First start-up
26
5
Figure 4.4
Flame lockout lamp connection
L1
Lockout lamp
L1
X9
X11
When the led comes on, in the manner described in Table
p. 26, it indicates the presence of a fault.
Table 4.1
Led status to signal faults
Fault
LED status
Flame lockout
Fixed
Limit thermostat trip or minimum flue gas temperature thermostat trip
(1)
Flashing (on = 4 seconds, off = 1 second) (2)
Other type of anomaly
Flashing (on = 1 second, off = 4 seconds) (2)
1
The flue gas temperature thermostat is present on the G series gas unit heaters.
2
After 72 hours of continuous flashing status, the led becomes fixed.
4.6
REMOTE THE ERROR RESET
Remote unlocking can also be performed. To do this, a
button must be connected to terminals X11 of the mo-
tor board (230V - 50Hz output, see diagram in Figure
4.5
Closing the contact causes the fault to be reset.
Figure 4.5
Flame lockout reset button connection
P1
Reset button
P1
X9
X11
5
FIRST START-UP
First start-up entails checking/setting up the com-
bustion parameters and may exclusively be carried
out by a Robur TAC. NEITHER the user NOR the in-
stallation technician is authorised to perform such
operations, under penalty of voiding the warranty.
The installer is obliged to carry out preliminary
checks described in Paragraph 5.1
5.1
PRELIMINARY CHECKS
Paragraph dedicated to the installer.
5.1.1
Preliminary checks for first start-up
Upon completing installation, before contacting the TAC
the installer must check:
▶
Electrical and gas systems suitable for the required ca-
pacities and equipped with all safety and control de-
vices required by the regulations in force.
▶
Absence of leaks in the gas system.
▶
Type of gas for which the appliance is designed (natu-
ral gas, LPG or other gas).
▶
Supply gas pressure complying with the values of
Table 3.1
p. 17, with max tolerance ±15%.
▶
Correct operation of the flue exhaust duct.
▶
Combustion air feed and flue gas exhaust correctly
carried out according to the regulations in force.
▶
Power supply mains complying with the appliance's
rating plate data.
▶
Appliance correctly installed, according to the manu-
facturer's instructions.
▶
System installed in a workmanlike manner, according
to national and local regulations.
5.1.2
Abnormal or hazardous installation
situations
Should any abnormal or hazardous installation situations
be found, the TAC shall not perform first start-up and the
appliance shall not be commissioned.
These situations may be:
▶
Failed compliance with minimum clearances.
▶
Insufficient distance from combustible materials.
▶
Conditions that do not warrant access and mainte-
nance in safety.
▶