rletech.com
SeaHawk 10K User Guide
27
3
Operation
3.2.
Manage Alarms
General Guidelines
1
If the audible alarm sounds, briefly press the Test/Reset button to silence it.
2
Look at the display, or read the appropriate Modbus register, to determine the type of alarm
and the distance to the leak, contamination, or cable break.
3
If you have a leak detection reference map, cross-reference the distance with the map.
4
Fix the problem (fix the leak, then dry the area and the section of cable involved in the leak;
replace broken cable; clean contaminated cable).
Contamination Alarm Guidelines
If the cable is in a contamination alarm state, check the following:
Verify that the cable is at least 4
feet (1.22m)
away from any air conditioning unit.
If there is dirt, grit, or grime on the cable, clean the cable with isopropyl alcohol and a clean
rag.
If the cable is in a high traffic area, move it or install a cable protector over it.