background image

A dedicated circuit breaker must be provided within 

close proximity to the LD5200 and be clearly marked as 

the LD5200’s disconnecting device.  Engage a certified 

electrician to run a 110 or 220 VAC power supply from a 

dedicated circuit breaker (following all state and local electrical codes)

 

and conduit to the device to support your cabling needs.

Install the Sensing Cable

Leader cable is used to connect sensing cable to the LD5200, 

since sensing cable cannot connect directly to the controller.  

1.  Insert the four stripped wires of the leader cable into the 

appropriate slots in the 4-pin terminal block connector - 

from left to right: white, black, green, and red.  Tighten 

the screws on the terminal block connector to secure the 

leader cable.  Thread the leader cable through a knockout 

on the bottom of the enclosure and plug the terminal 

block connector into TB2.

2.  Unscrew the EOL from the end of the leader cable.

3.  Attach the first length of sensing cable to the leader cable.

4.  Route the sensing cable according to your cable layout diagram.

5.  Secure the EOL to the unoccupied end of the sensing cable.

Apply Power to the LD5200

1.  Route the power supply through a knockout, into the enclosure, to the power 

input terminal block.  Insert the wires as noted on the enclosure’s backplate: 

Neutral - Line- Ground.  Ensure all connections are correct and the screw 

terminals are tightened and secure.

2.  Apply power.  The device will boot.  Once diagnostics are complete, the 

LCD displays the Main Menu.  No alarms should be present.  If an alarm is 

present, consult the Troubleshooting section of the LD5200 User Guide.

Configure Communications

Use the LCD touch screen on the 

front of the LD5200 to configure 

communications.

1.  Push the Setup button on the 

LD5200’s LCD.

2.  You’ll be prompted to enter a 

password.  By default, there is no 

password configured.  Leave the 

password field blank and press the 

enter button.

3.  Once you’ve accessed the Setup 

Menu, press the Down button 

until the System Settings option is 

highlighted in blue.  Press the Select 

button to access the System Setup 

Menu.

© Raymond & Lae Engineering, Inc. 2011. All rights reserved. RLE® is a registered trademark and Seahawk™, Falcon™,  and Raptor™ are 

trademarks of Raymond & Lae Engineering, Inc. The products sold by Raymond & Lae Engineering, Inc. are subject to the limited warranty, limited 

liability, and other terms and conditions of sale set forth at http://rletech.com/RLE-Terms-and-Conditions.html.

Installation Supplies

Included with the LD5200

LD5200 controller in wall-mount enclosure

15 foot (4.57m) leader cable

End-of-line terminator (EOL)

Available from RLE, Sold Separately

SeaHawk sensing cable - up to 10,00 feet (3048m) of conductive fluid sensing 

cable or 7,000 feet (12134m) of chemical sensing cable

Network Communications Information

Consult your IT administrator and determine the following LD5200 network 

settings:

•  IP Address _______________________________________________

•  Subnet Mask _____________________________________________

•  Default Gateway __________________________________________

Mount the Device

THE LD5200 is a wall mounted device.  Use the included wall mount kit and 

mount the controller in a convenient location.  Once the unit is mounted on the 

wall, carefully remove the appropriate knockouts from the enclosure.

SeaHawk LD5200 Quick Start Guide

Thank you for purchasing a SeaHawk 

LD5200 distance-read leak detection 

controller.  This guide outlines basic LD5200 

installation and configuration.

For additional installation and configuration 

instructions, download the LD5200 User 

Guide from our website - rletech.com.

If you need further assistance, please 

contact RLE Technologies via our website - 

http://www.rletech.com/ (go to the Support 

link) or call us at 970-484-6510, Option 2.

v1.0

(03/2012)

Отзывы: