8 • 61-1000RK-05/61-0140RK-05 Combustible Gas Detector

2.

At the mounting site you select, hang or mount the junction box with the detector 
facing down (see Figure 2).

Wiring the Combustible Gas Detector to a Controller

WARNING: Always verify that the power to the controller is off before you make 

wiring connections.

1.

Turn off the controller.

2.

Turn off power to the controller.

3.

If the detector is mounted remotely from a controller using the junction box, proceed 
to step 4.

If the detector is mounted directly to a controller, it is normally factory wired. Confirm 
that the detector’s wires are connected to the appropriate controller detector terminals 
and skip to “Start Up” on page 10. See Figure 3, the controller operator’s manual, and 
the controller’s detector head specification sheet for the 61-0140RK-05 detector for the 
wiring connections.

4.

Remove the junction box cover.

5.

Guide a four-conductor, shielded cable or four wires in conduit through the unused 
conduit hub of the junction box. Use appropriate conduit fittings and construction 
technique for the environmental rating and hazardous location classification of the 
junction box. The junction box is rated NEMA 4X and classified explosion proof for 
Class I, Groups B, C, and D.

6.

Connect the wires to the terminal block in the junction box.

WARNING: To maintain the explosion proof classification of the LEL detector/junction 

box combination, a conduit seal must be used at the junction box conduit 
hub used for wiring to the controller.

CAUTION:

Leave the shield drain wire insulated and disconnected at the detector. You will 
connect the opposite end of the cable’s drain wire at the controller.

7.

Secure the junction box cover to the junction box.

8.

Route the cable or wires leading from the combustible gas detector through one of the 
conduit hubs at the controller housing. Use appropriate conduit fittings and 
construction technique for the environmental rating of the controller. RKI controllers 
are typically rated NEMA 4X.

CAUTION:

Do not route power and detector wiring through the same conduit hub. The power 
cable may disrupt the transmission of the detector signal to the controller.

9.

Connect the wires to the applicable controller terminal strip. See the controller 
operator’s manual and the controller’s detector head specification sheet for the
61-1000RK-05 detector.

10. If using shielded cable, connect the cable’s drain wire to an available chassis ground at 

the controller. RKI controllers typically have a ground stud that is a convenient 
grounding location.

Содержание 61-0140RK-05

Страница 1: ...www rkiinstruments com 61 1000RK 05 61 0140RK 05 Combustible Gas Detector Operator s Manual Part Number 71 0087RK Revision F Released 10 26 18...

Страница 2: ...h Periodic calibration and maintenance of the detector is essential for proper operation and correct readings Please calibrate and maintain this detector regularly Frequency of calibration depends upo...

Страница 3: ...or replacement costs local repair costs transportation costs or contingent expenses incurred without our prior approval THIS WARRANTY IS EXPRESSLY IN LIEU OF ANY AND ALL OTHER WARRANTIES AND REPRESENT...

Страница 4: ...g the Combustible Gas Detector 7 Wiring the Combustible Gas Detector 8 Startup 10 Introducing Incoming Power 10 Setting the Zero Signal 10 Maintenance 11 Preventive Maintenance 11 Troubleshooting 11 R...

Страница 5: ...references to the junction box and junction box terminal strip Specifications WARNING Do not use this product in a manner not specified in this instruction manual Table 1 lists specifications for the...

Страница 6: ...ubs are normally 3 4 NPT so a 3 4 x 1 2 NPT reducer may be necessary to install the combustible gas detector A flame arrestor guard is located at the bottom of the detector and is permanently bonded t...

Страница 7: ...controller conduit hub Mounting the Combustible Gas Detector 1 Select a mounting site that is representative of the monitoring environment Consider the following when you select the mounting site Sele...

Страница 8: ...ed NEMA 4X and classified explosion proof for Class I Groups B C and D 6 Connect the wires to the terminal block in the junction box WARNING To maintain the explosion proof classification of the LEL d...

Страница 9: ...stible Gas Detector 9 Figure 3 Wiring the Combustible Gas Detector to a Controller Green White Red Controller LEL Detector Terminals J Box Terminal Strip Black Detector W ires Red Green White Combusti...

Страница 10: ...eading Setting the Zero Reading WARNING Do not remove the junction box cover while the circuits are energized unless the area is determined to be non hazardous Keep the junction box cover tightly clos...

Страница 11: ...on Fail Condition Controller indicates a fail condition The detector wiring is disconnected or misconnected The detector zero signal is low enough to cause a fail condition The detector is malfunction...

Страница 12: ...for environmental conditions apply thread sealant or Teflon tape to the hub and or detector threads to seal them 7 If the detector is installed directly on a controller connect the detector leads to t...

Страница 13: ...Calibration This section describes how to calibrate the combustible gas detector It includes procedures to prepare for calibration set the zero reading set the response reading and return to normal op...

Страница 14: ...ector to gas turn the regulator s on off knob counterclockwise to open it 3 Allow the gas to flow for one minute before continuing with the directions 4 After setting the response reading turn the reg...

Страница 15: ...in air 34 liter steel 81 0004RK 03 Calibration cylinder 50 LEL propane in air 103 liter 81 0007RK 01 Calibration cylinder 15 LEL hexane in air 34 liter steel 81 0012RK 01 Calibration cylinder 50 LEL m...

Отзывы: