background image

Rittal LCU DX

17

6 Installation

EN

7. For intake gas lines laid vertically with the direction of 

flow pointing upwards (external unit is above the in-
ternal unit), an oil elevation arc should be provided at 
least every 3 m of line length. The pre-insulated pairs 
of lines may be laid with no distance between them.

Protecting the pipework

1. Suitable precautions should be taken to prevent ex-

cessive vibrations or pulsations. In particular, care 
should be taken to prevent the direct transmission of 
noise or vibrations onto or through the supporting 
structure and the connected devices.

2. Safety devices, pipework and fittings should be pro-

tected from unfavourable environmental influences 
as far as possible. Due consideration should be giv-
en to unfavourable environmental influences, such 
as the risk of water collecting, relief lines freezing, or 
dirt and waste accumulating.

3. With long pipelines, adequate precautions should be 

taken with regard to expansion and contraction.

4. The pipelines of cooling systems should be de-

signed and laid in such a way that the system cannot 
be damaged by liquid slugging (hydraulic shock).

5. Pipelines with detachable connections must not be 

positioned in public thoroughfares, vestibules, stair-
wells, steps, entrances, exits or in ducts or shafts 
with unsecured openings to such areas, unless pro-
tected against disconnection.

6. Pipelines without detachable connections, valves, 

control and regulatory devices that are protected 
against accidental damage may be positioned in 
public thoroughfares, stairwells or vestibules, pro-
vided they are situated at least 2.2 m above the 
ground. 

Pipe supports

1. Both horizontal and vertical lines must be laid with vi-

bration-damping elements (such as rubber seals). 
These must be used at a spacing of at least 2 m.

2. Take care to ensure that the first pipe support be-

hind the internal unit and in front of the external unit 
does not exert any mechanical pressure (via the 
pipe) on the component. Pipe supports must not be 
located too close to bends, to give the lines space 
to expand.

Create the pipework system

1. To create the refrigerant pipework system, open the 

ends of the lines on the internal unit. Upon opening, 
gas should flow out audibly (from the nitrogen filling 
provided in the factory) as an indication that there 
are no leaks in the cooling circuit.

2. Only cut pipes to length using a pipe cutter.
3. Never saw pipes, as this could create swarf.
4. Only solder pipes under nitrogen or helium! To this 

end, allow dry inert gas to flow into the pipe at one 
end of the pipeline which has already been created. 
Before starting, introduce a powerful current, reduce 
this to a minimum when you start soldering, and 
maintain this weak flow of protective gas throughout 
the entire soldering process.

5. Before soldering the final connection, loosen the 

screw connection on the external unit, or leave it un-
tightened throughout, so that overpressure cannot 
build up in the pipeline system. Immediately after 
soldering, tighten the screw connection.

6. The pipelines may only be connected to the external 

unit with flares. However, flare connections should 
be restricted to soft pipes! After cutting the pipes to 
length, adjust to the correct internal diameter with 
light flaring. The flares must be tightened with the 
prescribed torque using a torque wrench.

Low-temperature insulation of the liquid line and 
intake gas line

1. Both lines outside and inside the building should be 

equipped with low-temperature insulation to DIN 
4140 made from UV-resistant HT/Armaflex or an 
equivalent material.

2. We recommend a wall thickness of 9 mm

Leak test / conducting the leak test

The system must undergo leak testing as a complete 
system. A test should also be carried out on site once 
the installation is complete.
Multiple techniques may be used to test for leaks, de-
pending on the manufacturing conditions, such as pres-
surisation with inert gas, or leak detection using radioac-
tive gas. In order to avoid emissions of hazardous sub-
stances, the pressure test may be carried out with inert 
gas such as nitrogen, helium or carbon dioxide. Oxy-
acetylene and hydrocarbons must not be used for safety 
reasons. Air and gas mixtures are to be avoided, since 
certain mixtures may be hazardous.
The manufacturer must select a test method which al-
lows suitable results to be achieved in accordance with 
the requirements outlined below.

Note:
Vibrations and pulsations should be as-
sessed with the system operational at maxi-
mum condensation temperature and when 
switching the system on and off, which has 
unfavourable impacts on the pipework. 

Note:
The internal unit is pressurised (filled with pro-
tective gas)!

Содержание 3311.490

Страница 1: ...LCU DX Assembly and operating instructions 3311 490 3311 491 3311 492 3311 493 ...

Страница 2: ... read this documentation carefully and pay particular attention to the safety instructions in the text and to section 2 Safety instructions This is the prerequisite for secure assembly of the LCU DX safe handling and the most trouble free operation possible Please keep the complete documentation readily availa ble so that it is always on hand when needed We wish you every success Your Rittal GmbH ...

Страница 3: ...ssembly procedure 12 5 2 1 Preparatory tasks 12 5 2 2 Mounting the internal unit 13 5 2 3 Mounting the internal unit accessories 13 5 2 4 Mounting the external unit 14 6 Installation 16 6 1 General information 16 6 2 Notes on pipework 16 6 3 Connecting the condensate discharge 18 6 4 Electrical connection 18 6 4 1 General 18 6 4 2 Connecting the external unit 19 6 4 3 Connecting the internal unit ...

Страница 4: ...struction specifications for the ventilation system also applies in conjunction with these assembly and operating instructions 1 6 Normative instructions 1 6 1 Legal information concerning the operating instructions We reserve the right to make changes in content Rittal GmbH Co KG and or Hannich GmbH are not respon sible for any damage which may result from failure to comply with these assembly an...

Страница 5: ...rt up again automatically following a power disruption Danger Hot components may cause in jury The external unit and the pipelines are hot during operation and may cause burns on direct contact Danger Risk of poisoning from refriger ant gases created under the influence of heat When carrying out welding and solder ing work shortness of breath or asphyx iation may occur The refrigerant is heavier t...

Страница 6: ...idual responsible for the cooling system together with the address and telephone number of the fire brigade police hospitals and burn victims centres 2 Type of refrigerant R410A comprising 50 di fluoromethane R32 CH2F2 and 50 R125 penta fluoroethane C2HF5 3 Instructions for switching off the cooling system in an emergency see section 7 2 3 Switching off in an emergency 4 The maximum permissible pr...

Страница 7: ...g and disposal of products and equipment containing such gases Leak test pursuant to Article 3 containment 3 kg 30 kg at 12 month intervals or 6 kg in hermet ically sealed systems 30 kg 300 kg at 6 month intervals more than 300 kg at 3 month intervals 2 3 4 Chemicals Climate Protection Ordinance This Ordinance applies in addition to the aforementioned Regulation EC No 842 2006 of the European Parl...

Страница 8: ...ntrol the re quired fan speed Any condensate incurred is collected in the integral con densate collecting tray below the heat exchanger and from there is routed outside via a condensate discharge hose 3 2 Air routing In order to achieve sufficient cooling in the server enclo sure it is important to ensure that the cooling air passes through the interior of the built in devices rather than flowing ...

Страница 9: ...ator coil via the expansion valve in liquid form The condenser is comprised of copper core pipes with aluminium mem branes and a DC fan motor which is speed controlled to adjust the output Electronic expansion valve to supply the evaporator coil with the required volume of refrigerant so as to ensure the corresponding optimum thermal absorp tion capacity to suit the current output requirements The...

Страница 10: ...e discharge hose with copper si phon 1 External unit 1 Set of accessories for mounting the internal unit and for the air block panel 1 Assembly and operating instructions Tab 1 Scope of supply of an LCU DX single variant Qty Parts 1 LCU DX ready to connect consisting of 1 Internal unit 2 Remote control operating unit 1 Holder for operating unit 482 6 mm 19 con sole 3 U 2 Temperature sensor server ...

