recovery) of 95 °F ambient temperature. Chilled water outlet temperature 45 °F, inlet 55 °F. Heat recovery delivery temperature 122 °F, inlet 104
°F. For conditions other than nominal, apply the correction factors in following tables.
(5)
Heating capacity at standard conditions (with recovery) of 95 °F ambient temperature. Chilled water outlet temperature 45 °F, inlet 55 °F. Heat recovery delivery temperature 122 °F, inlet 104
°F. For conditions other than nominal, apply the correction factors in following tables.
(6)
±10% according to the power supply voltage and tolerance on electrical motors consumption. Measured at outdoor temperature of 86 °F.
(7)
HHV (natural gas) 1014 Btu/CU.FT.