HE Series Infrared Gas Heater Installation and Operation Manual

 

TABLE 4

 

 

GAS TYPE

 

LINE PRESSURE 

 

INCHES WATER COLUMN

 

MANIFOLD PRESSURE 

 

(tap at gas valve outlet) 

INCHES WATER COLUMN 

 

MINIMUM

 

MAXIMUM

 

Natural Gas

 

5.0

 

14.0

 

3.5

 

LP Gas

 

11.0

 

14.0

 

10.0

 

NOTE:

 Access to the manifold pressure test port is located on the top of the valve. A 3/16" Al-

len Key is required.  A 

manometer  

should  be  used to check the manifold pressure. Gauges 

which measure in ounces or PSI are not accurate enough to measure or set the pressure. 

 

 

GAS CONNECTION

 

Connection  between the  gas supply  pip-

ing and the appliance must be in accord-
ance with local and national codes, 

ANSI 

Z223.1 (NFPA 54) 

in the USA. 

 

The HE Series is  approved  as  a Vented 

Overhead Heater and may be rigid piped 

to the building gas supply (

also see Flex-

ible Gas Connection Option, next  page

). 

Check  with  local  authority  for  locally  re-

quired gas connection.

 

 

 

WHEN USING A FLEXIBLE GAS CON-

NECTION TO THE APPLIANCE: 

 

 

13. 

GAS SUPPLY 

-

 GAS CONNECTION 

… 

continued

 

Provide a 1/8 in (3.2 mm) NPT plugged tapping, accessible for test gauge con-
nection, immediately upstream of the gas supply connection to the heater.  

 

The gas supply should be checked first with heater turned 

OFF

” 

followed by an-

other check with heater turned 

ON

”.

 

This appliance and its main gas valve must be disconnected from the gas supply 

piping system during any pressure testing of the gas supply piping system at test 

pressure in excess of 1/2 psi (3.5 kPa). 

 

This appliance must be isolated from the piping system by closing the equipment 
shut off valve (field supplied) during any pressure testing of  the gas piping sys-

tem at test pressure equal to or less than 1/2 psi (3.5 kPa).

I

 

MPORTANT: Minimum supply line pressure at the inlet to the heater regulator must not 
be lower  than 5.0 inches of water column pressure for natural gas, and not be lower  

than 10.0 inches of water column pressure for LPG. The supply gas pressure must be 
checked with all heaters in operation. 

 

Installation of  a gas line (trap) 

drip leg

” 

is required at the inlet connection tee following the 

pipe drop to the heater. Failure to provide a 

drip leg

” 

could result in condensation and foreign 

matter  passing into the gas valve. Failure to install a 

drip leg

” 

in the gas line can cause prop-

erty damage, injury or death and will void the heater warranty. 

 

Содержание RHE1S40N

Страница 1: ......

Страница 2: ...y result causing prop erty damage personal injury or loss of life Do not store or use gasoline or other flammable vapours and liquids in the vicinity of this or any other gas fired appliance WHAT TO D...

Страница 3: ...Horizontal Vent 20 21 Horizontal Vent Terminal Location 22 Vertical Vent Through Roof 23 12 COMBUSTION AIR REQUIREMENTS 24 13 GAS SUPPLY CONNECTION 25 ORIENTATION OF FLEXIBLE GAS CONNECTION if applic...

Страница 4: ...4 HE Series Infrared Gas Heater Installation and Operation Manual...

Страница 5: ...adults should be alerted to the hazards of high sur face temperatures and should stay away to avoid burns or clothing ignition Young children should be carefully supervised when they are in the same...

Страница 6: ...4 in USA and as indicated in this manual Refer to Sections 11 12 WARNING Start Up SMOKE Condition During start up the heating of material coatings used in the production process of tubes and reflector...

Страница 7: ...be posted either adjacent to the heater thermostat or in the absence of such thermostat in a conspicuous location In addition to stored or stationary material consideration must also be given to move...

Страница 8: ...FIGURE 1 MINIMUM CLEARANCES TO COMBUSTIBLES 3D VIEW Table 1 also lists values next page TUBE REFLECTOR MOUNTED UP TO 30 ANGLE EITHER DIRECTION TUBE REFLECTOR MOUNTED HORIZONTALLY Always maintain at le...

Страница 9: ...a nearby surface The stated clearance to combustibles represents a surface temperature of 117F 65C above room temperature It is the installer s responsibility to ensure that building materials with a...

Страница 10: ...T inches cm The minimum clearance to combustibles below this heater C is 53 inches 1346 cm Subtract C 53 inches 1346 mm from T Height above floor to get value H Enter the calculated value H on the sig...

Страница 11: ...r other flammable material should not be placed on or near the appliance Any safety screen or guard removed to service an appliance must be replaced prior to operating the appliance Installation and r...

Страница 12: ...be protected from damage by aircraft and other objects such as cranes and movable scaffolding D Heaters must be located so as to be accessible for servicing and adjustment 2 LABOR REQUIRMENTS Two pers...

Страница 13: ...he minimum clearances between the heater and combustibles as shown in FIG 1 TABLE 1 Pages 8 9 It is the installer s responsibility to ensure that building materials with a low heat tolerance which may...

Страница 14: ...burner housing MODEL GUIDELINE MOUNTING HEIGHT ft m DISTANCE HEATER LONG AXIS PARALLEL TO WALL HORIZONTAL ft m ANGLE MOUNTED HE Series 8 12 2 4 3 7 5 12 1 5 3 7 MINIMUM COMBUSTIBLE CLEARANCE BEHIND 1...

Страница 15: ...end the heat er from a structural member that can adequately support the weight of the heater Always maintain the required minimum clearances to combustible ma terials and vehicles see pages 7 to 10 I...

Страница 16: ...a structural member s of sufficient strength and integrity to support the weight of the heater 7 The heater comes fully assembled from the factory For locations where there is con strained access for...

Страница 17: ...Series Infrared Gas Heater Installation and Operation Manual FIGURE 5 HEATER DIMENSIONS Turbulators factory installed in tube Burner side tube 39 99 cm FIGURE 6 HEATER SUSPENSION HORIZONTAL UP TO 30...

Страница 18: ...ter The attachment of suspension hardware to the structure will be as required by site structural condi tions installation codes and or local engineering specifications Other types or systems of re st...

Страница 19: ...wances for heater expansion must be made in the venting Improper installation can result in property damage injury or death This heater has a positive vent pressure A vent termination cap is recommend...

Страница 20: ...apters Field Supplied Allow free expansion and contraction of the system and free flow of vent gas A wall thimble is not required through a non combustible wall Seal pipe penetration Seal all vent con...

Страница 21: ...p see clearance information previous page and next page Install the termination cap a minimum of 6 inches 15 cm from the outside wall to the inside edge of terminal opening to minimize back pressure c...

Страница 22: ...rom center of terminal 9 23 cm E Below an unventilated soffit 3 7 6 cm F To an outside corner 12 30 cm G To an inside corner 12 30 cm H To each side of centerline extended above a meter regulator asse...

Страница 23: ...or insulated with a suitable material as approved and specified by the insulation manufacturer to withstand tem perature up to 460 F 238 C Use an approved B vent termination cap as supplied by the ma...

Страница 24: ...l and national codes ANSI Z223 1 NFPA 54 in the USA The HE Series is an ap pliance approved as a Vented Overhead Heater under ANSI Z21 86 CSA 2 32 Vented Gas Fired Space Heating Appliances TEST FOR LE...

Страница 25: ...uge con nection immediately upstream of the gas supply connection to the heater The gas supply should be checked first with heater turned OFF followed by an other check with heater turned ON This appl...

Страница 26: ...ay be used Refer and ad here to local code requirements and NFPA 54 Section 9 6 in the USA If a flexible gas connector is used it must be installed in the orientation shown in Figure 14 be low as requ...

Страница 27: ...mostat TruTemp Thermostat or 24V controller signal must be used for the post purge feature to function A line voltage Thermostat or an ON OFF switch will disable the post purge feature A maximum night...

Страница 28: ...ation to ensure no debris is blocking the vent and that the integrity and construction of the vent piping is sound and no leakage is occurring 4 Visually inspect the burner flame periodically to ensur...

Страница 29: ...WIRING DIAGRAM FENWAL S87J PAGE 30 CHANNEL MICRO 50N PAGE 31 24V OR 120 VOLT THERMOSTAT SINGLE HEATER PER THERMOSTAT NOTE Heater must be controlled by 24Vac Thermostat to enable post purge by the igni...

Страница 30: ...30 HE Series Infrared Gas Heater Installation and Operation Manual 20 MULTIPLE TUBE HEATERS per THERMOSTAT Fenwal DSI P N 905000020...

Страница 31: ...t any time less than the 1 hour auto reset recovery from lockout requires a manual reset by either resetting the thermostat or removing 24 volts for a period of 5 seconds Flame Failure Re Ignition If...

Страница 32: ...ATION Proper location of the electrode assembly is important for optimum system performance The electrode assem bly should be located so that the spark gap is inside the flame envelope about 1 inch 2...

Страница 33: ...OMMENDED ACTION S 1 Dead A Miswired check electrical supply 120Vac 5 B Transformer bad 24Vac 10 C Fuse Circuit breaker bad D Bad control check LED for steady on 2 Thermostat on no blower output A Misw...

