10 • 65-2330RKSS H
2
S Transmitter
Installation
This section describes procedures to mount the H
2
S transmitter in the monitoring environment
and wire the transmitter to a controller.
Mounting the H
2
S Transmitter
1. Select a mounting site that is representative of the monitoring environment. Consider the
following when you select the mounting site.
•
Select a site where the transmitter is not likely to be bumped or disturbed. Make sure
there is sufficient room to perform start-up, maintenance, and calibration procedures.
•
Select a site that is at normal breathing level.
Figure 4: Mounting the H
2
S Transmitter
2. At the monitoring site you select, hang or mount the junction box with the detector facing
down (see Figure 4).
.20 Dia. x .45
Slot, 2X
3/4 NPT
Female, 2X
2.40
3.15
3.66
H2S Detector
J-Box
3.34
1.10
6.63 max