BASIC SINGLE HOOK-UP TO CHILLER WATER

CHILLER

EQUIPMENT

TO BE COOLED

SUPPLY

VENT

VENT

WARM OUT

TO DRAIN

COLD IN

WARM IN

COLD OUT

SUPPLY HEADER 1" NPT
RETURN HEADER 1 1/4" NPT

If chiller is installed outside, or
exposed to low  temperature, it
must have antifreeze.  The
crankcase heater must be w ired
direct to stay on continuously.

Use any std. w ater pipe.  DO NOT plumb w ith smaller size pipe than noted on this print.  The bypass line is necessary if units to be cooled have self
acting shut-off valves.  Water must circulate through chiller at all times for proper operation and temperature control.  Place bleeder valve at highest
point and fill unit until w ater discharges from bleeder.  Close bleeder -- unit is full.  Shut off outside w ater supply.

BASIC MULTIPLE HOOK-UP TO CHILLER WATER

EQUIPMENT

TO BE COOLED

SUPPLY
WATER

VENT

VENT

TO DRAIN

WARM
    IN

COLD OUT

CHILLER

EQUIPMENT

TO BE COOLED

 

 

Содержание R422D

Страница 1: ...rite temp INSTALLATION MAINTENANCE GUIDE WATER CHILLERS...

Страница 2: ...ping guide Engineering Guide 1 for air conditioning systems 3 Water piping Chillers should be designed and installed to meet application requirements Provisions Ethylene or Propylene Glycol must be ma...

Страница 3: ...this feature is standard in ALL compressors with the exception of scrolls Allow the compressor s to warm overnight or at least six hours This is a one time procedure for start up However if the main...

Страница 4: ...000 1 4 1 4 1 4 1 4 3 000 3 8 3 8 3 8 3 8 4 500 1 4 1 4 3 8 3 8 4 500 3 8 3 8 1 2 1 2 6 500 1 4 1 4 3 8 3 8 6 500 3 8 1 2 1 2 1 2 8 500 1 4 3 8 3 8 3 8 8 500 3 8 1 2 1 2 5 8 12 000 3 8 3 8 3 8 1 2 12...

Страница 5: ...ater pipe DO NOT plumb w ith smaller size pipe than noted on this print The bypass line is necessary if units to be cooled have self acting shut off valves Water must circulate through chiller at all...

Страница 6: ...circuit or burnout i Loose wiring i Check all wire junctions Tighten all terminal screws Compressor noisy or vibrating a Flooding of refrigerant into crankcase a Check setting of expansion valve b Im...

Страница 7: ...refrigerant a Check or leaks Repair and add charge b Evaporator dirty b Clean chemically c Clogged liquid line filter drier c Replace cartridge s d Clogged suction line or compressor suction gas strai...

Страница 8: ...ty switch defective d Replace e Worn oil pump e Replace f Oil pump reversing gear stuck in wrong position f Reverse direction of compressor rotation g Worn bearings g Replace compressor h Low oil leve...

Страница 9: ...ot start until fault is corrected f High ambient temperature around the overload relay f Provide ventilation to reduce heat g Failure of second starter to pull in on part winding start system g Repair...

Страница 10: ...original Purchaser User that products manufactured by Rite Temp shall be free from defects in material and workmanship under normal use and service for a period of twelve months from date of shipment...

Страница 11: ...DO NOT USE AUTOMOTIVE OR RV ANTI FREEZE RITE TEMP RECOMMENDS USING EITHER ETHYLENE GLYCOL OR PROPYLENE GLYCOL...

Страница 12: ...rite temp Water Chillers Distributed By RITE TEMP MANUFACTURING INC PO BOX 1275 1704 S 1ST STREET ROGERS AR 72757 800 462 3120 PH 479 986 0727 FAX www ritetemp com...

Отзывы: