Two Stage Systems

A 2nd stage is a second or additional system that
will provide extra heating or cooling.  When a
2nd stage is operating the display will show the
number 2 by the heat/cool icons.

A temperature differential (default value is 2.0  °F or 1.0 °C) and time
delay (default value 20 minutes) control the 2nd stage cycle.

Operation of the 2nd stage begins when:

• The room temperature changes from the setpoint by the sum of the

1st and 2nd stage differential settings.

• The first stage has been on for the specified delay time, but the

heating/cooling demand has not yet been met.

Three Stage Systems

A 3rd stage is a third or additional system that will
provide extra heating in heat pump applications.
When a 3rd stage is operating the display will
show the number 2 and E by the heat icon.

A time delay (default value 20 minutes) controls the 3rd stage cycle.
This time delay starts when the second stage turns on.

Backlit Display

This thermostat is equipped with a backlight to make viewing the display

easy.  Press the 

button to activate the backlight.  The backlight will

turn off after 10 seconds of inactivity.  If the thermostat is wired to have
the backlight stay on all the time the night light can be turned on/off in
the settings menu.

Automatic Shut-Down

The thermostat will not display the room temperature if the temperature
goes higher than 99 °F (37 °C) or lower than 32 °F (0 °C).

The display will show HI or LO. The thermostat continues to control
heating and cooling and will resume the display of real time information
when the room temperature is back inside the display’s range.

Setting The Fan To ON, AUTO or CIRC

The fan has 3 settings: On, Auto, or Circ. Press the 

button to switch

among the three.

ON:

The fan is on constantly.  The status of the heating/cooling
equipment has no effect on the fan.

AUTO: Whenever there is a call for heating or cooling the fan will turn on.

CIRC: The fan operates in a cycle of on for 10 minutes and off for 20

minutes.  Whenever there is a call for heating or cooling the
cycle stops and the fan responds to the call.  The fan circulation
resumes when the call for heating or cooling is satisfied.

9

Содержание RS4220C

Страница 1: ...Circulating Fan Worry Free memory retention Easy change battery Large back lit display Filter change reminder Low battery indicator Fahrenheit and Celsius displays Dual power Adjustable 1st stage temp...

Страница 2: ...and national building and electrical codes and ordinances Do not short jumper across terminals on the gas valve or at the system control to test installation This will damage the thermostat and void...

Страница 3: ...moved If 24V AC is not present the thermostat runs on batteries only and THE SYSTEM WILL NOT OPERATE Replace batteries immediately Replace batteries if leaving thermostat unattended for more than 30 d...

Страница 4: ...capability for multi stage heat pump systems To determine if your system is capable of using emergency heat contact your contractor Use the button to enter the EMER mode An E will be displayed with t...

Страница 5: ...ses flashing item HEAT COOL Toggles through OFF HEATING COOLING and AUTO If configured as HP then emergency heat is also displayed Changing the User Settings When and are pressed at the same time the...

Страница 6: ...erates with the first stage to control a second heating cooling system This number will be added to the first stage differential See Two Stage Systems If the first stage is running too often lower the...

Страница 7: ...ailable only when auto changeover is enabled Hi High Heat Limit This is the highest allowed heating setpoint The user will not be allowed to set a heating setpoint higher than this value Note High Hea...

Страница 8: ...the same time and hold them in for 5 seconds You will be asked for a 2 digit password 2 The digits are set using the and buttons to progress through 00 to 99 Press the to move to the next digit Press...

Страница 9: ...acklight to make viewing the display easy Press the button to activate the backlight The backlight will turn off after 10 seconds of inactivity If the thermostat is wired to have the backlight stay on...

Страница 10: ...e differential See Changing Scale Clock Mode Differential Filter Hours Short Cycle or Offset section System fan does not operate properly Move fan option switch to either gas or electric to match syst...

Страница 11: ...Repair or replacement as provided under this warranty is the exclusive remedy of the consumer Invensys Controls shall not be liable for any incidental or consequential damages for breach of any expres...

Страница 12: ...12 NOTES 352 00058 001 Rev B 515 South Promenade Avenue Corona CA 92879 1736 United States of America www invensyscontrols com 2008 Invensys Controls 2 08...

Страница 13: ...s tracas Remplacement facile de la pile Grand cran d affichage r tro clair Rappel de changement de filtre Indicateur de d charge de la pile Affichage en Centigrade ou en Fahrenheit Alimentation double...

Страница 14: ...avec les r glements et codes de construction et les r glements et codes lectriques en vigueur Ne court circuitez pas avec un cavalier les bornes au niveau du robinet de gaz ou du contr le du syst me...

Страница 15: ...iles et LE SYST ME NE FONCTIONNERA PAS Changez imm diatement les piles Changez les piles si vous laissez le thermostat sans surveillance pendant plus de 30 jours Description g n rale L affichage du th...

Страница 16: ...et RS4320C ont une capacit de chauffage d urgence pour les syst mes multi tag s avec thermopompe Pour savoir si votre syst me est capable d utiliser le chauffage d urgence contactez votre entrepreneu...

Страница 17: ...qui clignote CHAUFFAGE CLIMATISATION HEAT COOL Permet de passer de l arr t au chauffage la Climatisation et au mode automatique OFF HEATING COOLING AUTO S il est configur comme thermopompe HP le chauf...

Страница 18: ...out au diff rentiel du premier tage de fonctionnement Voyez Syst mes deux tages Si le premier tage du syst me s allume trop souvent diminuez cette valeur Ceci allumera le deuxi me tage pour aider le p...

Страница 19: ...st grande plus la temp rature ambiante pourra varier Il peut s agir du chaud au froid ou du froid au chaud Uniquement disponible quand l Inversion automatique est activ e Hi Limite Haute de chauffage...

Страница 20: ...tisation qualifi CL talonnage Modifie la temp rature affich e par rapport la temp rature r elle par 3 3 degr s et par incr ments d un degr Une augmentation de l talonnage de 2 fera afficher par le the...

Страница 21: ...porisation la valeur par d faut est de 20 minutes contr le le cycle du 2 me tage Le 2 me tage d quipement s allume quand La temp rature de la pi ce s carte de la valeur de r glage par la somme des val...

Страница 22: ...ateur a 3 r glages On Auto ou Circ Appuyez sur pour passer d un r glage l autre ON Le ventilateur fonctionne constamment Le mode de l quipement de chauffage et de climatisation n a aucun effet sur le...

Страница 23: ...r changer les valeurs chelle horloge diff rentiel heures du filtre cycle court ou talonnage Le ventilateur du syst me ne fonctionne pas correctement R glez le commutateur du ventilateur sur l option g...

Страница 24: ...co t de la d pose et de la repose du thermostat La r paration ou le remplacement pr vus par cette garantie constituent le seul rem de pour le consommateur Invensys Controls ne sera pas responsable des...

Отзывы: