SECTION 14: V
ARIABLE
F
REQUENCY
D
RIVE
P
ROGRAMMING
F
OR
U
SE
W
ITH
CORAY-
67 of 85
14.2 Alterin
g
VFD Parameters For Use With CORAYVAC
®
Modulatin
g
Heatin
g
Control
Using the proced
u
re described
, alter the follo
w
ing
parameters:
*Depends on the VFD rated po
w
er
**VFD sho
u
ld be in modb
u
s mode
u
nless man
u
al mode is desired temporarily
***Parameter N
u
mber P14 set to 101
u
nlocks parameters P15-P53
Parameter
Number
Parameter Name
Factory Default
New Settin
g
P01
Maxim
u
m Freq
u
ency (Hz)
50.0
60.0
P02
Minim
u
m Freq
u
ency (Hz)
0.0
40.0
P03
Accel. Time (sec)
5
10
P04
Decel. Time (sec)
5
10
P07
Nominal Motor Voltage (V)
230*
(Motor Voltage)
P08
Rated Motor C
u
rrent (A)
4.8
Rated Motor C
u
rrent (from Motor Data Plate)
P09
Rated Motor Freq
u
ency (Hz)
50.0
Rated Motor Freq
u
ency (from Motor Data
Plate)
P12
Control Le
v
el
0.0
1
‐
Manual
Run
Mode
3
‐
Modbus
(internal
ramp
times)**
P14***
VFD Access Code
0.0
101.0
P36
Comm
u
nication Config
u
ration
-
VFD
Slave
Address
(1)
or
(2)
-
Modbus
RTU
baud
Rate
(9600)
-
Time
Out
(0)
Содержание Corayvac CRV-B Series
Страница 2: ......
Страница 4: ......
Страница 5: ......
Страница 6: ......
Страница 8: ......
Страница 73: ...SECTION 13 STARTING THE SYSTEM 65 of 85 FIGURE 48 Vacuum Reading ...
Страница 84: ...CRV SERIES INSTALLATION OPERATION AND SERVICE MANUAL 76 of 85 18 1 Troubleshooting Flow Chart ...
Страница 85: ...SECTION18 TROUBLESHOOTING 77 of 85 Troubleshooting Flow Chart ...
Страница 92: ...CRV SERIES INSTALLATION OPERATION AND SERVICE MANUAL 84 of 85 ...
Страница 93: ...SECTION 21 THE ROBERTS GORDON CORAYVAC LIMITED WARRANTY 85 of 85 2017 ...
Страница 94: ......
Страница 95: ......
Страница 96: ......