Top view of
WaterMatic 100 shown
with Riser Tube
underneath
Models 100, 150, 150S, 300, & 1000
WaterMatic Fountain Installation Instructions
A.
Location -
Putting the fountain in a location that offers protection from the wind will enhance the
performance of the unit. Livestock will tend to gather in a protected area, enticing them to drink more. If possible,
the side that supply line enters the fountain should be opposite of prevailing wind for additional protection to the
supply line.
B.
Water Supply Line –
The horizontal underground water line (#1) should be sized to account for pressure
drop, relating to distance, at least 3/4” in diameter and 1’ below normal frost depth. A 3/4” vertical supply pipe
(#2) is recommended. A shut-off valve (#3) may be installed under the fountain for servicing. For optimum
serviceability a stop and waste valve can be installed below frost level to drain water back when the unit is not in
use. This can be obtained from your local plumber. Flush water supply line before connecting to fountain. Water
supplies with material such as sand, rust, etc. may require a filter to keep valve working properly.
C.
Riser Tube
– Install a riser tube (#4) around pipe to provide room for plumbing and to accommodate
optional shut-off valve. Ensure that the water supply line is centered in the riser tube. Do not add any insulation in
the riser tube, as it provides a path for frost. For optimum water line protection, use the 12” outside diameter
insulated Ritchie Thermal Tube. Use whatever combination of Thermal Tubes is required to reach at least 1'
below frost line.
For the 100, 150, and 150S units, the riser tube must NOT extend above the
concrete platform, see drawing below.
Ritchie Thermal Tubes
18158
1’ top section
16417
2’ top section
16612
4’ top section
16416
2’ extension
NOTE:
The supply line touching the riser tube is the most common cause of the supply line freezing.
Do not surround the supply line with insulation, wood, or other foreign material. Any foreign material in
the tube may cause frost to migrate to the supply line causing it to freeze.
WaterMatic Series Instruction Manual
1
August 13, 2022