SECTION 16: R
EMOVAL
AND
R
EPLACEMENT
P
ARTS
39
16.5 Pressure Switch
Pull off 3 way connector. Spring open plastic clips of
mounting cradle. Replace with correct type of
pressure switch for model. The pressure switches
are colour coded for each pressure setting.
C
ar
b
on
M
ono
x
ide
H
a
z
ard
U
se
correct
pressure
switch
specified
for
each
model.
U
se
of
incorrect
pressure
switch
could
cause
unsafe
condition.
Failure
to
follow
these
instructions
can
result
in
death
or
serious
injury.
WARN
I
NG
Carry out a commission after working on or
changing a pressure switch.
See Page 24, Section
11
.
Pressure
Switch
CTU-22
CTU-30
CTU-35
CTU-40
CTU-50
CTU-60
CTU-75
CTU-90
CTU-100
CTU-115
RG P/N
90439801
90439810 90439804 90439803 90439810 90439802 90439811 90439807 90439811 90439807
Colour
Code
pink
grey
white
grey
grey
yellow
grey
brown
grey
brown
Set Point
mbar
0.57
0.92
1.17
1.02
0.87
0.80
1.79
1.69
1.79
1.69
in wc
0.23
0.37
0.47
0.41
0.35
0.32
0.72
0.68
0.72
0.68