2 of 12

SECTION 1: INTRODUCTION

Your Safety is Important to Us!
This symbol is used throughout 
the manual to notify you of 
possible fire, electrical or burn 
hazards. Please pay special atten-
tion 

w

hen reading and follo

w

ing 

the 

w

arnings in these 

sections.

Installation, service and annual inspection of 
controller must be done by an electrician qualified in 
the installation and service of control systems for 
heating equipment.
Installation, service and annual inspection of heater 
must be done by a contractor qualified in the 
installation and service of gas or oil fired heating 
equipment.
Read this manual carefully before installation, 
operation, or service of this equipment.
The equipment must be applied and operated under 
the general concepts of resonable use and installed 
using best building practices.
This equipment is not intended for use by persons 
(including children) 

w

ith reduced physical, sensory or 

mental capabilities, or lack of experience and 
kno

w

ledge, unless they have been given supervision 

or instruction concerning use of the appliance by a 
person responsible for their safety.
Children should be supervised to ensure that they do 
not play 

w

ith the equipment.

For optimum heater performance and safe heating 
conditions, inspect and maintain heater(s) before 
every heating season and as necessary. Also, kno

w

 

and maintain heater clearances to combustibles, see 
heater Installation, Operation and Service Manual for 
further details. If you require additional manuals, con-
tact Roberts-Gordon at +44 (0)121 506 7700 or at 

www

.robertsgordon.co.uk.

1.1 Electrical Re

q

uirements

Failure to comply 

w

ith the installation instructions 

w

ill 

invalidate the limited 

w

arranty.

All 

w

iring must comply 

w

ith current 

w

iring regulations 

and any local regulations 

w

hich may apply. Al

w

ays 

s

w

itch off electrical supply to equipment and discon-

nect by removing plug before 

w

orking on equipment.

Equipment must be electrically grounded in accor-
dance 

w

ith local specifications and codes.

1.2 Check Installation Materials

Before proceeding 

w

ith installation of ROBERTS 

GORDON

®

 COMBAT

®  

HVE Fan, check the follo

w

ing 

points:

1.2.1 Control Options

Each HVE Fan has a built in thermostat that allo

w

s it 

to turn on 

w

hen ambient temperature at fan exceeds 

thermostat’s setpoint. In addition, HVE Fans can be 
used 

w

ith a number of different speed control 

options.

Control Options Specifications

DANGER

Electrical Shock Hazard

Disconnect electric before service.

Equipment must be properly 

g

rounded.

Failure to follow these instructions can 

result in death or electrical shock.

Model

WAC6

DP5

BJ8

Control Unit Capacity (No. of Fans)

HVE400

1

4

8

HVE450

N/A

1

2

HVE650

N/A

1

2

Manual On/Off

Yes

Yes

Yes

Manual Fan Speed Adjustment

Yes

Yes

No

Automatic Fan Speed Adjustment

No

No

Yes

Fans ‘ON’ Neon Indicator

Yes

No

No

Temperature Sensor Range

[°C]

N/A

N/A

0-40

Temperature Sensor Cable Length

[m]

N/A

N/A

10

Maximum Starting Current

[A]

3

10

20

Maximum Running Current

[A]

1.5

5

10

Содержание Combat HVE 400

Страница 1: ...heating equipment Improper installation adjustment alteration service or maintenance can result in death injury or property damage Read the Installation Operation and Service Manual thoroughly before installing or servicing this equipment Installer Please take the time to read and understand these instructions prior to any installation Installer must give a copy of this manual to the owner Owner K...

Страница 2: ......

Страница 3: ...tion 2 1 1 Electrical Requirements 2 1 2 Check Installation Materials 2 1 3 Safety Labels and Their Placement 3 SECTION 2 Specifications 4 2 1 Electrical Specifications 4 2 2 Fan Specifications 4 2 3 Dimension Data 4 SECTION 3 Critical Considerations 5 3 1 Location and Suspension 5 3 2 Minimum Required Installation Clearances 5 SECTION 4 Installation 6 4 1 Preparation 6 4 2 Electrical Supply 7 SEC...

Страница 4: ......

Страница 5: ... 3 Mounting Hole Layout 6 Figure 4 Suspension Methods 7 Figure 5 BJ8 Fan Control Wiring Diagram 8 Figure 6 DP5 Fan Control Wiring Diagram 8 Figure 7 WAC6 Fan Control Wiring Diagram 9 Figure 8 HVE Fan Without Speed Control Wiring Diagram 9 Figure 9 Internal Components Diagram 12 ...

