roal RCB1200 Скачать руководство пользователя страница 13

 

 

13 

 

 

Reverse Current Protection (RCP) 
The standard output modules use synchronous rectification in the output stages to achieve high efficiency and, as a result, the 
outputs can both source and sink current. The sink current is internally limited to approximately -6% of the maximum rated 
current. However, in applications where the output modules are connected to external power sources, such as batteries or 
other power supplies, certain precautions must be observed to prevent damage to the unit. 

 The outputs should never be directly connected to to external power sources without some form of reverse current protection 
such as an external diode or controlled MOSFET. If protection is not used, large reverse currents which will ultimately result in 
damage to the unit will occur, especially when the AC mains is disconnected.  

Output Module Average and Peak Power  
All modules have an average and peak power rating. The average power of each unit must at all times remain below its 
specified limit. However, each output can deliver up to 150% of its average power rating for a maximum of 5 seconds at 50% 
duty-cycle, subject to the current limit not being exceeded and subject to the overall average power drawn from that section 
being less than the specified average power rating (including any input de-rating due to temperature or line voltage). The 
available peak power is a function of the output voltage and maximum current for each module. Full peak power is only 
possible when the output voltage is adjusted to V

MAX

 and the maximum current is drawn from the module. Note that both 

average and peak power ratings are subject to the same temperature de-rating as the input section (de-rate by 2.5% per °C 
above 50°C), but are not subject to any line de-rating. 

 

Start up and Shut down 
All outputs are designed to have a regulated monotonic start-up 
with a rise time of approximately 3 ms as shown in the diagram 
right. The power good signal stays low until the voltage exceeds 
the power good threshold (

≈90%). 

 

 

Where multiple output modules are used, in each section, the 
default start up scheme is ratio-metric with all outputs starting 
at the same time as shown in the diagram right. External 
control circuits may be used to implement tracking or 
sequenced start up if necessary. 

 

The outputs are not designed to start into a pre-biased load and 
may discharge any externally capacitance before beginning to 
ramp the output voltage up in the normal way. 

 

At shut-down the outputs enter a high impedance state. Where 
no external load is present it may take some time for the 
voltage to decay. When driving inductive loads, care must be 
taken to limit the voltage at the output terminals so as to 
prevent damage to the unit.   

 

 

Synchronisation 
All output modules in the same section of the power unit are synchronised. The typical operating frequency is 260 kHz and 
paralleled/seriesed modules will not produce beat frequencies. 

 

DISTRIBUTED BY TEXIM EUROPE

Содержание RCB1200

Страница 1: ...r to their respective output sections Each output section consist of four slots where can be plugged a 150 W fully isolated output module Each section offers as a standard a 5 V 200 mA isolated bias s...

Страница 2: ...IGNALS 10 OUTPUT MODULE OPERATION 12 ADVANCED OUTPUT MODULE FEATURES 15 OUTPUT MODULES IN SERIES 18 OUTPUT IN PARALLEL CONFIGURATION 19 MECHANICAL DIMENSIONS AND MOUNTING 23 MECHANICAL CONNECTORS AND...

Страница 3: ...and is a useful guide in identifying the optimal configuration for every application Output Module Nominal Voltage Rated current Voltage Adjustment Load Regulation Line Regulation OVP Output Power A 5...

Страница 4: ...ng appropriately Avoid excessive back pressure in the general system or when using ducting to navigate hot air out of the system Earth terminal marking To comply with the requirements of UL60950 1 EN6...

Страница 5: ...to an appropriate DC voltage whilst providing protection from AC line disturbances and preventing excessive EMI emissions and current harmonics The integrated EMI filters attenuate high frequency cur...

Страница 6: ...fficient zero voltage switching circuits ZVS are used to drive the medically isolated transformers from the hold up capacitors The output modules of each section connect to their respective transforme...

Страница 7: ...for typically 100 ms after the output modules have turned off Hold up For short line disturbances 20 ms the output voltages will not be affected However the ACOK signal may still go low to warn that...

Страница 8: ...can be calculated using the following conditional equations Equation for line de rating If Vin 120 VRMS Pout Prated Line de rating factor Prated 1 0 0083 120 Vin Otherwise Pout Prated Equation for tem...

Страница 9: ...Estimate the efficiency of an RCB1200 AABCDDDD at 160 VRMS input 100 W load on each output of the first section and 140 W on each output of the second section 1 Define load efficiencies for each outpu...

Страница 10: ...conditions may cause one or both power supply s sections to latch off which will disable their 5V bias supply Over temperature of any stage of the section Over voltage on the correspondent output Int...

Страница 11: ...provides four inhibit inputs to disable each of its output module individually and a fifth global inhibit input GINH to inhibit all modules of the correspondent section simultaneously Each inhibit inp...

Страница 12: ...xcessive output voltages This is implemented as a fixed voltage threshold VOVP in the table above and if the output voltage exceeds this threshold the correspondent section of the power unit will be l...

Страница 13: ...a function of the output voltage and maximum current for each module Full peak power is only possible when the output voltage is adjusted to VMAX and the maximum current is drawn from the module Note...

Страница 14: ...type Transient Response The RCB1200 output modules have been especially designed to have high reliability and to achieve this all electrolytic capacitors have been eliminated from the design Due to th...

Страница 15: ...nit off Alternatively by manually adjusting the output voltage to less than 1 3 rd of the OVP voltage ensures that OVP can never be tripped by remote voltage control Care must be also taken to ensure...

Страница 16: ...on the current limit When using an output module as a modulated current source the output voltage should be manually adjusted to the maximum that will be required by the application and this will be...

Страница 17: ...in each case An internal circuit measures the voltage between S to V and S to V when this voltage exceeds the thresholds specified in the datasheet the output voltage is reduced to benign levels Durin...

Страница 18: ...anced V control and I control functions as described earlier However individual control of each module can be complex as the various control terminals are referenced to the positive output of the prec...

Страница 19: ...inal of the second module 2 and adjust the second module 2 until the voltmeter reads 0 000 volts 4 Repeat step 3 for the remaining modules always using the positive terminal of the first module 1 as t...

Страница 20: ...imately 6 of the maximum rated current for each module The current output signal Ictrl can still be used to measure the output current but it must be scaled by N where N is the number of paralleled mo...

Страница 21: ...bly rated diode or controlled MOSFET must be used on each output to prevent a device failure from causing a system failure However the diode introduces voltage drops between the supply and the load th...

Страница 22: ...xactly as with a stand alone module The same scheme applies when the output modules are paralleled across the two RCB1200 sections It is not recommended to use remote voltage current programming in no...

Страница 23: ...4 00 mm max including chassis OUTPUT MODULES X 16 Screw type M3X5 C Sink Pozidriv Stainless steel Tightening torque Tighten to 0 65 Nm Penetration depth Defined by screw CHASSIS X 4 Screw type M3X5 C...

Страница 24: ...2 1 J2 2 2 00 mm 0 079 in 12 circuits housing with locking ramp or any direct equivalent Crimp terminal 24 30 AWG gold finish or any direct equivalent Molex 0511101260 0503948051 Output Power J3 J4 Qu...

Страница 25: ...the power supply Remove the unit from the system if there has been previously installed WARNINGS Leave the unit to stand for a minimum of 3 minutes after removing all power and other connections from...

Страница 26: ...e the screws that hold an OP while leaving tightened BP s ones Step 4 Once all the screws that hold the OPs has been removed the next step is opening the lid by rotating it around the two pins that bi...

Страница 27: ...s header must be plugged directly into the mating connector on the unit printed circuit board PCB To do so simply align the connector and push the OP properly down securing it in the notch at the back...

Страница 28: ...re closing it To facilitate operations the BPs should be assembled before the OPs As evidence of power unit proper closing output modules PCBs must be properly housed in the notches and in the slots o...

Страница 29: ...led by a tamper evident security label Removing it makes accessible high voltage parts exposing a operator to electric shock danger Any alteration affecting the label will void the warranty on the Pow...

Страница 30: ...and technical personnel Always remove the power before handling the unit During operation the external surface of the unit can become hot Leave to stand for 10 minutes to allow the unit to cool down b...

Страница 31: ...ld be separated as much as possible Output power and sense cables should be twisted pairs and routed parallel to each other Do not twist sense and power cables together All cables lengths and loop are...

Страница 32: ...hours Reliability data is collected on an ongoing basis Please contact ROAL Electronics or your distributor for the most up to date reliability data or to get reliability prediction for a specificall...

Страница 33: ...T 45 88 20 26 30 F 45 88 20 26 39 E nordic texim europe com Zuiderlaan 14 bus 10 B 1731 Zellik T 32 0 2 462 01 00 F 32 0 2 462 01 25 E belgium texim europe com Martin Kollar Strasse 9 D 81829 M nchen...

Отзывы: