background image

65-2451RK Hydrogen Transmitter • 11

8.

Connect the detector leads to the detector terminal strip as shown in Table 3 below 
and Figure 3 on page 6 of this manual.

9.

Turn on power to the controller.

10. Turn on the controller and place it into normal operation.

CAUTION:

Allow the replacement detector to warm up for 5 minutes before you continue with 
the next step.

11. Calibrate the transmitter as described in “Calibration” on page 13 of this manual.

Replacing the Amplifier

1.

Turn off power to the controller.

2.

Place the controller’s on/off switch in the OFF position.

3.

Remove the junction box cover.

4.

Unplug the detector terminal strip and controller terminal strip from their sockets. 
You may leave the wires connected to the terminal strips.

5.

Unscrew and remove the screw with the flat and lock washers that secures the 
amplifier to the junction box.

6.

Remove the old amplifier.

7.

Install the amplifier into the junction box with the screw, lock washer, and flat washer 
you removed in Step 5 above. A foam gasket that orients the amplifier and keeps it 
from rotating is installed on the bottom of the amplifier. Make sure the amplifier is 
seated flat in the junction box.

8.

Install the detector and controller terminals strips into their sockets on the new 
amplifier as shown in Figure 3 on page 6 of this manual. If controller leads or detector 
leads were removed during this procedure, refer to Table 4 and Table 5 below.

Table 3:Reconnecting the Hydrogen

Detector to the Amplifier

Detector Lead

Detector Terminal Strip

Red

LEL “R”

White

LEL “W”

Green

LEL “G”

Black

LEL “B”

Table 4:Reconnecting the Amplifier

 to the Controller

Amplifier Controller 

Terminal Strip

Controller

Transmitter Terminal 

Strip (typical)

PWR/SIG “-”

- (DC -)

PWR/SIG “S”

S (4 - 20 mA In)

PWR/SIG “+”

+ 24V

www.

GlobalTestSupply

.com

Find Quality Products Online at:

[email protected]

Содержание 65-2451RK

Страница 1: ...65 2451RK Hydrogen Transmitter Operator s Manual Part Number 71 0133RK Revision C Released 5 17 11 www GlobalTestSupply com Find Quality Products Online at sales GlobalTestSupply com...

Страница 2: ...itter is essential for proper operation and correct readings Please calibrate and maintain this transmitter regularly Frequency of calibration depends upon the type of use you have and the sensor type...

Страница 3: ...n costs or contingent expenses incurred without our prior approval THIS WARRANTY IS EXPRESSLY IN LIEU OF ANY AND ALL OTHER WARRANTIES AND REPRESENTATIONS EXPRESSED OR IMPLIED AND ALL OTHER OBLIGATIONS...

Страница 4: ...up 7 Introducing Incoming Power 7 Setting the Zero Signal 7 Maintenance 8 Preventive Maintenance 8 Troubleshooting 9 Replacing Components of the Hydrogen Transmitter 10 Calibration Frequency 12 Calibr...

Страница 5: ...ing the 65 2451RK you must follow the instructions and warnings in this manual to assure proper and safe operation of the 65 2451RK and to minimize the risk of personal injury Be sure to maintain and...

Страница 6: ...only allows hydrogen to diffuse into the detector The 1 2 inch NPT mounting threads at the top of the detector allow you to mount it into the bottom conduit hub of the junction box A rainshield screw...

Страница 7: ...e zero pot is located in the upper left corner of the amplifier see Figure 1 Use a small flat blade screwdriver to turn the zero pot s adjustment screw and adjust the amplifier s zero fresh air output...

Страница 8: ...troller Mounting the Hydrogen Transmitter 1 Select a mounting site that is representative of the monitoring environment Consider the following when you select the mounting site Select a site where the...

Страница 9: ...tion box 7 Pull out the controller terminal strip and connect the three wires to the terminal strip as follows see Figure 3 Connect the positive wire to the PWR SIG terminal Connect the signal wire to...

Страница 10: ...ed connect the cable s drain wire to an available chassis earth ground at the controller Controller or Recording Device 24 VDC Amplifier Black Red Cable Shield DC Ground 4 20 mA In S PWR SI G S R W G...

Страница 11: ...ing operation CAUTION If you suspect the presence of hydrogen in the monitoring environment use the calibration kit and the zero air calibration cylinder to introduce fresh air to the detector and ver...

Страница 12: ...e performing this test NOTE The following procedure assumes the use of a calibration kit which includes a calibration gas cylinder a 0 5 LPM fixed flow regulator with an on off knob a calibration cup...

Страница 13: ...he regulator 6 Unscrew the regulator from the calibration cylinder 7 Unscrew the calibration cup from the detector NOTE For convenience leave the regulator and calibration cup connected by the sample...

Страница 14: ...te the transmitter 3 If the fail condition continues replace the detector 4 If the fail condition continues contact RKI for further instruction Slow or No Response Difficult or Unable to Calibrate Tra...

Страница 15: ...the amplifier to the junction box 6 Remove the old amplifier 7 Install the amplifier into the junction box with the screw lock washer and flat washer you removed in Step 5 above A foam gasket that ori...

Страница 16: ...n dictates otherwise RKI Instruments Inc recommends a calibration frequency of every 3 months If an application is not very demanding for example detection in a clean temperature controlled environmen...

Страница 17: ...gative lead into the black test point 5 Use the following formula to determine the correct test points output for the calibrating sample Output mV calibrating sample fullscale X 400 100 For example wi...

Страница 18: ...e reading to match the correct response reading 4 Turn the regulator knob clockwise to close the regulator 5 Unscrew the regulator from the calibration cylinder Returning to Normal Operation 1 Remove...

Страница 19: ...es detector junction box and amplifier 71 0133RK 65 2451RK Hydrogen Transmitter Operator s Manual this document 81 0002RK 01 Steel calibration cylinder 50 LEL hydrogen in air 34 liter 81 0076RK 01 Ste...

Отзывы: