65-2462RK Hydrogen Transmitter • 5
Overview
This manual describes the 65-2462RK hydrogen transmitter. This manual also describes how to install,
start up, configure, maintain, and calibrate the transmitter when it is used with a gas monitoring
controller. A parts list at the end of this manual lists replacement parts and accessories for the hydrogen
transmitter.
Specifications
Table 1 lists specifications for the hydrogen transmitter.
WARNING: When using the 65-2462RK, you must follow the instructions and warnings in this
manual to assure proper and safe operation of the 65-2462RK and to minimize the
risk of personal injury. Be sure to maintain and periodically calibrate the 65-2462RK
as described in this manual.
Table 1:Specifications
Target Gas
Hydrogen
Area Classification
Explosionproof for Class I, Groups B, C, and D
Sampling Method
Diffusion
Signal Output
4 to 20 mA
Detection Range
0 to 10% volume
Accuracy
± 5% of reading or ± 2% of full scale (whichever is greater)
Response Time
90% in 45 seconds