BASIC SINGLE HOOK-UP TO CHILLER WATER
CHILLER
EQUIPMENT
TO BE COOLED
SUPPLY
VENT
VENT
WARM OUT
TO DRAIN
COLD IN
WARM IN
COLD OUT
SUPPLY HEADER 1" NPT
RETURN HEADER 1 1/4" NPT
If chiller is installed outside, or
exposed to low temperature, it
must have antifreeze. The
crankcase heater must be w ired
direct to stay on continuously.
Use any std. w ater pipe. DO NOT plumb w ith smaller size pipe than noted on this print. The bypass line is necessary if units to be cooled have self
acting shut-off valves. Water must circulate through chiller at all times for proper operation and temperature control. Place bleeder valve at highest
point and fill unit until w ater discharges from bleeder. Close bleeder -- unit is full. Shut off outside w ater supply.
BASIC MULTIPLE HOOK-UP TO CHILLER WATER
EQUIPMENT
TO BE COOLED
SUPPLY
WATER
VENT
VENT
TO DRAIN
WARM
IN
COLD OUT
CHILLER
EQUIPMENT
TO BE COOLED