Страница 11: ...ip over Risk of toppling especially after the unit is re moved from the pallet Caution Transportation of the LCU DX without a pallet Use only suitable and technically sound lifting gear and load bearing devices with sufficient load capacity Note After unpacking the packaging materials must be disposed of in an environmentally friendly way They consist of the following materials Wood polyethylene f...

Страница 12: ...it and external unit 5 1 3 Supply connections required at the installa tion site Power is usually supplied to the external unit LCU DX 3 kW LCU DX 6 5 kW 5 1 4 Electromagnetic interference Interfering electrical installations high frequency are to be avoided 5 2 Assembly procedure 5 2 1 Preparatory tasks The internal unit may be mounted both on the right and on the left of the TS IT server enclosu...

Страница 13: ...ernal unit Position the internal unit on the mounting devices in such a way that the air outlet opening is on the opera tor side of the server enclosure and the fans are in the rear section The end face of the internal unit must be flush with the front edge of the TS frame Align the internal unit horizontally In this position screw the internal unit to the punched section with mounting flange usin...

Страница 14: ...led or the fan would need to work against the wind and be unable to move the re quired volume of air If necessary a wind break should be installed at a dis tance of 1 m from the device If the unit is installed underneath a canopy there must be a distance of at least 2 m between the floor and the canopy The following distances should be observed for mainte nance purposes Fig 6 Distances from extern...

Страница 15: ...Assembly and siting EN Fig 8 Top view of attachment points Key 1 For 3 kW unit 550 mm For 6 5 kW unit 560 mm 2 Distance 1000 mm 3 For 3 kW unit 325 mm For 6 5 kW unit 335 mm 4 12 x 20 mm elliptical drilled holes 1 1 2 3 4 ...

Страница 16: ...otected or covered if there is a risk of damage 4 Flexible connecting parts such as connection lines between indoor and outdoor devices that could be come displaced during regular work operations must be protected against mechanical damage 5 The maximum distance between the supports of the copper pipes is 1 m for pipelines with 1 4 to 3 8 1 25 m for pipelines with 1 2 to 5 8 and 2 m for pipelines ...

Страница 17: ... nitrogen filling provided in the factory as an indication that there are no leaks in the cooling circuit 2 Only cut pipes to length using a pipe cutter 3 Never saw pipes as this could create swarf 4 Only solder pipes under nitrogen or helium To this end allow dry inert gas to flow into the pipe at one end of the pipeline which has already been created Before starting introduce a powerful current ...

Страница 18: ...ired fill volume has been added 3 The set volume of refrigerant is determined by weighing the refrigerant bottle during the filling pro cess 4 The additional fill volume or the new total fill volume should be noted on the rating plate and operating manual 6 3 Connecting the condensate discharge Any condensate which may develop is collected in the condensate collecting tray of the internal unit For...

Страница 19: ...in the electronic box to terminals L1 and 11 for the sin gle version and terminals L1 and 11 as well as L2 and 23 remote or ON OFF for the redundant version see section 11 7 3 Circuit diagram external unit In the closed state the system is then deactivated If both terminals are jumpered the status message will appear in the display 6 5 Checking the entire system prior to commissioning Before opera...

Страница 20: ...he rear may reach a high temperature This is intention al since it increases the transmission performance of the heat exchanger in the internal unit Distribute the equipment you wish to install evenly across the 482 6 mm 19 level Close any areas you do not require with 482 6 mm 19 blanking plates Cover the side opposite the internal unit in the enclo sure with an air baffle plate see section 13 Ac...

Страница 21: ...Rittal LCU DX 21 6 Installation EN Fig 13 Partitioning with foamed plastic pieces on the side of the LCU internal unit Key 1 Partitioning above 2 Partitioning inside 3 Partitioning below 3 1 2 ...

Страница 22: ...device 3 Key 1 Manual to request operating statuses 2 Operation permanently illuminated during operation flashes when the system is being booted up 3 Timer no function 4 DEF FAN no function 5 Alarm flashes red in case of malfunction 6 LCD display 1 and 2 displays a fault code in case of an alarm 7 2 Switching the LCU DX on and off 7 2 1 Switching on the internal and external units Once both the in...

Страница 23: ...vice 2 On control and display device 2 keep the Set button held down for 3 seconds Your setting is displayed Using the arrow keys set the same setting as previ ously set on control and display device 1 Confirm this value by pressing the Set button again The setpoint is displayed on control and display unit 2 As a general rule the setpoints on all control compo nents should be set to the same value...

Страница 24: ...ing the ad dresses shown in section 15 Customer service addresses No Description of malfunction LED 1 Operation LED 2 Timer LED 3 DEF FAN LED 4 Alarm Malfunction code in display 1 Clash between operating modes 5 Hz E0 2 Communication malfunction between in ternal and external unit 5 Hz E1 3 Temperature sensor for server air intake defective or missing 5 Hz E2 4 Pipe temperature sensor T2 defective...

Страница 25: ...egularly check the refrigerant circuit and all main components for correct functioning at least once a year according to DIN EN 378 Regularly check for leaks using a suitable device an nually as required by the F gas regulation see section 2 3 3 F gas regulation and section 2 3 4 Chemicals Climate Protection Ordinance Note At an ambient temperature of 40 C the nom inal service life of the built in...

Страница 26: ...Please contact us for advice Caution Risk of damage The LCU DX must not be subjected to temperatures above 50 C during stor age Caution Risk of environmental contami nation Never allow refrigerant from the cooling circuit or oil from the compressor to es cape into the environment Refrigerant and oil must be properly dis posed of in accordance with the valid national legislation and regulations ...

Страница 27: ...e 100 100 Cooling output Nominal cooling output kW L22 L35 3 5 server inlet air temperature Power consumption at nominal cooling output kW L22 L35 1 35 server inlet air temperature Energy Efficiency Ratio EER L22 L35 2 6 Air throughput max m3 h 2 500 Cooling circuit Refrigerant filled weight kg R410A 1 8 Fluid Group 2 Additional refrigerant from the 5th metre g m 30 Max permissible pressure bar PS...

Страница 28: ...ing output Nominal cooling output kW L22 L35 6 2 kW server inlet air temperature Power consumption at nominal cooling output kW L22 L35 3 14 kW server inlet air temperature Energy Efficiency Ratio EER L22 L35 1 97 Air throughput max m3 h 4 800 Cooling circuit Refrigerant filled weight kg R410A 1 8 Fluid Group 2 Additional refrigerant from the 5th metre g m 30 Max permissible pressure bar PS HP 42 ...

Страница 29: ... Settings Position of the sensor on the front of the server Due to the control response the temperature directly at the air outlet of the internal unit may fluctuate between 3 K and 4 K A fluctuation period lasts one to two min utes On average the temperatures at the air outlet of the internal unit are within the tolerance of 2 K Caution The LCU DX may only be operated with refrigerant R410A Use o...

Страница 30: ... output kW min max 1 00 3 50 1 00 3 50 1 00 3 50 Power consumption kW 0 43 0 62 0 45 0 69 0 48 0 68 Tab 11 Exterior temperature 10 C Exterior temperature C 20 Setpoint C 2 K 22 25 28 Cooling output kW min max 1 00 3 50 1 00 3 50 1 00 3 50 Power consumption kW 0 49 0 99 0 46 1 05 0 49 0 68 Tab 12 Exterior temperature 20 C Exterior temperature C 35 Setpoint C 2 K 22 25 28 Cooling output kW min max 1...

Страница 31: ...ng output kW min max 3 00 6 50 3 00 6 50 3 00 6 50 Power consumption kW 1 57 2 06 1 53 2 18 1 66 2 18 Tab 17 Exterior temperature 10 C Exterior temperature C 20 Setpoint C 2 K 22 25 28 Cooling output kW min max 3 00 6 50 3 00 6 50 3 00 6 50 Power consumption kW 1 80 2 63 1 86 2 67 1 89 2 67 Tab 18 Exterior temperature 20 C Exterior temperature C 35 Setpoint C 2 K 22 25 28 Cooling output kW min max...

Страница 32: ...l unit LCU DX 3 kW and 6 5 kW Fig 17 Overview drawing of internal unit LCU DX 3 kW and 6 5 kW redundant version Key 1 Insert for data and supply cables 2 Refrigerant line for single version 1 pair 3 Refrigerant line for redundant version 2 pairs 4 Condensate discharge 2 3 2 3 1 3 3 4 1 ...

Страница 33: ...W and 6 5 kW Fig 18 Dimensions of internal unit LCU DX 3 kW and 6 5 kW Outlet zone for cold air Condensate runoff for left side installation Refrigerant connections Inspection opening for electronics Condensate runoff for right side installation Intake zone for hot air M o u n t i n g h o l e s ...

Страница 34: ...1 6 RI flow chart LCU DX Fig 19 RI flow chart Shut off valve Internal part External part Electronic expansion valve Capillaries Capillaries Condenser Evaporator coil 4 way valve Compressor Cooling Heating Accumulator Refrigerant gas Refrigerant liquid ...

Страница 35: ...trol and display device 1 Control and display device 1 redundant Control and display device 2 DIXELL Control and display device 3 Control and display device 3 WAGO connector X3 Sensor A Optional Fans 1 and 2 Fans 1 4 Midea Motherboard internal unit WAGO connector internal unit A Electrical connection diagram Midea Motherboard internal unit Redundant version only WAGO connector internal unit B ...

Страница 36: ...e switching on off Shielded cable Shielded cable Collective fault signal Operation Connection by the customer Open On COM NC COM NO Caution 230 V Remote switching on off Collective fault signal Operation Open On COM NC Connection by the customer Connection by the customer SK 3311 490 491 492 and 493 Voltage 230 V 1 N PE 50 Hz External unit A Supply lead Connection by the customer SK 3311 491 and 4...

Страница 37: ... Motherboard External temperature sensor Register sensor Hot gas sensor Electronic expansion valve 4 way valve Compressor heater Floor heating DC fan motor Compressor Main supply lead 3 x 2 5 mm Fuse as per table Connection cable to internal unit 3 x 2 5 mm Pilot wire 3 x 0 75 mm Only shielded cable should be used as the pilot wire Inductor coil ...

Страница 38: ... Qty Packs of Evaporator coil control board 1 Display 1 Compressor 1 Inverter motherboard 1 Electronic expansion valve 1 Evaporator coil fan 1 Dixell evaporator coil 1 Temperature sensor hot cold air 1 Refrigerant filter 2 Tab 21 List of spare parts LCU DX ...

Страница 39: ... 13 Accessories Item Model No Qty Packs of Remarks Refrigerant pipe kit 1 Refrigerant pipe kit 20 m insulated for LCU DX 3 kW 3311 495 1 Refrigerant pipe kit 20 m insulated for LCU DX 6 5 kW 3311 496 1 Tab 22 List of accessories LCU DX ...

Страница 40: ...ate up to 4 5 kW heat loss per 7 U and 700 mm depth Front to back cooling principle The devices built into the server enclosure are normally cooled according to the front to back cooling princi ple Under this cooling principle cold air supplied by exter nal air conditioning is blown to the front of the server enclosure The fans in the devices built into the server enclosure direct this air horizon...

Страница 41: ...ddresses For technical queries please contact Tel 49 0 2772 505 9052 E mail info rittal de Homepage www rittal com For complaints or service requests please contact Tel 49 0 2772 505 1855 E mail service rittal de Rittal GmbH Co KG Auf dem Stützelberg 35745 Herborn Germany ...

Страница 42: ... Enclosures Power Distribution Climate Control IT Infrastructure Software Services You can find the contact details of all Rittal companies throughout the world here www rittal com contact 02 2016 ...

Отзывы: