61  Configure the inverter prior to operation 

61.1 Frequency 

setting 

The AC-Frequency may be selected by DIP-Switch S4 on the front panel as follows.  

AC-Frequency (Hz) 

S1 

50 0 

60 I 

To activate the new selected value, the inverter must be turned ON and OFF (Reset) . 

61.2 

Sleep mode/ Power saving mode (automatic load detection) 

Power Saving Mode 

S4 

enable 0 

disable I 

To activate the new selected value, the inverter must be turned ON and OFF (Reset) . 

61.3 

Optional PC RS 232 connection  

Baud Rate 

S2 

S3 

2400 I  I 

4800 0  I 

9600 I  0 

19200 0 

To activate the new selected value, the inverter must be turned ON and OFF (Reset) . 

Caution! If the inverter is detecting a load it takes 15 to 18 seconds before the output power is available (delayed). 
Be careful when working with machinery (we recommend to disable the sleep mode). 

61.4 

Output Voltage Tune ACV-ADJ 

Tune VR ( VAC ) output voltage from 100 – 120 VAC or 200 – 240 VAC 
The VAC value will gradually increase, tune VR from right to left. 

62 Operation 

The Inverter is controlled by an ON / OFF switch located on the front panel of the inverter.  

Engaging  
Set the power switch to the ON position; you will hear three beep. After that, you will hear the continuous sound 
from internal alarm. Then, the AC voltage shows on the display. The Inverter is ready to use. 

Power down 
Switch to  „OFF-Position“. All LED’s are dark. The inverter output is OFF. 

Remark
Even if the inverter is switched to off, it is not disconnected from the battery. It still draws very little power from the 
battery. If you don’t need the inverter for an extended period disconnect it from the battery to avoid low discharge 
of battery.  

Содержание HIPHOP pro

Страница 1: ...DE Bedienungsanleitung GB User s manual FR Manuel d utilisation ES Manual de usuario SWING pro JAZZ pro HIPHOP pro...

Страница 2: ...s 15 23 Einstellungen am Inverter vor der Inbetriebnahme 15 23 1 Frequenz w hlen 15 23 2 Ausgangsspannung w hlen 15 23 3 Schlafmode automatische Lasterkennung 15 23 4 RS 232 Schnittstelle 15 24 Betrie...

Страница 3: ...2 Sleep mode Power saving mode automatic load detection 35 55 3 Output Voltage setting 35 55 4 Optional PC RS 232 connection 35 56 Operation 35 57 Display 36 57 1 Output Voltage Indicator 36 57 2 Outp...

Страница 4: ...conomie d nergie d tection automatique de charge 55 87 4 Connexion PC RS232 55 88 Utilisation 56 89 Affichage 56 89 1 VAC Affichage de la tension de sortie 56 89 2 Affichage du courant de sortie 56 8...

Страница 5: ...de energ a detecci n de carga autom tica 75 118 4 Conexi n opcional PC RS 232 75 119 Operaci n 76 120 Visor 76 120 1 Indicador de voltaje de salida 76 120 2 Indicador de corriente de salida 76 120 3 I...

Страница 6: ...Sie sich bitte an Ihren Fachh ndler Er hilft Ihnen gerne weiter 4 Einf hrung Diese Installations Anleitung hilft Ihnen bei der Installation und Inbetriebnahme Ihres Ger tes Diese Installations Anleit...

Страница 7: ...rden von der Garantie ausgeschlossen Bei Eingriffen in das Ger t durch Dritte oder zerst rtem Garantiesiegel erlischt jegliche Garantie Beanstandungen k nnen nur anerkannt werden wenn Sie das Ger t im...

Страница 8: ...le eines Einbaus des Ger tes in einen Schaltschrank sorgen Die Kondensatoren k nnen auch nach dem Trennen der beiden DC Leitungen noch gef hrliche Spannung f hren Das Ger t darf deshalb nur von geschu...

Страница 9: ...ziert werden Entfernen Sie unn tige Verbraucher Das Ger t muss mit dem Ein Ausschalter zur ckgestellt werden Andere St rungen berpr fen Sie die Erdung des Inverters und Ihres Systems Volt pro Zelle Di...

Страница 10: ...berlastf higkeit des Inverters ab Wird der Ger te in H hen von mehr als 1000 m ber Meer eingesetzt so darf dem Ger t aufgrund der verminderten K hlleistung weniger als die angegebene Nennlast im Dauer...

Страница 11: ...ss genug ist 15A Schliessen Sie nun die beiden Batterie Kabel an Plus Pol der Batterie an DC Schutzschalter oder Sicherung Minus Pol der Batterie an Minus Klemme Die rote Farbe wird immer f r Batterie...

Страница 12: ...ss der Schalter in die Stellung REMOTE geschaltet werden 19 LED Anzeige 19 1 berspannungsschutzanzeige OVP Bei zu hoher Eingangsspannung Batteriespannung schaltet der Inverter automatisch aus Die Anze...

Страница 13: ...13 85 V 1 0 20 Technische Daten 200VA 350VA...

Страница 14: ...1000 48 230 6 15 40 Verbinden Sie nun die beiden konfektionierten Batterie Kabel mit den Klemmen des Inverters Plus Pol der Batterie an DC Schutzschalter oder Sicherung Minus Pol der Batterie an Minu...

Страница 15: ...er Inverter muss Ein und Ausgeschaltet Reset werden um den neuen Wert zu aktivieren 23 2 Ausgangsspannung w hlen Ausgangsspannung VAC S4 S5 200 0 0 220 0 1 230 1 0 240 1 1 Der Inverter muss Ein und Au...

Страница 16: ...terie verhindert 25 Anzeige Taste Select Durch wiederholtes dr cken der SELECT Taste wird die gew nscht Information in folgender Reihenfolge angezeigt VAC AMP WATT VDC TEMP HZ Wenn ein Fehler auftritt...

Страница 17: ...ei bertemperatur schaltet der Inverter automatisch aus Die Anzeige OTP erscheint im Display Vorsicht K hlt sich der Inverter wieder ab schaltet das Ger t automatisch wieder ein bertemperatur kann Aufg...

Страница 18: ...18 85 V 1 0 26 Technische Daten JAZZ pro 700 JAZZ pro 1000...

Страница 19: ...eichstromkabel in der richtigen Gr sse Zur Berechnung der Kabelgr sse steht Ihnen auf unserer Homepage ein Rechner zur Verf gung Zur groben Bestimmung des DC Kabels kann auch die nachfolgende Tabelle...

Страница 20: ...nau 27 3 Erdung Damit der Personenschutz gew hrleistet ist muss das Ger t geerdet werden Erden Sie das Ger t an der daf r vorgesehenen grossen Erdklemme mit einem 8 10mm2 Kabel AWG 8 an der Hauserde B...

Страница 21: ...muss Ein und Ausgeschaltet Reset werden um den neuen Wert zu aktivieren 29 3 RS 232 Schnittstelle Baud Rate S2 S3 2400 1 1 4800 0 1 9600 1 0 19200 0 0 Der Inverter muss Ein und Ausgeschaltet Reset wer...

Страница 22: ...terie verhindert 31 Anzeige Taste Select Durch wiederholtes dr cken der SELECT Taste wird die gew nscht Information in folgender Reihenfolge angezeigt VAC AMP WATT VDC TEMP HZ Wenn ein Fehler auftritt...

Страница 23: ...r Inverter automatisch aus Die Anzeige OTP erscheint im Display Vorsicht K hlt sich der Inverter wieder ab schaltet das Ger t automatisch wieder ein bertemperatur kann Aufgrund mangelnder K hlung bei...

Страница 24: ...24 85 V 1 0 32 Technische Daten HIPHOP pro 1500 HIPHOP pro 2000...

Страница 25: ...25 85 V 1 0 HIPHOP pro 3000...

