16
−
FULL POWER SWITCH
Select the voltage using the FULL
POWER SWITCH in accordance with the
electrical appliance.
Refer to
TABLE 2
.
120V 120V
240V
Change the FULL POWER SWITCH
after turning the no-fuse breaker to
"OFF".
[
CAUTION
]
GFCI RECEPTACLE
After starting the engine, check the GFCI for proper functioning by the following
test procedure.
■
Push blue TEST button, The red RESET button will pop out exposing the word
TRIP. Power is now off at the outlets protected by the GFCI, indicating that the
device is functioning properly.
■
If TRIP dose not appear when testing, do not use the generator. Call a
qualified electrician.
■
To restore power, push RESET button.
If the RESET button pops out during operation, stop the generator
immediately and call a qualified electrician for checking generator and
the appliances.
WARNING
NOTE :
Voltmeter always indicates the lower voltage whichever the FULL POWER
SWITCH is set.
TABLE 2
Switch position
Lower Voltage Receptacle
Higher Voltage Receptacle
120V
Activated full rated output
N.A
120/240V
Activated half of rated output
Activated full rated output