4.1 Address Setting 

 

PROFIBUS address setting 

Set an address of PROFIBUS. For this setting, use a small 
slotted screwdriver.

 

 

Setting range:  1 to 125 
[01h to 7Dh: hexadecimal] 
(Factory set value: 00h) 

Address setting switch 2 

9

8

7

C

B

A

6

5

4

3

2

1

0

F

E

D

9

8

7

C

B

A

6

5

4

3

2

1

0

F E D

5

4

3

2

1

0

9 8 7

6

5

5

4

3

2

1

0

9 8 7

6

5

FAIL/RUN  

RX/TX 

EVENT1 
EVENT2 

EVENT3 

EVENT4 

9

87

C

B

A

6

5

4

3

2

1

0

F E D

9

8

7

C

B

A

6

5

4

3

2

1

0

F E D

FA

I

RU

O

N

TX

/R

X

High-order digit setting 
(Set value 

 10h) 

Low-order digit setting 
(Set value 

 1h) 

 

No communication with PROFIBUS can be conducted 
with each factory set value (00h) left as it is. Always 
set the PROFIBUS address. 

 

 

Module address setting 

Set an address of module. For this setting, use a small slotted 
screwdriver.

 

 

5

4

3

2

1

0

9 8 7

6

5

5

4

3

2

1

0

9 8 7

6

5

Address setting switch 1 

5

4

3

2

1

0

9 8 7

6

5

5

4

3

2

1

0

9 8 7

6

5

FAIL/RUN 

RX/TX 

EVENT1 
EVENT2 

EVENT3 
EVTNT4 

9

8

7

C

B

A

6

5

4

3

2

1

0

F E D

9

8

7

C

B

A

6

5

4

3

2

1

0

F

E

D

FA

I

L

RU

N

ON

L

TX

/R

X

High-order digit setting
(Set value 

 10) 

Low-order digit setting
(Set value 

 1) 

Setting range: 0 to 98 
(Factory set value: 00) 

 

 

Do not set address 99. Otherwise, problems or 
malfunction may result. 

 

For Modbus, the value obtained by adding “1” to 
the set address corresponds to the address used 
for the actual program.

 

 

Set the module address such that it is different to 
the other addresses on the same line. Otherwise, 
problems or malfunction may result.

 

 

4.2 Internal Data Bus Termination Resistor 

Setting (PROFIBUS side) 

Set the termination resistor of internal data bus for internal 
communication.

 

When two or more modules are connected, set the internal data 
bus termination resistors to ON in modules at both ends. 
As a rule, as the X-TIO-G module is connected to the left end, 
set the internal data bus termination resistor to ON (No.8 of DIP 
switch 1: ON) on the PROFIBUS side and set that to OFF (No.8 
of DIP switch 2: OFF) on the temperature control side. 

 

 

1  2 3 4 5 6 7  8 

ON 

1  2 3 4 5 6 7  8 

ON 

ON

OFF

Left side view (PROFIBUS side) 

DIP switch 1 

 

 

Internal data bus termination resistor setting

(PROFIBUS side)

 

OFF 

Termination resistor OFF 

ON 

Termination resistor ON 

Factory set value: Termination resistor ON

 

 

 

Switch No. 1 to 7: OFF fixed (Do not change this one)

 

 

If the X-TIO-G module is used independently, the 
internal data bus termination resistors on the 
PROFIBUS and temperature control sides also need 
to be set to ON (No. 8 of DIP switches 1 and 2: ON). 

4.3  RKC Communication/Modbus Setting 

(Temperature control side) 

With the DIP switch 2 which there is on the right side of module, 
select communication speed for RKC communication/Modbus, 
data bit configuration for RKC communication/Modbus, protocol 
and termination resistor of internal data bus.

 

 

1 2 3 4 5 6 7 8

ON 

1 2 3 4 5 6 7 8

ON 

DIP switch 2 

Right side view (

temperature control side

ON

OFF

 

 

1 2 

Communication 

speed 

OFF

OFF

2400 bps 

ON

OFF

9600 bps 

OFF

ON

19200 bps 

ON

ON

38400 bps 

Factory set value: 9600 bps 

 

Data bit configuration 

OFF

OFF

OFF

Data 7-bit, without parity, Stop 1-bit 

*

OFF

OFF

ON

Data 7-bit, Even parity, Stop 1-bit 

*

 

OFF

ON

ON

Data 7-bit, Odd parity, Stop 1-bit 

*

 

ON

OFF

OFF

Data 8-bit, without parity, Stop 1-bit 

ON

OFF

ON

Data 8-bit, Even parity, Stop 1-bit 

ON

ON

ON

Data 8-bit, Odd parity, Stop 1-bit 

*

 

When the Modbus communication protocol is selected, this 
setting becomes invalid.

 

Factory set value: Data 8-bit, without parity, Stop 1-bit 

 

6 Protocol 

selection 

OFF

RKC communication 

ON

Modbus 

Factory set value: RKC communication 

 

Internal data bus termination resistor setting 

(temperature control side) 

OFF

Termination resistor OFF 

ON

Termination resistor ON 

Factory set value: Termination resistor OFF 

 

 

Switch No. 7 must be always OFF. Do not set to ON. 

 

When two or more modules are connected on the 
same communication line, the DIP switch settings 
(switch 1 to 6) of all modules must be the same 
positions. 

 

When RKC communication/Modbus is not used, 
switches other than switch 8 need not be set. 

 

For RKC communication/Modbus, refer to the 

Module 

Type Controller SRX Communication Instruction 
Manual (IMS01N01-E

)

 
 

5. MOUNTING 

 
 
 
 
 
 
 

 

5.1 Mounting Cautions 

(1) This instrument is intended to be used under the following 

environmental conditions. 

(IEC61010-1)

   

[OVERVOLTAGE CATEGORY II, POLLUTION DEGREE 2]

 

 

 

 

 

   

   

To prevent electric shock or instrument failure, 
always turn off the power before mounting or 
removing the instrument. 

!

WARNING 