SECTION 3: CRITICAL CONSIDERATIONS
3.1 Location and Suspension
All models:
• Must be installed indoors.
• Must be installed in a level position.
• Fan must be suspended from above (
See Page 7,
Figure 4
). Drop rods must be a minimum of 10
mm diameter mild steel. Four suspension points
(M10 nuts) are located on top of fan. Mounting
hard
w
are must be sufficient to support fan
w
eight
as listed in the dimension data
on Page 4, Sec-
tion 2.3
.
• Must be installed in a manner
w
hich allo
w
s
access to all serviceable components.
3.2 Minimum Re
q
uired Installation Clearances.
Clearances around fan must be as indicated
on Page
4, Section 2.3
to ensure access for servicing and cor-
rect operation.