8
Input Power:
120/208-240V AC 50/60 Hz (+10,-15%)
Power Consumption:
6 VA max
Defrost termination switch (terminal G) input impedance to terminal C: 85k
Ω
+/- 5%
Operating Voltage:
120V AC (+10%, -15%) @ 50/60Hz
208V AC to 240V AC (+10%, -15%) @ 50/60Hz
NOTE: There are no user-required adjustments to switch between the high and low voltage.
Ambient Operating Conditions:
-40°F to 131°F (-40°C to 55°C); 0 to 95% RH (non-condensing)
NOTE: While the display is not harmed at temperatures as low as -40°C, it is not visible at -30°C and below. The display
is visible when the ambient temperature is above -30°C.
Storage Temperature:
-40°F to 140°F (-40°C to 60°C)
Outside Dimensions:
Individual Unit:
4.40”W x 7.82”H x 3.80”D
Individual Unit (in shipping box):
4.75”W x 8.875”H x 4.75” D
Individual Case Shipping Weight:
3.2 lb
Agency Approvals:
Listed Product – Models 9045-00 and 9145-00
Recognized Component – Models 9045-00M and 9145-00M
Ratings:
9145
Terminal A:
15A resistive @ 120V AC to 240V AC
1/4HP @ 120V AC, 1/2HP @ 208V AC to 240V AC
Terminal B:
30A resistive @ 120V AC to 240V AC
1HP @ 120V AC, 2HP @ 208V AC to 240V AC
Terminal E:
30A resistive @ 120V AC to 240V AC
1HP @ 120V AC, 2HP @ 208V AC to 240V AC
9045
Terminal A:
30A resistive @ 120V AC to 240V AC
1HP @ 120V AC, 2HP @ 208V AC to 240V AC
Terminal E:
30A resistive @ 120V AC to 240V AC
1HP @ 120V AC, 2HP @ 208V AC to 240V AC
NOTE: SPST normally closed (SPST NC) relays assume the normally closed state when power is applied. When power is
lost, the relay will return to the de-energized (NO) state.