Rittal RCM Inline Meter
8
Mass configuration / initial commissioning
To allow easy and quick commissioning of several RCMs, they can be preconfigured using a special
configuration file. The configuration file copied to a USB data carrier allows several RCMs to be config-
ured in just a few minutes without an operational network connection being required. To edit the file on
a PC, you will need either the RCM serial numbers or the first MAC address of the RCM network inter-
faces. A predefined sample file as well as a description of the procedure can be found on the PDU prod-
uct pages at our website.
9
Technical specifications
9.1
General technical specifications
Note:
Once a slave RCM has paired with a master RCM, it can no longer be paired with a dif-
ferent master RCM. To do so, you will need to reconfigure the slave RCM via the
PDU
Mode
menu. The display will show "PDU", which also applies to the RCM in this instance.
Note:
Software updates for the slave RCM are distributed via the master RCM. The master RCM
must be updated first. For further information, please visit www.rittal.com or contact Rittal
Service (see section 10). The software updates are subsequently distributed automatical-
ly among the individual slave RCMs.
Technical specifications
Temperature application range:
Temperature Operation: +5 °C…+50 °C (at 100% load))
Temperature Storage: -20 °C…+70 °C
Humidity application range:
10%…95% relative humidity, non-condensing
Protection category:
IP 20 to IEC 60 529
Protection class:
1
Overvoltage category:
II
Degree of contamination:
2
max. operating height:
3,000 meters above sea level
min. operating time:
100,000 h
EU conformity:
Low-Voltage Directive 2014/35/EU
EMC Directive 2014/30/EU
IEC/EN 62368
Input voltage range (L – N)
90 V…260 (400) V AC, 50…60 Hz
Input current
16 A/32 A (depending on variant)
No. of phases
1 or 3 depending on RCM variant
Differential current measurement range AC/DC
+/- 100 mA
Connection cable type
H05-VV
No. of wires
3/5 (single-phase/3-phase RCM)