RKC INSTRUMENT V-TIO-E Скачать руководство пользователя страница 6

IMS01P04-E4

 

Continued from the previous page.

 

5 6 7 

Communication 

protocol 

OFF  OFF  OFF  Host communication 2 (RKC communication)

ON  OFF  OFF  Host communication 2 (Modbus) 

OFF  ON  OFF 

Don’t set this one 

ON ON OFF 

PLC communication 
OMRON SYSMAC series special protocol 

C mode command (RD/WD) 

OFF OFF  ON 

PLC communication 
MITSUBISHI MELSEC series special protocol

ACPU common command (WR/WW) 

ON OFF ON 

PLC communication 
MITSUBISHI MELSEC series special protocol

AnA/AnUCPU common command (QR/QW) 

OFF  ON  ON 

Don’t set this one 

ON  ON  ON 

Don’t set this one 

Factory set value:  Host communication 2 (RKC communication) 

 

8 Modular 

connector 

PLC/host communication 

selection 

OFF 

COM. PORT1: 

PLC communication/host communication 2 

 [RS-232C/RS-422A]

COM. PORT2/COM. PORT3:   

Host communication 1 [RS-422A] 

ON 

COM. PORT1: 

Host communication 1 [RS-232C/RS-422A] 

COM. PORT2/COM. PORT3:   

PLC communication/host communication 2 [RS-422A]

Factory set value: COM. PORT1: 
 

Host communication 1 [RS-232C/RS-422A] 

 

COM. PORT2/COM. PORT3:   

 

PLC communication/host communication 2   

  

[RS-422A] 

 

When two or more V-TIO-E/F modules are multi-drop 
connected, set the PLC communication setting 
switches in all of the V-TIO-E/F modules to the same 
positions. 

COM. PORT2 and COM. PORT3 become the same 
communication specification. 

 
 

 

Host communication setting switc

h

 

Set the communication speed, data bit configuration, and 
protocol for host communication 1. 

 

1 2 3 4 5 6 7  8 

ON 

1 2 3 4 5 6 7  8 

ON 

ON

OFF

Left side 

Host communication   

setting switch 

 

1 2 

Communication 

speed 

OFF OFF 

2400 

bps 

ON OFF 

9600 

bps 

OFF ON 

19200 

bps 

ON ON 

38400 

bps 

Factory set value: 9600 bps 

 

Data bit configuration

 

OFF

OFF

OFF

Data 7-bit, without parity, Stop 1-bit 

*

OFF

OFF

ON

Data 7-bit, Even parity, Stop 1-bit 

*

 

OFF

ON

OFF

Don’t set this one 

OFF

ON

ON

Data 7-bit, Odd parity, Stop 1-bit 

*

 

ON

OFF

OFF

Data 8-bit, without parity, Stop 1-bit 

ON

OFF

ON

Data 8-bit, Even parity, Stop 1-bit 

ON

ON

OFF

Don’t set this one 

ON

ON

ON

Data 8-bit, Odd parity, Stop 1-bit 

*

 When the Modbus communication protocol is selected, this 

setting becomes invalid.

 

Factory set value: Data 8-bit, without parity, Stop 1-bit 

 

6 Communication 

protocol

 

OFF

Host communication1 (RKC communication) 

ON

Host communication 1 (Modbus) 

Factory set value: Host communication 1 (RKC communication) 

 

• 

Switch No. 7 and 8 must be always OFF. Do not set 
to ON. 

• 

When two or more V-TIO-E/F modules are 
multi-drop connected, for switch Nos.1 to 6 set the 
PLC communication setting switches in all of the 
V-TIO-E/F modules to the same positions.

 

 
 

 

Internal communication setting switch 

Use this module without changing the factory set values. 

[Factory set value] 

 Communication speed: 38400 bps 

 Data bit configuration:  Data 8-bit, without parity 

 Protocol: 

Modbus 

[Factory set value of internal communication setting switch] 

No. 1:  ON 

No. 5:  OFF 

No. 2:  ON 

No. 6:  ON 

No. 3:  ON 

No. 7:  OFF 

No. 4:  OFF 

No. 8:  OFF 

 

 

1 2 3 4 5 6 7 8

ON 

1 2 3 4 5 6 7 8

ON 

Internal communication 

setting switch 

Right side 

ON

OFF

 

 

 

When connecting two or more modules (V-TIO-A, B, 
C or D) to the V-TIO-E/F module, match all of their 
communication speed, data bit configuration and 
communication protocol settings with the internal 
settings of the V-TIO-E/F module.

 

For details of internal communication setting switch, see   
the 

Module Type Controller SRV PLC/Host   

Communication Instruction Manual (IMS01P05-E )

.

 

 

 

Содержание V-TIO-E

Страница 1: ...osed instrumentation panel All high voltage connections such as power supply terminals must be enclosed in the instrumentation panel to avoid electric shock by operating personnel All precautions desc...

Страница 2: ...groups and then installed Usable modules Temperature control TIO module Basic type V TIO A C Temperature control TIO module Extension type V TIO B D Up to 30 modules Event input output connector optio...

Страница 3: ...JPt100 P17 0 to 400 C PC5 32 to 752 F P23 0 to 600 C PC4 32 to 1112 F P16 0 0 to 400 0 C PC7 32 0 to 752 0 F P28 200 0 to 400 0 C PC6 328 0 to 752 0 F Voltage current input Code Type Code Type Voltage...

Страница 4: ...e See P 5 Set the unit address for PLC communication PLC communication setting switch left side See P 5 Set the communication speed data bit configuration and protocol for PLC communication Set the sa...

Страница 5: ...imal Factory set value 0 9 8 7 C B A 6 543 2 1 0 F E D Address setting switch 2 for unit address PLC communication Up to four V TIO E F modules can be connected to a PLC communication port Therefore t...

Страница 6: ...ps ON ON 38400 bps Factory set value 9600 bps 3 4 5 Data bit configuration OFF OFF OFF Data 7 bit without parity Stop 1 bit OFF OFF ON Data 7 bit Even parity Stop 1 bit OFF ON OFF Don t set this one O...

Страница 7: ...y reach of the operator It shall be marked as the disconnecting device for the equipment 5 2 Dimensions Unit mm 110 6 8 40 5 125 78 5 The above figure shows when provided with the event input output c...

Страница 8: ...se induction keep input signal wire away from instrument power line load lines and power lines of other electric equipment If there is electrical noise in the vicinity of the instrument that could aff...

Страница 9: ...e modular connector should be used for the connection to the V TIO E F module Recommended manufacturer and model Hirose Electric TM4P 66P Event input output connector 1 6 Event input output connector...

Страница 10: ...low Deviation high low Band Process high Process low Heater break alarm Control loop break alarm Burnout Temperature rise completion Option Event input Number of inputs 1 point Input type Dry contact...

Отзывы: