10 Technical specifications
12
Rittal fan-and-filter unit assembly and operating instructions
EN
10 Technical specifications
– Observe the mains connection data
(voltage and frequency) as per the
rating plate.
– Observe the pre-fuse as per the specifi-
cations on the rating plate.
Unit
Model No. SK
Fan-and-filter unit,
RAL 7035
–
3237.100
3237.110
3237.124
3238.100
3238.110
3238.124
EMC fan-and-filter
unit,
RAL 7035
–
3237.600
–
–
3238.600
–
–
Rated operating
voltage
V
Hz
230, 1~,
50/60
115, 1~,
50/60
24 (DC)
230, 1~,
50/60
115, 1~,
50/60
24 (DC)
Rated current max.
A
0.065/
0.052
0.14/
0.12
0.14
0.12/
0.11
0.24/
0.23
0.28
Power
consumption
W
11/9
3
19/17
6
Pre-fuse T
A
2
Dimensions
B1/H1
mm
116.5 x 116.5
148.5 x 148.5
B2/H2
mm
92 x 92
124 x 124
T1
mm
16
T2
(max. installation
depth)
mm
43
58.5
Air throughput,
unimpeded air flow
m³/h
20/25
20
55/66
55
Air throughput
with outlet filter
including standard
filter mat
m³/h
1 x 3237.200: 15/18
1 x 3238.200: 43/50
–
2 x 3238.200: 46/56
Outlet filter
–
3237.200
3238.200
EMC outlet filter
–
3237.060
3238.060
Fan
–
Axial, self-starting
shaded pole motor
Axial,
DC motor
Diagonal, self-starting
shaded pole motor
Diagonal,
DC motor
Noise pressure
level
dB (A) 38/43
38
46/49
46
Operating
temperature
°C
–15 to +55
Storage
temperature
°C
–30 to +70
Protection category
(to EN 60 529)
–
IP 54 standard
IP 55 with hose-proof hood
IP 56 with hose-proof hood
IP 54 standard
IP 55 with hose-proof hood
IP 56 with hose-proof hood
Tab. 2: Technical specifications
We reserve the right to make technical modifications.