RKC INSTRUMENT X-TIO-G Скачать руководство пользователя страница 2

IMS01N09-E4

 

1. OUTLINE 

The X-TIO-G (temperature control module for PROFIBUS) can 
send/receive data to/from PROFIBUS compatible programmable 
controllers (PLC) via PROFIBUS. 
One X-TIO-G module enables temperature control corresponding 
to two channels. It has power supply and communication terminals 
in addition to temperature control input and output terminals.

 

All data are set by communication.

 

For details, refer to the 

Module Type Controller SRX 

PROFIBUS Communication Instruction Manual 
(IMS01N10-E

and

 

the 

Module Type Controller SRX 

Communication Instruction Manual (IMS01N01-E

)

.

 

 

 

Control output

Measured 

input 

Power supply input 

(24 V DC) 

Usable modules: 

 Temperature control module   

[Basic type]: 

X-TIO-A 

 Temperature control module   

[Extension type]: 

X-TIO-B 

 Digital input module:  X-DI-A/B 

 Digital output module:  X-DO-A/B 

(Up to 29 modules) 

PROFIBUS-DP 

Temperature control 

module for PROFIBUS 

X-TIO-G 

Programmable 

controller (PLC) 

 

 
 

2. PRODUCT CHECK 

Before using this product, check each of the following: 

 Model code 

  Check that all of the accessories delivered are complete. 

 Check that there are no scratch or breakage in external 

appearance (case, front panel, or terminal, etc). 

X-TIO-G- 

 

 - 

 

 

 

 / Y 

(1) (2) (3)  (4) (5)  (6) (7)  (8) 

(1) Type 

G: Module for PROFIBUS 

(2) Input channel 1,  (3) Input channel 2 

K:  TC K 

J:  TC J 

 

T:  TC T 

S:  TC S 

R:  TC R 

A:  TC PL

 

N:  TC N 

E:  TC E 

W:  TC W5Re/W26Re   

 

B:  TC B 

D:  RTD Pt100   

 

 

 

P:  RTD JPt100 

1:  0 to 10 mV DC   

2:  0 to 100 mV DC 

3:  0 to 1 V DC 

4:  0 to 5 V DC   

 

5:  0 to 10 V DC 

6:  1 to 5 V DC 

7:  0 to 20 mA DC   

8:  4 to 20 mA DC 

(4) Control output 1,  (5) Control output 2 

M:  Relay contact output   

V:  Voltage pulse output 0/12 V DC 

4:  0 to 5 V DC 

5  0 to 10 V DC 

6:  1 to 5 V DC 

7:  0 to 20 mA DC 

8:  4 to 20 mA DC 

(6) CT1 input,  (7) CT2 input 

N: None 

P: CTL-6-P-N 

S: CTL-12-S56-10L-N 

(8) Version symbol 

No code: For Japanese domestic market   
/Y: For 

International 

market 

 

Heater break alarm (HBA) function can not be used 
when control output is Voltage/Current output. 

 
 
 
 
 
 
 
 

If any of the products are missing, damaged, or if your 
manual is incomplete, please contact RKC sales office or 
the agent.

 

 

The manuals can be downloaded from the official RKC 
website:  
http://www.rkcinst.com/english/manual_load.htm. 

 

 

3. PARTS DESCRIPTION 

 

Terminal cover 

Indication lamps 1 

Address setting
switch 1 

Terminal cover

Joint connector 
(Right-side) 

Joint connector 
(Left-side) 

Indication lamps 2

Address setting

switch 2

PROFIBUS

connector 

(COM.PORT)

PROFIBUS side  Temperature control side

5

4

3

2

1

0

9 8 7

6

5

5

4

3

2

1

0

9 8 7

6

5

FAIL /RUN  

RX/TX 

EVENT1 

EVENT2 

EVENT3 

EVENT4 

9

8

7

C

B

A

6

5

4

3

2

1

0

F E

D

9 8

7

C

B

A

6

5

4

3

2

1

0

F E D

FA

I

L

RU

N

ON

L

TX

/R

X

 

 

FAIL/RUN
RX/TX 
EVENT1 
EVENT2 
EVENT3 
EVENT4 

FA

IL

RU

N

ON

L

TX

/R

X

 

 

 
[Indication lamps 1] 

 FAIL/RUN (for temperature control side) 

When normally: 

A green lamp turns on (RUN) 

When abnormally: A red lamp turns on (FAIL) 

 RX/TX (for RKC communication/Modbus) 

During data send and receive:  A green lamp turns on 

 EVENT 1 to 4 

Display various states by setting. 
During ON state:  A green lamp turns on 

Display contents

 

Event 1 state, Event 2 state, Comprehensive event state, Output state,   
Control state, Executing segment state, Time signal state 

 

[Indication lamps 2]   

 FAIL (for PROFIBUS side) 

When hardware is normal: 

A red lamp turns off 

When hardware is abnormal: 

A red lamp turns on 

 RUN (for internal communication) 

When normally: 

A green lamp turns on 

When abnormally: A green lamp is flashing 

 ONL 

During PROFIBUS connection establishment: 
 

A green lamp turns on 

 RX/TX (for PROFIBUS communication) 

During data send and receive:  A green lamp turns on 

 

 

4. COMMUNICATION SETTING 

Set communication setting before mounting and wiring of SRX.

 

 
 

Do not separate the module mainframe from the terminal base 
with the power turned on. If so, instrument failure may result. 

 

 

Accessories

 

End Plate .......................................................................... 2
Joint connector cover ....................................................... 2
X-TIO-G Instruction Manual (IMS01N09-E4) ................... 1
GSD file (download free) * ................................................ 1

* The GSD file can be downloaded from the official RKC website:

http://www.rkcinst.com/english/download/field_network.htm. 

*