Страница 26: ...pro 200 12 230 und 200 24 230 und 200 48 230 Sine wave Inverter SWING pro 350 12 230 und 350 24 230 und 350 48 230 Sine wave Inverter JAZZ pro 700 12 230 und 700 24 230 und 700 48 230 Sine wave Inver...

Страница 27: ...difications or breaking the warranty label without a written permission from RIPEnergy AG means that the warranty is lost immediately Always return the units in it s original package and completely as...

Страница 28: ...the unit may overheat and an automatic shut off may occur Even if DC Wiring is not longer connected to the batteries inbuilt large capacitors may hold Dc Voltage for an extended period of time The in...

Страница 29: ...ple A 12V Battery contains 6 single cells a 24V Battery contains 12 single cells etc 45 Maintenance Only little maintenance is required to keep your inverter and system operating reliable The inverter...

Страница 30: ...100m elevation 47 2 Installation These units must be only installed by qualified authorized and trained personnel familiar with the locally applicable standards and taking into consideration all rele...

Страница 31: ...car for correct size 15A Connect the cables with care to the battery inline fuse If possible use coloured cables Red colour means battery positive while black is used for battery negative Reversing p...

Страница 32: ...onnect it from the battery to avoid low discharge of battery 51 LED Indicator 51 1 Overload protection LED OLP The overload indicator indicates that the power inverter has shut itself down When output...

Страница 33: ...33 85 V 1 0 52 Technical data 200VA 350VA...

Страница 34: ...r damage to the inverter and is not covered by warranty Note Large capacitors in the units may hold DC Voltage for a long period of time Also a spark may occur while connecting the DC cables or insert...

Страница 35: ...e the new selected value the inverter must be turned ON and OFF Reset Caution If the inverter is detecting a load it takes 15 to 18 seconds before the output power is available delayed Be careful when...

Страница 36: ...light on AMP as show as output current value 57 3 Output Watts Indictor LED displays light on WATT as show as output watts value 57 4 Input DC Voltage Indictor LED displays light on VDC as show as inp...

Страница 37: ...levels above its rating or because it has been installed in a location which does not allow it to dissipate heat properly The power inverter will automatically back up once it has cooled off 57 10 Ov...

Страница 38: ...38 85 V 1 0 58 Technical data JAZZ pro 700 JAZZ pro 1000...

Страница 39: ...or terminals Always use DC cables of the correct size to avoid fire and other damage You may use the following recommendations for best performance of inverter Inverter DC Cable AWG mm2 Inline fuse A...

Страница 40: ...is also connected to earth Use a 8 10mm2 cable AWG 8 and connect it to the earth terminal of the inverter This is also important for lighting protection Do not operate the power inverter without conne...

Страница 41: ...er is available delayed Be careful when working with machinery we recommend to disable the sleep mode 61 4 Output Voltage Tune ACV ADJ Tune VR VAC output voltage from 100 120 VAC or 200 240 VAC The VA...

Страница 42: ...light on AMP as show as output current value 63 3 Output Watts Indictor LED displays light on WATT as show as output watts value 63 4 Input DC Voltage Indictor LED displays light on VDC as show as inp...

Страница 43: ...because it has been installed in a location which does not allow it to dissipate heat properly The power inverter will automatically back up once it has cooled off 63 10 Overload protection indicator...

Страница 44: ...44 85 V 1 0 64 Technical data HIPHOP pro 1500 HIPHOP pro 2000...

Страница 45: ...45 85 V 1 0 HIPHOP pro 3000...

Страница 46: ...ondant bien votre appareil Il est valable pour les appareils suivants Onduleur sinuso dal SWING pro 200 12 230 et 200 24 230 et 200 48 230 Onduleur sinuso dal SWING pro 350 12 230 et 350 24 230 et 350...

Страница 47: ...t l annulation imm diate de la garantie Toujours retourner les produits dans leur emballage d origine et compl tement assembl s Une courte description de la panne nous aidera mieux vous servir RIPEner...

Страница 48: ...urchauffe et un arr t automatique peut se produire M me si le c blage de l entr e DC n est plus connect la batterie les gros condensateurs l int rieur peuvent conserver une tension continue leurs born...

Страница 49: ...on nominale lorsqu on utilise des batteries au plomb est 2 VDC l ment Exemple une batterie de 12V contient 6 l ments une batterie de 24V contient 12 l ments etc 77 Maintenance Il faut peu de maintenan...

Страница 50: ...appareils doivent tre install s uniquement par du personnel qualifi autoris form et familier avec les normes localement applicables et tenant compte de toutes les mesures et conseils de s curit en vi...

Страница 51: ...cigare de votre voiture V rifier que le fusible de votre voiture a le bon calibre 15A Connecter avec soin les c bles de l entr e DC au fusible d entr e et la batterie Si possible utiliser des c bles d...

Страница 52: ...z pas l onduleur durant une longue p riode le d connecter de la batterie pour viter une d charge profonde de la batterie 83 Affichage par LED 83 1 LED pour la protection contre la surtension OVP L aff...

Страница 53: ...53 85 V 1 0 84 Caract ristiques techniques 200VA 350VA...

Страница 54: ...000 48 230 6 15 40 Assembler les c bles pour l entr e DC et les connecter au bornier de l onduleur DC AC Le couple pour serrer les vis du bornier est de 12 13 Nm Connecter avec soin l autre extr mit d...

Страница 55: ...S lectionn e de la tension de sortie Tension de sortie VAC S4 S5 200 0 0 220 0 1 230 1 0 240 1 1 Pour mettre en service la nouvelle valeur choisie l onduleur DC AC doit tre mis sur les positions ON pu...

Страница 56: ...terie 89 Affichage Touche de s lection Quand vous poussez par impulsions successives la touche Select il s affiche diff rentes donn es sur l cran telles que VAC AMP WATT et ainsi de suite Quand un dys...

Страница 57: ...ce qu il a t utilis une puissance sup rieure ses possibilit s ou parce qu il a t install un endroit qui ne lui permet pas de dissiper la chaleur correctement L onduleur red marrera automatiquement qua...

Страница 58: ...58 85 V 1 0 90 Caract ristiques techniques JAZZ pro 700 JAZZ pro 1000...

Страница 59: ...ereuses des c bles ou des borniers Toujours utiliser des c bles pour l entr e DC de dimensions correctes pour viter le feu ou tout autre dommage Vous pouvez utiliser les recommandations suivantes pour...

Страница 60: ...ipale de l onduleur DC AC Il et encore plus s r d utiliser un interrupteur diff rentiel de 15 ou 30mA dans le circuit en sortie de l onduleur DC AC 91 3 Mise la masse La protection par le fil de terre...

Страница 61: ...choisie l onduleur DC AC doit tre mis sur les positions ON puis OFF Reset 92 3 Connexion PC RS232 Vitesse de transmission Bauds S2 S3 2400 0 0 4800 0 1 9600 1 0 19200 1 1 Pour mettre en service la no...

Страница 62: ...terie 94 Affichage Touche de s lection Quand vous poussez par impulsions successives la touche Select il s affiche diff rentes donn es sur l cran telles que VAC AMP WATT et ainsi de suite Quand un dys...

Страница 63: ...sance sup rieure ses possibilit s ou parce qu il a t install un endroit qui ne lui permet pas de dissiper la chaleur correctement L onduleur red marrera automatiquement quand il aura refroidi 94 10 Af...

Страница 64: ...64 85 V 1 0 95 Caract ristiques techniques HIPHOP pro 1500 HIPHOP pro 2000...

Страница 65: ...65 85 V 1 0 HIPHOP pro 3000...

Страница 66: ...200 12 230 e 200 24 230 e 200 48 230 Inversor de onda sinusoidal SWING pro 350 12 230 e 350 24 230 e 350 48 230 Inversor de onda sinusoidal JAZZ pro 700 12 230 e 700 24 230 e 700 48 230 Inversor de o...