Страница 6: ......

Страница 7: ...intained in accordance with these instructions These instructions refer to appliances designed to operate in the European Union Appliances designed for other countries Non European Union are available on request This appliance must be installed in accordance with the local and national codes in force and used only in a sufficiently ventilated space as specified in these instructions Before install...

Страница 8: ...er clearances to combustibles see heater Installation Operation and Service Manual for further details If you require additional manuals con tact Roberts Gordon at 44 0 121 506 7700 or at www robertsgordon co uk 1 1 Electrical Requirements Failure to comply with the installation instructions will invalidate the limited warranty All wiring must comply with current wiring regulations and any local r...

Страница 9: ...ement Product safety signs or labels should be replaced by product user when they are no longer legible Please contact Roberts Gordon Europe Limited or your ROBERTS GORDON independent distributor to obtain replacement signs or labels FIGURE 1 Label Placement Description Part Number Logo Label 91040030 Shock Hazard Label 91008001 Address Label 91040006 Wiring Diagram Label 91040400 Terminal Connect...

Страница 10: ...F 3 8 12 Electrical Supply 230 V 50 Hz 1 Ø Starting Current A 1 5 6 4 6 0 Running Current A 1 0 1 6 2 6 Noise Level 3m NR dB A 55 68 70 Maximum Ambient Temperature C 60 65 40 Thermostat Recommended Minimum Setting C 15 15 15 Maximum Setting C 30 30 30 Recommended Minimum Setting above room temperature C 3 3 3 Model HVE 400 HVE 450 HVE 650 A Depth mm 300 305 284 B Casing Width mm 527 610 790 C Over...

Страница 11: ... minimum of 10 mm diameter mild steel Four suspension points M10 nuts are located on top of fan Mounting hardware must be sufficient to support fan weight as listed in the dimension data on Page 4 Sec tion 2 3 Must be installed in a manner which allows access to all serviceable components 3 2 Minimum Required Installation Clearances Clearances around fan must be as indicated on Page 4 Section 2 3 ...

Страница 12: ...above See Page 7 Figure 4 Drop rods must be a minimum of 10 mm diameter mild steel Four suspension points M10 nuts are located on top of fan Mounting hardware must be sufficient to support fan weight as listed in the dimension data on Page 4 Sec tion 2 3 Must be installed in a manner which allows access to all serviceable components 4 1 2 Suspension Mounting Model HVE 400 HVE 450 HVE 650 A mm 493 ...

Страница 13: ...z single phase supply connected to terminals L N and Earth Polarity L N must be correct The voltage between neutral and earth should be 0 and never exceed 15 volts All fans and controls must be correctly earthed All external wiring must comply with relevant IEE and local regulations and be carried out by a qualified electrician ...

Страница 14: ...aced it must be replaced with wiring material having a temperature rating of at least 105 C and 600 V FIGURE 5 BJ8 Fan Control Wiring Diagram FIGURE 6 DP5 Fan Control Wiring Diagram DANGER Electrical Shock Hazard Disconnect electric before service More than one disconnect switch may be required to disconnect electric to the unit Failure to follow these instructions can result in death or electrica...

Страница 15: ...SECTION 5 TYPICAL EXTERNAL WIRING DIAGRAMS 9 of 12 FIGURE 7 WAC6 Fan Control Wiring Diagram FIGURE 8 HVE Fan Without Speed Control Wiring Diagram ...

Страница 16: ...n trol over HVE Fan speed See Page 8 Section 5 wir ing diagrams to utilize HVE Fan thermostat In this case each fan will turn on when temperature at fan exceeds thermostat setpoint The fans speed will be determined by speed set on controller To disable HVE Fan thermostat wire line power to terminal 1 rather than terminal L In this configuration fan con trol ON OFF switch will be used to turn HVE F...

Страница 17: ... manual Failure to follow these instructions can result in death electric shock injury or property damage Explosion Hazard DANGER Electrical Shock Hazard Fire Hazard DANGER Electrical Shock Hazard Disconnect electric before service More than one disconnect switch may be required to disconnect electric to the unit Failure to follow these instructions can result in death or electrical shock ...

Страница 18: ...ON OPERATION AND SERVICE MANUAL 12 of 12 FIGURE 9 Internal Components Diagram Model Description Part Number HVE 400 Axial Fan 400 mm A263A HVE 450 Axial Fan 450 mm A268A HVE 650 Axial Fan 650 mm A269 N A Thermostat 230 V C2334B ...

Страница 19: ......

Страница 20: ......

Отзывы: