61-1007RK/61-0198RK Combustible Gas Detector • 5

2.

At the mounting site you select, hang or mount the junction box with the detector 
facing down (see Figure 3).

Wiring the CO

2

 Detector to a Controller

WARNING: Always verify that the power to the controller is off before you make 

wiring connections.

1.

Turn off the controller.

2.

Turn off or unplug power to the controller.

3.

If the detector is mounted remotely from a controller using the junction box, proceed 
to step 4.

If the detector is mounted directly to a controller, it is normally factory wired. Confirm 
that the detector’s wires are connected to the appropriate controller detector terminals 
and skip to “Start Up” on page 7. See Figure 4, the controller operator’s manual, and 
the controller’s detector head specification sheet for the 61-0198RK detector for the 
wiring connections.

4.

Remove the cover from the junction box.

5.

Guide a four-conductor, shielded cable or four wires in conduit through the top 
conduit hub of the junction box. Use appropriate conduit fittings and construction 
technique for the environmental rating of the junction box. The junction box is rated 
NEMA 4X.

6.

Connect the wires to the terminals opposite the detector leads.

CAUTION:

Leave the shield drain wire insulated and disconnected at the 61-1007RK. You will 
connect the opposite end of the cable’s drain wire at the controller.

7.

Secure the junction box cover to the junction box.

8.

Route the cable or wires in conduit leading from the detector through one of the 
conduit hubs at the controller. Use appropriate conduit fittings and construction 
technique for the environmental rating of the controller. RKI controllers are typically 
rated NEMA 4X.

CAUTION:

Do not route power and detector wiring through the same conduit hub. The power 
cable may disrupt the transmission of the detector signal to the controller.

9.

Connect the wires to the applicable controller terminal strip. See the controller 
operator’s manual and the controller’s detector head specification sheet for the 
61-1007RK detector.

Содержание 61-0198RK

Страница 1: ...www rkiinstruments com 61 1007RK 61 0198RK CO2 Detector Operator s Manual Part Number 71 0200RK Revision A Released 4 12 11...

Страница 2: ...riodic calibration and maintenance of the detector is essential for proper operation and correct readings Please calibrate and maintain this detector regularly Frequency of calibration depends upon th...

Страница 3: ...eplacement costs local repair costs transportation costs or contingent expenses incurred without our prior approval THIS WARRANTY IS EXPRESSLY IN LIEU OF ANY AND ALL OTHER WARRANTIES AND REPRESENTATIO...

Страница 4: ...tor 4 Wiring the CO2 Detector to a Controller 5 Startup 7 Introducing Incoming Power 7 Setting the Zero Signal 7 Maintenance 8 Preventive Maintenance 8 Troubleshooting 9 Replacing the CO2 Detector 10...

Страница 5: ...x and junction box terminal block Specifications Table 1 lists specifications for the CO2 detector WARNING When using the 61 1007RK you must follow the instructions and warnings in this manual to assu...

Страница 6: ...the 61 1007RK 10 which has a detection range of 0 100 volume The detector is an infrared type of detector This section describes the components of the 61 1007RK and 61 0198RK detectors The 61 1007RK...

Страница 7: ...ignal reaches the controller Housing Cap Cap Gasket The housing cap screws onto the detector housing It retains the plug in sensor and protects it from damage A foam gasket is installed inside the hou...

Страница 8: ...If you purchased a 61 0198RK detector that is factory installed in and factory wired to a controller detector installation is not necessary Mounting the CO2 Detector 1 Select a mounting site that is...

Страница 9: ...e or four wires in conduit through the top conduit hub of the junction box Use appropriate conduit fittings and construction technique for the environmental rating of the junction box The junction box...

Страница 10: ...f using shielded cable connect the cable s drain wire to an available chassis ground at the controller RKI controllers typically have a ground stud that is a convenient grounding location Controller L...

Страница 11: ...kit that includes a calibration cup a calibration cylinder of 100 nitrogen sample tubing and a 0 5 LPM liters per minute fixed flow regulator with an on off knob 1 Screw the calibration cup onto the...

Страница 12: ...ing device during the response test procedure NOTE Performing a response test on the CO2 detector may cause alarms Be sure to put the controller into its calibration program or disable external alarms...

Страница 13: ...ting The troubleshooting guide describes symptoms probable causes and recommended action for problems you may encounter with the CO2 detector NOTE This troubleshooting guide describes detector problem...

Страница 14: ...CAUTION The plug in sensor contains electrolyte which is a dilute acid Do not disassemble the sensor when replacing it with a new one If sensor electrolyte comes in contact with your skin wash affecte...

Страница 15: ...a controller in a junction box disconnect the detector leads from the terminal block in the junction box Note the position of the color coded leads as you remove them 5 Unscrew the detector from the...

Страница 16: ...des procedures to prepare for calibration set the zero reading set the response reading and return to normal operation WARNING The controller is not an active gas monitoring device during the calibrat...

Страница 17: ...he gas to flow to the detector for 1 minute 3 Turn the regulator s on off knob clockwise to close the regulator 4 Set the response reading according to the controller s operator s manual 5 Unscrew the...

Страница 18: ...5040RK 03 CO2 replacement plug in sensor 0 5 Volume 61 5040RK 05 CO2 replacement plug in sensor 0 50 Volume 61 5040RK 10 CO2 replacement plug in sensor 0 100 Volume 71 0200RK 61 1007RK 61 0198RK CO2 D...

Отзывы: