SECTION 14: VARIABLE FREQUENCY DRIVE PROGRAMMING FOR USE WITH CORAYVAC
®
MODULATING HEATING CONTROL
14.1 VFD Parameter Settin
g
s For Use With
CORAYVAC
®
Modulatin
g
Heatin
g
Control
The VFD parameters come
w
ith factory defa
u
lt set-
tings. The follo
w
ing parameter settings m
u
st be
changed. Settings can only be altered
w
hen the
p
u
mp motor is stopped.
Verify that there is po
w
er to the VFD (LCD display
w
ill
be on) and is set to off.
To o
v
erride the rotary disconnect s
w
itch inside the
VFD enclos
u
re, t
u
rn the sq
u
are rod
w
ith a
w
rench to
the ON position. In order to be able to close the co
v
er
of the disconnect, the rods need to be t
u
rned back to
the OFF position.
14.1.1
To enter the PROGRAM mode and access the
parameters, hold "OK"
u
ntil P01 appears.
Display reads "P01"
14.1.2
Use the arro
w
b
u
ttons to scroll to P14
(the factory set pass
w
ord is 0.0).
Press "OK" to enter pass
w
ord (101).
Once the correct pass
w
ord
v
al
u
e is entered, the dis-
play
w
ill read "P14",
w
hich indicates that the
PROGRAM mode has been accessed at the begin-
ning of the parameter men
u
(P01 is the first
parameter).
14.1.3
Use the arro
w
b
u
ttons to scroll to the desired
parameter n
u
mber. For ne
w
parameter settings
.
14.1.4
Once the desired parameter n
u
mber is fo
u
nd:
Press "OK" to display present parameter setting
(example setting is 20.0).
Use arro
w
b
u
ttons to change setting.
Press "OK" to store ne
w
setting and exit the
program mode.
14.1.5 To chan
g
e another parameter, press the
"OK" key a
g
ain to re-enter the PROGRAM mode
(the parameter menu will be accessed at the
parameter that was last viewed or chan
g
ed
before exitin
g
).
DANGER
Electrical Shock Hazard
Enclosure contains live electrical
components.
Programming must be done by a trained
technician only.
Replace cover before operating.
Failure to follow these instructions can result
in death or electrical shock.
Содержание Corayvac CRV-B Series
Страница 2: ......
Страница 4: ......
Страница 5: ......
Страница 6: ......
Страница 8: ......
Страница 73: ...SECTION 13 STARTING THE SYSTEM 65 of 85 FIGURE 48 Vacuum Reading ...
Страница 84: ...CRV SERIES INSTALLATION OPERATION AND SERVICE MANUAL 76 of 85 18 1 Troubleshooting Flow Chart ...
Страница 85: ...SECTION18 TROUBLESHOOTING 77 of 85 Troubleshooting Flow Chart ...
Страница 92: ...CRV SERIES INSTALLATION OPERATION AND SERVICE MANUAL 84 of 85 ...
Страница 93: ...SECTION 21 THE ROBERTS GORDON CORAYVAC LIMITED WARRANTY 85 of 85 2017 ...
Страница 94: ......
Страница 95: ......
Страница 96: ......