AirLink T3A Operator’s Manual
Installation
•
17
Remote-Mounted Kit Wiring
The remote-mounted kit generally comes prewired but if it becomes disconnected, follow these
steps to reconnect it.
CAUTION:
The internal components can be static sensitive. Use caution when opening the
enclosure and handling internal components.
CAUTION:
Make sure the power source is off before beginning the wiring procedure.
CAUTION: DO NOT
use any metal objects or tools to remove the terminal board from the
internal system.
1. Unscrew each enclosure lid and set it aside.
2. At the amplifier junction box, grab the thumbscrews and gently lift the internal system out of
the enclosure. It can rest on the edge of the enclosure.
3. One end of the cable has a connector and the other has ferruled wires.
4. Feed the connector end of the cable through a 3/4 NPT conduit hub at the amplifier junction
box.
WARNING: If installed in a classified area, use appropriate construction technique to
maintain the explosion-proof classification of the assembly.
5. Plug the connector into the sensor connector socket at the amplifier junction box.
6. Feed the ferruled-wire end of the cable through a 3/4 NPT conduit hub at the detector junction
box.
WARNING: If installed in a classified area, use appropriate construction technique to
maintain the explosion-proof classification of the assembly.
7. Connect the ferruled wires to the color-coded terminals in the detector junction box.
8. Secure the detector junction box’s enclosure lid back onto the enclosure.