D
UAL
A
IR
®
H
EATING
AND
COOLING
U
NITS
I
NSTALLATION
O
PERATION
AND
S
ERVICE
M
ANUAL
38
16.4 Flue Fan
IT IS IMPORTANT THAT ONLY THE CORRECT FLUE FAN SPECIFIED FOR EACH MODEL TYPE IS
USED WHEN REPLACING THESE ITEMS.
Carry out a commission after working on or changing a flue fan.
See Page 25, Section 12
.
Vent Box
Outlet
Gasket
Flue Fan
Vent Box
screws
Flue
Adapter
Flue Adapter
to Flue Fan
screws
Rear Panel
Hole
Disconnect
electrical connections
at plug in tabs.
Mounting Plate
to Vent Box
screws
Mounting
Plate
Gasket
Air Plate
Mounting Plate
to Flue Fan
screws
Vent Box
Gasket
Remove screws securing outlet
flange to the flue adapter.
Remove screws securing flue
fan mounting plate to vent box
Remove screws securing
mounting plate to fan.
Refit in reverse.
Use new gaskets.
Ensure sealed joints.
Ensure mounting plate orifice is
clear and not obstructed.
MODEL
75
90
100
115
Flue Fan
AO Smith
JFIG07INS
AO Smith
JFIG07INS
AO Smith
JFIG07INS
Torin DSF
146-052
077274
RG P/N
90710001
90710001
90710001
90710450
Air mm dia
97.0
103.6
110.5
152.4
Plate in dia
3.82
4.08
4.35
6
RG P/N
11011134
11011133
11011132
11011131