IMS01N09-E4
3
4.1 Address Setting
PROFIBUS address setting
Set an address of PROFIBUS. For this setting, use a small
slotted screwdriver.
Setting range: 1 to 125
[01h to 7Dh: hexadecimal]
(Factory set value: 00h)
Address setting switch 2
9
8
7
C
B
A
6
5
4
3
2
1
0
F
E
D
9
8
7
C
B
A
6
5
4
3
2
1
0
F E D
5
4
3
2
1
0
9 8 7
6
5
5
4
3
2
1
0
9 8 7
6
5
FAIL/RUN
RX/TX
EVENT1
EVENT2
EVENT3
EVENT4
9
87
C
B
A
6
5
4
3
2
1
0
F E D
9
8
7
C
B
A
6
5
4
3
2
1
0
F E D
FA
I
RU
O
N
TX
/R
X
High-order digit setting
(Set value
10h)
Low-order digit setting
(Set value
1h)
No communication with PROFIBUS can be conducted
with each factory set value (00h) left as it is. Always
set the PROFIBUS address.
Module address setting
Set an address of module. For this setting, use a small slotted
screwdriver.
5
4
3
2
1
0
9 8 7
6
5
5
4
3
2
1
0
9 8 7
6
5
Address setting switch 1
5
4
3
2
1
0
9 8 7
6
5
5
4
3
2
1
0
9 8 7
6
5
FAIL/RUN
RX/TX
EVENT1
EVENT2
EVENT3
EVTNT4
9
8
7
C
B
A
6
5
4
3
2
1
0
F E D
9
8
7
C
B
A
6
5
4
3
2
1
0
F
E
D
FA
I
L
RU
N
ON
L
TX
/R
X
High-order digit setting
(Set value
10)
Low-order digit setting
(Set value
1)
Setting range: 0 to 98
(Factory set value: 00)
Do not set address 99. Otherwise, problems or
malfunction may result.
For Modbus, the value obtained by adding “1” to
the set address corresponds to the address used
for the actual program.
Set the module address such that it is different to
the other addresses on the same line. Otherwise,
problems or malfunction may result.
4.2 Internal Data Bus Termination Resistor
Setting (PROFIBUS side)
Set the termination resistor of internal data bus for internal
communication.
When two or more modules are connected, set the internal data
bus termination resistors to ON in modules at both ends.
As a rule, as the X-TIO-G module is connected to the left end,
set the internal data bus termination resistor to ON (No.8 of DIP
switch 1: ON) on the PROFIBUS side and set that to OFF (No.8
of DIP switch 2: OFF) on the temperature control side.
1 2 3 4 5 6 7 8
ON
1 2 3 4 5 6 7 8
ON
ON
OFF
Left side view (PROFIBUS side)
DIP switch 1
8
Internal data bus termination resistor setting
(PROFIBUS side)
OFF
Termination resistor OFF
ON
Termination resistor ON
Factory set value: Termination resistor ON
Switch No. 1 to 7: OFF fixed (Do not change this one)
If the X-TIO-G module is used independently, the
internal data bus termination resistors on the
PROFIBUS and temperature control sides also need
to be set to ON (No. 8 of DIP switches 1 and 2: ON).
4.3 RKC Communication/Modbus Setting
(Temperature control side)
With the DIP switch 2 which there is on the right side of module,
select communication speed for RKC communication/Modbus,
data bit configuration for RKC communication/Modbus, protocol
and termination resistor of internal data bus.
1 2 3 4 5 6 7 8
ON
1 2 3 4 5 6 7 8
ON
DIP switch 2
Right side view (
temperature control side
)
ON
OFF
1 2
Communication
speed
OFF
OFF
2400 bps
ON
OFF
9600 bps
OFF
ON
19200 bps
ON
ON
38400 bps
Factory set value: 9600 bps
3
4
5
Data bit configuration
OFF
OFF
OFF
Data 7-bit, without parity, Stop 1-bit
*
OFF
OFF
ON
Data 7-bit, Even parity, Stop 1-bit
*
OFF
ON
ON
Data 7-bit, Odd parity, Stop 1-bit
*
ON
OFF
OFF
Data 8-bit, without parity, Stop 1-bit
ON
OFF
ON
Data 8-bit, Even parity, Stop 1-bit
ON
ON
ON
Data 8-bit, Odd parity, Stop 1-bit
*
When the Modbus communication protocol is selected, this
setting becomes invalid.
Factory set value: Data 8-bit, without parity, Stop 1-bit
6 Protocol
selection
OFF
RKC communication
ON
Modbus
Factory set value: RKC communication
8
Internal data bus termination resistor setting
(temperature control side)
OFF
Termination resistor OFF
ON
Termination resistor ON
Factory set value: Termination resistor OFF
Switch No. 7 must be always OFF. Do not set to ON.
When two or more modules are connected on the
same communication line, the DIP switch settings
(switch 1 to 6) of all modules must be the same
positions.
When RKC communication/Modbus is not used,
switches other than switch 8 need not be set.
For RKC communication/Modbus, refer to the
Module
Type Controller SRX Communication Instruction
Manual (IMS01N01-E
)
.
5. MOUNTING
5.1 Mounting Cautions
(1) This instrument is intended to be used under the following
environmental conditions.
(IEC61010-1)
[OVERVOLTAGE CATEGORY II, POLLUTION DEGREE 2]
To prevent electric shock or instrument failure,
always turn off the power before mounting or
removing the instrument.
!
WARNING