Страница 67: ...a de la etiqueta de garant a sin un permiso escrito de RIPEnergy AG significan que la garant a se pierde inmediatamente Devuelva siempre las unidades en su paquete original y completamente ensamblado...

Страница 68: ...ar conectados a la salida de la corriente alterna de los inversores El inversor se destruir a inmediatamente La carcasa puede calentarse hasta 80 C Nunca obstruya las rejillas ni coloque otros art cul...

Страница 69: ...ble instalado en la salida AC Bajo Voltaje DC El voltaje de la bater a ha ca do por debajo de 1 75V Celda Compruebe el fusible de la bater a Cargue la bater a si la carga no resuelve el problema puede...

Страница 70: ...aci n e instalaci n de su inversor Aseg rese que usted es consciente de las reglas locales y de las medidas de seguridad 110 1 Consumo de energ a requerido Antes de conectar sus aparatos al inversor c...

Страница 71: ...el tama o correcto 15A Conecte los cables con cuidado a la bater a fusible de l nea Si es posible use cables coloreados El color rojo significa el polo positivo mientras que el negro es usado para el...

Страница 72: ...d no necesita el inversor durante un per odo ampliado descon ctelo de la bater a para evitar una baja descarga de la bater a 114 Indicador LED 114 1 Protecci n de sobrecarga LED OLP El indicador de so...

Страница 73: ...73 85 V 1 0 115 Datos t cnicos 200VA 350VA...

Страница 74: ...ntinua y conecte los cables a los terminales del inversor La torsi n para apretar los tornillos terminales es 12 13 Nm Conecte el otro extremo de los cables de la corriente continua reunidos con cuida...

Страница 75: ...ado 118 2 Ajuste del Voltaje de salida Voltaje de salida VAC S4 S5 200 0 0 220 0 1 230 1 0 240 1 1 Para activar el nuevo valor seleccionado el inversor debe encenderse y apagarse ON y OFF Reiniciado 1...

Страница 76: ...Cuando pulsa secuencialmente Select key se mostrar n varios estados en la pantalla tales como VAC AMP WATT etc tera Cuando ocurra un funcionamiento defectuoso su visor parpadear en la pantalla 120 1 I...

Страница 77: ...orque se ha hecho funcionar a niveles de potencia por encima de su intervalo o porque ha sido instalado en una posici n que no permite que se disipe el calor correctamente El inversor de potencia se r...

Страница 78: ...78 85 V 1 0 121 Datos t cnicos JAZZ pro 700 JAZZ pro 1000...

Страница 79: ...erminales Siempre use cables de corriente continua del tama o correcto para evitar el fuego y otros da os Puede usar las siguientes recomendaciones para un mejor funcionamiento del inversor Inversor C...

Страница 80: ...ral del inversor Incluso es m s seguro usar un interruptor de salida de tierra de 15mA o 30mA en la instalaci n de la corriente alterna 122 3 Conexi n a tierra La protecci n del cable de tierra es s l...

Страница 81: ...Reiniciado 124 2 Modo de espera Modo de ahorro de energ a detecci n de carga autom tica Schlafmode S4 Modo de ahorro de energ a 0 disponible 1 Para activar el nuevo valor seleccionado el inversor debe...

Страница 82: ...Cuando pulsa secuencialmente Select key se mostrar n varios estados en la pantalla tales como VAC AMP WATT etc tera Cuando ocurra un funcionamiento defectuoso su visor parpadear en la pantalla 126 1 I...

Страница 83: ...a niveles de potencia por encima de su intervalo o porque ha sido instalado en una posici n que no permite que se disipe el calor correctamente El inversor de potencia se reiniciar autom ticamente un...

Страница 84: ...84 85 V 1 0 127 Datos t cnicos HIPHOP pro 1500 HIPHOP pro 2000...

Страница 85: ...85 85 V 1 0 HIPHOP pro 3000...

Отзывы: