Discharge Pressure

 

a) Faulty condenser temperature regulation

 

a) Check condenser control operation

 

b) Suction shut-off valve partially closed

 

b) Open valve

 

c) Insufficient refrigerant in system

 

c) Check for leaks. Repair and add charge

 

d) Low suction pressure

 

d) See Corrective Steps for low suction pressure below

 

e) Compressor operating unloaded

 

e) See Correction Steps for failure of compressor to load 
up below

 

f) Condenser too large*

 

f) Check condenser rating table against the operation

 

g) Low ambient conditions*

 

g) Check condenser rating tables against the operation

 

  

Suction Pressure

 

a) Lack of refrigerant

 

a) Check or leaks. Repair and add charge

 

b) Evaporator dirty

 

b) Clean chemically

 

c) Clogged liquid line filter-drier

 

c) Replace cartridge(s)

 

d) Clogged suction line or compressor suction 
gas strainers

 

d) Clean strainers

 

e) Expansion valve malfunctioning

 

e) Check and reset for proper superheat. Replace if 
necessary

 

f) Condensing temperature too low

 

f) Check means for regulating condensing temperature

 

g) Compressor will not unload

 

g) See Corrective Steps for failure of compressor to 
unload

 

h) Insufficient water flow

 

h) Adjust gpm.

 

  

Compressor will not unload or load up

 

a) Defective capacity control

 

a) Replace

 

b) Unloader mechanism defective

 

b) Replace

 

c) Faulty thermostat stage or 
broken capillary tube

 

c) Replace

 

d) Stages not set for application

 

d) Reset thermostat setting to fit application

 

  

Содержание R422D

Страница 1: ...rite temp INSTALLATION MAINTENANCE GUIDE WATER CHILLERS...

Страница 2: ...ping guide Engineering Guide 1 for air conditioning systems 3 Water piping Chillers should be designed and installed to meet application requirements Provisions Ethylene or Propylene Glycol must be ma...

Страница 3: ...this feature is standard in ALL compressors with the exception of scrolls Allow the compressor s to warm overnight or at least six hours This is a one time procedure for start up However if the main...

Страница 4: ...000 1 4 1 4 1 4 1 4 3 000 3 8 3 8 3 8 3 8 4 500 1 4 1 4 3 8 3 8 4 500 3 8 3 8 1 2 1 2 6 500 1 4 1 4 3 8 3 8 6 500 3 8 1 2 1 2 1 2 8 500 1 4 3 8 3 8 3 8 8 500 3 8 1 2 1 2 5 8 12 000 3 8 3 8 3 8 1 2 12...

Страница 5: ...ater pipe DO NOT plumb w ith smaller size pipe than noted on this print The bypass line is necessary if units to be cooled have self acting shut off valves Water must circulate through chiller at all...

Страница 6: ...circuit or burnout i Loose wiring i Check all wire junctions Tighten all terminal screws Compressor noisy or vibrating a Flooding of refrigerant into crankcase a Check setting of expansion valve b Im...

Страница 7: ...refrigerant a Check or leaks Repair and add charge b Evaporator dirty b Clean chemically c Clogged liquid line filter drier c Replace cartridge s d Clogged suction line or compressor suction gas strai...

Страница 8: ...ty switch defective d Replace e Worn oil pump e Replace f Oil pump reversing gear stuck in wrong position f Reverse direction of compressor rotation g Worn bearings g Replace compressor h Low oil leve...

Страница 9: ...ot start until fault is corrected f High ambient temperature around the overload relay f Provide ventilation to reduce heat g Failure of second starter to pull in on part winding start system g Repair...

Страница 10: ...original Purchaser User that products manufactured by Rite Temp shall be free from defects in material and workmanship under normal use and service for a period of twelve months from date of shipment...

Страница 11: ...DO NOT USE AUTOMOTIVE OR RV ANTI FREEZE RITE TEMP RECOMMENDS USING EITHER ETHYLENE GLYCOL OR PROPYLENE GLYCOL...

Страница 12: ...rite temp Water Chillers Distributed By RITE TEMP MANUFACTURING INC PO BOX 1275 1704 S 1ST STREET ROGERS AR 72757 800 462 3120 PH 479 986 0727 FAX www ritetemp com...

Отзывы: