RM Cylinders Intercyl Скачать руководство пользователя страница 8

ISSUE 2016 Rev 1 - Installation Manual 

RM Cylinders 

 

the drain point. For electrical powered models where off peak tariffs are being used, then secondary circulation is not recommended.  
 
All Indirect Coils 
 
22mm primary coils of coil-in-coil design are fitted to all indirect models incorporating 22mm compression fittings for easy connection. These 
coils are suitable for both open vented and sealed system applications up to a maximum of 6.0bar and must be positively pumped. 
Ensure air release valves are used at high points such as the entry/exit points of the coil. Either connection may be used as the flow or return 
without compromising performance. 
 
Maximum operating temperature of primary coils under normal circumstances is 85° C. 
 
Ensure corrosion inhibitor compatible with stainless steel coils is used in the primary circuit. 
 
Connection to a Boiler 
 
Gas, oil and electric powered boilers may be used but must be under effective thermostatic control and employ high limit control. 
Uncontrolled heat sources must not be used. 
 
The two port valve provided must be installed in the primary flow. The dual control/high limit thermostat provided fits onto the probe pocket 
positioned just above the coil connection and wired back to the two port valve to create both temperature control and primary isolation should 
the high temperature limit control be triggered - 

See wiring diagrams. 

 
Connection too Solar 
 
For solar, connect to the solar coil allowing for air removal. The temperature sensor controlling the solar input connects into the probe pocket 
directly above the solar coil connection using the cable grommet provided to ensure stable mounting. The single high limit thermostat installs 
into the probe pocket at high level on the cylinder and wires back to the solar pump to prevent further input when triggered. 
 
When connecting a twin coil cylinder to a boiler and solar thermal system the upper coil connects to the boiler and the lower to the solar 
system.  
 
Where a twin coil cylinder is being heated by two boilers, the upper coil should utilise the dual control/high limit thermostat as described in 
Connection to a Boiler section. For connection to the lower coil you will require a further two port valve and a single control thermostat 

(both

 

available from RM Cylinders)

 to ensure a legal installation. The single control stat inserts into the probe pocket directly above the lower coil 

and the single high limit stat into the probe pocket at upper level on the cylinder body. Wired together and back to the two port valve 
connected into the primary flow this will provide temperature control and high temperature isolation of the primary heat source. 
 
Wiring 
 
A competent electrician in accordance with the latest I.E.E. wiring regulations should complete any electrical wiring required.  
 
Typical Wiring – S Plan, 1 zone 
Typical Wiring – S Plan, 2 zone 
Typical Wiring – Y Plan 
 
See Wiring Plans section (Pages 18 - 19). 
 
Immersion Heater 
 
As a requirement of the Building Regulations, the immersion heaters are fitted with a non-self setting thermal cut-out, in addition to the 
normal control thermostat. The immersion heaters have a 1¾” BSP thread. They are of a low noise Incoloy construction and rated at 3kW at 
240V. Replacement immersion heaters should be purchased via ourselves otherwise your guarantee may be affected. 
 
The ‘O’ ring on the head of the immersion heater should be correctly positioned and lubricated before fitting. Screw in hand-tight until almost 
sealed, and then gently tighten, as the ‘O’ rings will seal easily. The electrical supply to each immersion heater) must be fused at 13A via a 
double pole isolating switch to BS 3456. The 3kW immersion heaters must be wired in 2.5mm heat resistant cable – failure to comply with 
this can cause nuisance tripping and we will be unable to support your installation until this has been addressed. 
 
Do not operate the immersion heaters until the unit is full of water. If any sterilization liquid is in the cylinder do not operate the immersion 
heaters as this will cause premature failure.  
 
In commercial or heavy duty installations, where constant usage and reheating is required, or where an external programmer designed for 
immersion heaters is not present, Titanium immersion heaters must be fitted in order to comply with the warranty. 
  

Содержание Intercyl

Страница 1: ...INSTALLATION MANUAL Issue 2016 Rev 1 Tested to BS EN 12897 2006 FOR MORE INFORMATION GO TO WWW RMCYLINDERS COM Note By installing this product you agree to be bound by our Conditions of Sale found wi...

