background image

 

IM100CZ04-E4

 

3

  If the pressure sensor is used for screen changer operation, it may 

suffer an impact during screen changer operation, causing sensor 
troubles. In such a case, carefully consider the position and 
direction when installing the sensor. 

 

 

Mounting pressure sensors

 

  When the diaphragm at the end of CZ-100P and its surroundings 

completely touch with its mounting hole, large indication error may 
occur. In this case, temperature may exert a large influence 
especially upon the zero point. Therefore, much attention should 
be paid when a mounting hole is drilled. 

 
 
 
 
 
 

 

  When using a lead pipe cover, pay attention that the lead pipe 

cover end does not directly touch the barrel. (Refer to the “

 

Exposed length at the bottom of the sensor outer case

”)

 

 

 
 
 
 
 
 

 

 

  Prior to mounting the pressure sensor, check the appearance of 

the diaphragm. If the diaphragm has a deformed or abnormal end, 
it needs to be repaired or re-calibrated. As there is a case where 
the diaphragm is already deformed by the application of overload 
when used previously, carefully check its condition before the 
pressure sensor is re-used.

 

 

 

Mounting hole 

 When mounting the pressure sensor, check its mounting hole 

dimensions. (Do not overtighten its screw.

  If resin or its carbide still remains in the mounting hole, this may 

damage the pressure sensor. Therefore, prior to mounting the 
sensor, always remove any residue from the mounting hole. 

 Check that the diaphragm surface does not protrude from the 

inner wall of the barrel, since this may score the diaphragm 
surface with the screw, etc. If necessary, adjust the position 
between the diaphragm surface and the inner wall of the barrel 
using stainless steel gaskets, etc. 

  For the loose nut type, resin leakage may occur more easily than 

the fixed nut type, as the pressure sealing surface becomes wider. 
If any resin leaks through the mounting gap of the sensor, use 
copper gaskets (thickness:  t 

  2  mm) or aluminum gaskets 

(thickness: t 

 2 mm) by taking into account the position between 

the diaphragm surface and the inner wall of the barrel. (Copper 
Gasket: Included in only the Loose nut type)

 

 

 

Mounting direction 

  If the sensor is installed in the upright direction (Fig.1-A), it may be 

affected directly by heat flow from heater or heat source (rising 
current of heated air). In such a case, the temperature of the strain 
gauge in the sensor may exceed an allowable maximum 
temperature of 150 

C. In order not to exceed this limit 

temperature, it is necessary to keep the sensor outer cylinder 
surface at a temperature of less than 134 

C (Fig.2). Conduct the 

following treatments.

 

1.

 In order to avoid heat flow, wind a heat insulating material round 

such a heat source (heater, etc.). 

2.

 Further extend the length of the exposed lead pipe. 

  In order to keep the specified sensor performance longer, it is 

recommended that the sensor outer cylinder surface temperature 
be keep at less than 134 

C. 

  When the sensor is installed in the upright position, thermal effects 

on the sensor may not sufficiently lessen even if the length of the 
exposed lead pipe is further extended. In this case, take measures 
of

 1

  The effect of heat flow lessens as the installing direction of the 

sensor changes from the slanting direction (Fig.1-B) to the 
horizontal direction (Fig.1-C) in this order. In this case, take 
measures of

  1

 and

  2

 if necessary by checking the sensor outer 

cylinder surface temperature. (To the relevant manufacturer: It is 
recommended that the sensor be installed in the horizontal or 
slanting direction in order to lessen the effect of heat on the strain 
gauge.) 

 

 

 

 

 

 

 

 

 

Exposed length at the bottom of the sensor 
outer case

 

  Cases where the temperature of the strain gauge in the sensor 

become less than 150 

C is as follows: 

  The effect of heat flow is small. 

  The sensor is installed in the upright position. 

  The diaphragm is at a temperature of 400 

C. 

 The length of the exposed sensor outer cylinder is more than 

  70 mm. (Refer to below) 

However, as the effect of heat flow from an actual extruder is 
serious, if there is no enough exposed section below the sensor 
outer cylinder even at a diaphragm temperature of less than       
200 

C, the operating temperature of the sensor strain gauge may 

exceed its limit. Therefore, check the temperature environment 
where the sensor is installed (by indirectly checking the 
temperature of the sensor outer cylinder surface), and take 
necessary measures to lessen the temperature of the sensor 
strain gauge by using a heat insulating material, if necessary. 

 

If the temperature of the sensor outer cylinder surface 
exceeds 160 

C, the outer cylinder surface changes its 

color from black to dark brown and then brown in this 
order. If it exceeds 180 

C, the color may change to silver. 

 
 

 

 

 

 

 

 

 

 

  A lead pipe cover is mainly for protecting the exposed section below 

the sensor outer cylinder from being exposed to cold wind. 
Therefore, do not install the sensor such that it is embedded in the 
heat source (such as in the barrel or heater) together with the lead 
pipe cover. This may heighten thermal conductivity from the heat 
source, resulting in a temperature increase in the sensor strain 
gauge. 

 

3.1.2 Caution in removing pressure sensors 

 

Always remove the sensor while resin is being melted

, since 

the diaphragm of the sensor may be damaged if the sensor is 
removed after the resin has hardened. If the sensor is re-mounted 
under this condition the repeatability may deteriorate. 

  When removing the pressure sensor, remove it under the same 

temperature as that during installation. Removing the pressure 
sensor under the different temperature as that during installation 
cause irregular engagement of the thread. 

  If resin flows into the gap between the lead pipe and the mounting 

hole, it may be impossible to remove the sensor even with the 
threads completely disengaged. In this case, if the sensor is 
forcibly removed using a puller, the sensor may be knocked when 
removed, damaging the diaphragm and reducing the accuracy. 
Slowly remove the sensor without knocking it. 

Do not wind sealing tapes, etc. round this section   
for preventing oil or resin leakage. 

Packing surface (Sealing surface)   
[Flat tightening or tapered tightening surface]   
(Oil or resin leakage is prevented at this point.) 

Barrel 

Lead pipe cover 

Mount the sensor so that this block   
does not directly touch the barrel. 

The aims of a 
temperature 
measurement 
position 

(Fig. 2) 

(Fig. 1) 

A: Upper mounting 
B: Oblique mounting 
C: Side mounting 

A section of a extruder 

Mounting environment:
Ambient temperatures
at room temperatures 

25 

C

 

CZ-100P 

Mounting adapter 

Temperature of heater 

400 

 

90 

60 

70 

(Unit: mm)

Содержание CZ-100P

Страница 1: ...wer is turned on again To prevent instrument damage as a result of failure protect the power line and the input output lines from high currents with a suitable overcurrent protection device with adequ...

Страница 2: ...Diaphragm section material S SUS630 Standard H HASTELLOY C Optional 3 Diaphragm surface treatment N Standard K CERAMIC Kanigin plate Optional 4 Intrinsically safe N Standard For non explosionproof spe...

Страница 3: ...he slanting direction Fig 1 B to the horizontal direction Fig 1 C in this order In this case take measures of 1 and 2 if necessary by checking the sensor outer cylinder surface temperature To the rele...

Страница 4: ...llow loose fitting Z 1024 or Z 1024A type 0 to 1 MPa Z 1024 or Z 1024A type 24 0 0 2 3 1 5 Pressure sensor installation 1 Make sure the mounting hole is correctly machined If installing the pressure s...

Страница 5: ...maximum available current of 8 A Use the solderless terminal appropriate to the screw size Screw size M3 6 Recommended tightening torque 0 4 N m 4 kgf cm Specified solderless terminals With isolation...

Страница 6: ...de of PCT 300 refer to drawing on page 6 to 2 Gain setting for CZ 100P LLA Z 1024A type Set the RATED OUTPUT Rated output mV V value specified on the label of the pressure sensor at Gain setting in th...

Страница 7: ...wing correction equation and correction factor e1 e0 1 0 5 S K L 5 e0 Rated output of the resin pressure sensor e1 Rated output after the correction S Conductor nominal cross sectional area mm2 K Corr...

Страница 8: ...on is fluctuated Value different from the sensor rated output set to the rated output setter for the PCT 300 The diaphragm deteriorated deformed or damaged The sensor exposed to hot or cold wind Some...

Страница 9: ...aphragm deformed or damaged as the push rod pushes the diaphragm from the inside as a result of the deformation of the sensor flange by excessive tightening torque 9 EXPLANATION OF EACH TERMS Term Exp...

Страница 10: ...0 5 As the input side of bridge resistance the 350 5 type is also available This type is interchangeable with the 374 10 type Temperature characteristics Maximum diaphragm temperature 400 C Maximum st...

Страница 11: ...Linearity Within 0 01 of span Noise Within 0 1 p p of span 0 1 to 10 Hz Response 10 Hz 100 Hz transfer type Factory shipment 10 Hz Power supply 90 to 264 V AC Including power supply voltage variation...

Страница 12: ...1995 The fourth edition OCT 2013 IMQ00 HEADQUARTERS 16 6 KUGAHARA 5 CHOME OHTA KU TOKYO 146 8515 JAPAN PHONE 03 3751 9799 81 3 3751 9799 E mail info rkcinst co jp FAX 03 3751 8585 81 3 3751 8585 RKC...

Отзывы: