Maintenance
Installation, use and maintenance manual – G gas unit heater
41
7
6.6
SETTING RANGE
Through the chronothermostat it is possible to set the
heat output of the gas unit heater, setting a value (in per-
centage) different from the nominal one.
This option modifies the maximum heat output of the gas
unit heater accordingly and can be implemented when
you want the gas unit heater to have a heat output lower
than the nominal one.
The adjustment of the heat output can only be
carried out by a TAC or by professionally qualified
personnel.
In case of intervention, the parameter to be modi-
fied is PM 05 (Table 6.4
p. 35). For any adjustment,
follow the setting instructions given in Paragraph
The following Table 6.8
p. 41 shows, depending on the
model, the values (in percentage) that can be set and
the corresponding heat input (to be reported on the
nameplate).
Example:
For a G100 gas unit heater, if you want to adjust a heat
output of 86,9 kW, you must set (in parameter PM 05) the
value 90.
The value of 100 (%) (default value) corresponds to
the nominal heat output of the gas unit heater; the
value of 0 (%) corresponds to the minimum heat
output of the gas unit heater.
Table 6.8
Blower speed and corresponding heat input
PM 05
G30
G45
G60
G100
(upper modu-
lation depth
limit)
Value to be set
[%]
Combustion
blower speed
[rpm]
Heat input
[kW]
Combustion
blower speed
[rpm]
Heat input
[kW]
Combustion
blower speed
[rpm]
Heat input
[kW]
Combustion
blower speed
[rpm]
Heat input
[kW]
100%
3500
30,0
4850
45,0
5650
58,0
6000
93,0
95%
3420
29,3
4693
43,5
5468
56,1
5803
89,9
90%
3340
28,6
4535
42,1
5285
54,3
5605
86,9
85%
3260
27,9
4378
40,6
5103
52,4
5408
83,8
80%
3180
27,3
4220
39,2
4920
50,5
5210
80,8
75%
3100
26,6
4063
37,7
4738
48,6
5013
77,7
70%
3020
25,9
3905
36,2
4555
46,8
4815
74,6
Once the heat input of the heater has been
changed, it is mandatory to update the nameplate,
showing on it the value of the nominal heat input
at the time of commissioning (EN 1020 and prEN
17082) in indelible letters and in a durable manner.
7
MAINTENANCE
7.1
WARNINGS
Correct maintenance prevents problems, assures
efficiency and keeps running costs low.
Maintenance operations described herein may ex-
clusively be performed by the TAC or skilled main-
tenance technician.
Any operation on internal components may exclu-
sively be performed by the TAC.
Before performing any operation, switch off the
appliance by means of the control device and wait
for the end of the shutdown cycle, then disconnect
power and gas supply, by acting on the electrical
disconnector and gas valve.
The efficiency checks and every other "check and
maintenance operation" (see Table 7.1
must be performed with a frequency according to
current regulations or, if more restrictive, according
to the provisions set forth by the manufacturer, in-
staller or TAC.
Responsibility for efficiency checks, to be carried
out for the aims of restricting energy consumption,
lies with the system manager.