ROBOVENT • PFX SERIES OWNER’S MANUAL
SECTION 600
Installation
Electrical Hook-Up
The PFX Collectors require a 3 phase, 460 volt electrical
feed. (see Figure 1). (Other voltages are also available,
special order). Amperage requirements for the motor can
be found under “Specifications” for the particular DFM
model. Electrical connections should only be done by a
licensed electrician and in accordance with NEC and all
applicable local codes.
Blower Rotation
IMPORTANT!
Check blower rotation of the unit
by jogging the motor. Blower rotation should be
CLOCKWISE when viewed from above the unit.
The blower will still draw air if the motor is running
backward but the air draw will only be a fraction of what
it should be!
A visual inspection will verify that the motor is turning
clockwise when viewed form above the unit.
FIGURE 1
Содержание PFX Series
Страница 2: ......
Страница 6: ......
Страница 7: ...ROBOVENT PFX SERIES OWNER S MANUAL 7 SECTION 100 Important Safety Instructions ...
Страница 9: ...SECTION 200 Features of the PFX Series Collector ...
Страница 11: ...SECTION 300 Receiving Inspection ...
Страница 13: ...SECTION 400 General Description ...
Страница 15: ...SECTION 500 Specifications ...
Страница 26: ...26 ROBOVENT PFX SERIES OWNER S MANUAL ...
Страница 27: ...SECTION 600 Installation ...
Страница 29: ...SECTION 700 Operation ...
Страница 31: ...ROBOVENT PFX SERIES OWNER S MANUAL 31 SECTION 800 Standard Maintenance and Filter Change Maintenance ...
Страница 35: ...SECTION 900 VFD Maintenance Procedure ...
Страница 38: ...38 ROBOVENT PFX SERIES OWNER S MANUAL ...
Страница 39: ...ROBOVENT PFX SERIES OWNER S MANUAL 39 SECTION 1000 Motor Greasing Guide ...
Страница 48: ...48 ROBOVENT PFX SERIES OWNER S MANUAL ...
Страница 49: ...ROBOVENT PFX SERIES OWNER S MANUAL 49 SECTION 1100 Troubleshooting ...
Страница 51: ...ROBOVENT PFX SERIES OWNER S MANUAL 51 ...