Страница 2: ...2 Product Specifications 3 General Installation and Commissioning 6 Service and Maintenance 9 Fault Finding 10 Benchmark Commissioning Checklist 15 Service Record 16 User Guide and Customer Service 17...

Страница 3: ...ISSUE 2016 Rev 1 Installation Manual 3 RM Cylinders 2...

Страница 4: ...responsibilities on both manufacturers and installers The purpose is to ensure that customers are provided with the correct equipment for their needs that it is installed commissioned and serviced in...

Страница 5: ...a flat base capable of supporting the weight of the cylinder when full The minimum recommended cupboard size is 650mm square Nominal diameter of cylinder is 545mm Areas that are subject to freezing sh...

Страница 6: ...0 15MPa 1 5 bar working pressure and a 20 litres per minute flow rate Where mains inlet pressures Hot Outlet Non Return Valve Pump Temperature and Pressure Relief Valve Secondary Return Boiler Flow B...

Страница 7: ...n order to service the inlet control set Ensure the directional flow arrow on the inlet control set follows the required flow of water See schematic diagram A balanced cold supply is necessary if ther...

Страница 8: ...ld utilise the dual control high limit thermostat as described in Connection to a Boiler section For connection to the lower coil you will require a further two port valve and a single control thermos...

Страница 9: ...700 Specification for the design installation testing and maintenance of services supplying water for domestic use within buildings and their curtilages From the tundish pipework should terminate in a...

Страница 10: ...of water is drained from the unit Open the hot tap closest to the unit and open the draining tap Note Water drained off may be hot SERVICE AND MAINTENANCE Servicing must be carried out annually and s...

Страница 11: ...erating tap outlet Insecure Pipework Increase the number of pipe clips External works to public mains Wait for works to be completed Reduced water flow Debris from water mains Strip cleanorreplace Inl...

Страница 12: ...DING Is water running from the Tundish Is the water being discharged hot Tundish YES NO Do you have pressure YES NO No fault See the flow chart for T P Valve See the flow chart for Inlet Control Group...

Страница 13: ...mperature Pressure Relief Valve YES NO Do you have pressure YES NO No fault with the T P No fault with the T P Replace T P if required Replace T P if required Check temperature setting of the cylinder...

Страница 14: ...st fails replace Dual Stat Test Stat continuity Reset Limit Stat Test Dual Stat continuity Is there power to the Element Thermostat Has the thermostat tripped Does the Immersion Heater work Find corre...

Страница 15: ...RM Cylinders ENERGY CUT OUT FAULT FINDING Is the Cut Out Thermostat working Test Stat continuity Energy Cut Out Thermostat NO YES Reset Limit Stat No fault with the Thermostat If test fails replace Du...

Страница 16: ...incoming static cold water pressure at the inlet to the system Has a strainer been cleaned of installation debris if fitted Is the installation in a hard water area above 200ppm If yes has a water sca...

Страница 17: ...VICE 9 Date Engineer Name Company Name Telephone Number Signature SERVICE 8 Date Engineer Name Company Name Telephone Number Signature SERVICE 7 Date Engineer Name Company Name Telephone Number Signat...

Страница 18: ...uty installations where constant usage and reheating is required titanium immersion heaters must be fitted to comply with the warranty Exclusions 16 The effect of scale build up on the unit or its com...

Страница 19: ...1 Installation Manual 3 RM Cylinders TYPICAL WIRING S PLAN 1 ZONE TYPICAL WIRING Y PLAN COLOUR CODES W WHITE G GREY BL BLUE G Y GREEN YELLOW L LIVE N NEUTRAL C COMMON SL SWITCHED LIVE E EARTH 3 Port M...

Страница 20: ...ISSUE 2016 Rev 1 Installation Manual 3 RM Cylinders TYPICAL WIRING S PLAN 2 ZONE COLOUR CODES W WHITE G GREY BL BLUE G Y GREEN YELLOW L LIVE N NEUTRAL C COMMON SL SWITCHED LIVE E EARTH 19...

Страница 21: ...ll the goods to third parties in the normal course of business In this respect the Buyer shall act in the capacity of the Companies commission agent and the proceeds of such sale 6 6 1 shall be held i...

Страница 22: ...ISSUE 2016 Rev 1 Installation Manual 3 RM Cylinders NOTES 21...