Страница 34: ...34 HE Series Infrared Gas Heater Installation and Operation Manual This Page Intentionally Left Blank...

Страница 35: ...35 HE Series Infrared Gas Heater Installation and Operation Manual This Page Intentionally Left Blank...

Страница 36: ...36 HE Series Infrared Gas Heater Installation and Operation Manual This Page Intentionally Left Blank...

Страница 37: ...37 HE Series Infrared Gas Heater Installation and Operation Manual This Page Intentionally Left Blank...

Страница 38: ...38 HE Series Infrared Gas Heater Installation and Operation Manual This Page Intentionally Left Blank...

Страница 39: ...39 HE Series Infrared Gas Heater Installation and Operation Manual This Page Intentionally Left Blank...

Страница 40: ...al on the Ignition Control to establish a spark Pull the wire away from the stud and note the length of gap at which spark discontinues A spark length of 1 8 in 3 mm or more indicates satisfactory vol...

Страница 41: ...GNITER IS SHORTING OUT CHECK GROUND WIRING REMOVE AND INSPECT IGNITER AND LEAD CHECK BOOT OF THE IGNITION CABLE FOR SIGNS OF MELTING OR OVERHEATING IF YES TAKE PROTECTIVE ACTION TO SHIELD CABLE AND BO...

Страница 42: ...DOWNS EVEN THOUGH OPERATION IS NOR MAL AT THE TIME OF CHECKOUT CHECK FOR EXCESSIVE HEAT AT SENSOR INSU LATOR AS TEMPERATURES ABOVE 1000 F 538 C CAUSES SHORT TO GROUND CHECK FLAME SIGNAL IN SERIES WITH...

Страница 43: ...S ARE COMPATIBLE WITH THIS HEATER AND TO THIS EQUIPMENT HAS BEEN FACTORY FIRED AND TESTED PRIOR TO SHIPMENT HOWEVER THIS APPLIANCE IS NOT PLUG PLAY IT RE QUIRES COMMISSIONING AND FIELD ADJUSTMENT SPEC...

Страница 44: ...EADING AT THE IGNITION MODULE VOLTS WHAT IS THE FLAME SIGNAL STRENGTH IN uA FROM SENSOR uA microamps IS HEATER CONTROLLED BY A THERMOSTAT YES NO IS THE THERMOSTAT STRATEGICALY LOCATED YES NO WHAT IS T...

Страница 45: ...mm x 305 mm Burner Weight 26 pounds 11 8 kg Dimensions 16 L x 10 25 W x 10 75 H 406 mm x 260 mm x 273 mm Tube Reflector System Weight 60 pounds 27 kg Dimensions 103 5 L x 16 5 W x 7 5 H 2629 mm x 420...

Страница 46: ...elow 31 HIGH ALTITUDE INSTALLATION Field Conversion Kit required to convert between fuel gas types Part number 903000039 HE Series Natural Gas to Propane Gas Conversion Kit Part number 903000040 HE Se...

Страница 47: ...Safety Snap Hooks 2 pkg of 25 pkg of 100 903000071 903000064 903000070 TruTemp Infrared Setback Thermostat True comfort control for radiant heating systems senses and averages ambient and radiant temp...

Страница 48: ...The pins that extend from each side of the two guard sections are inserted into these sets of holes Fig 1 Fig 2 Step 1 On ONE SIDE of the reflector remove the bottom screws Qty 3 that fasten the refle...

Страница 49: ...e screws at the bottom edge of the reflector into the three hangers Fig 7 Fig 9 Fig 10 Center Fig 11 End Notes 1 To bend the pins use needle nose pliers to hold the guard screen securely Fig 8 and ano...

Страница 50: ...ESTRICTOR 908000012 Air Intake Restrictor 1 5 Hole 40 NG LP 10 BLOWER 908000013 Blower Assembly Tube Burner 11 MANIFOLD BUSHING 906000076 Manifold bushing 12 90 DEGREE ELBOW FITTING 1 2 906000077 Stre...

Страница 51: ...LECTRICAL CORD 905000028 Cord electrical 6 24 IGNITION SPARK CABLE See Above 25 IGNITER KIT 906000082 Spark Igniter Gasket Kit 26 SIGHT GLASS ASSEMBLY 909000118 Sight glass assembly tube heater 27 FLA...

Страница 52: ...Positions tube in hanger reflector system 31 PREFORMED U TUBE 906000147 Preformed U Tube 17 ft tube length 32 HANGER 909000134 System Hanger 33 REFLECTOR 906000131 Reflector 34 REFLECTOR END PLATE 90...

Страница 53: ...53 HE Series Infrared Gas Heater Installation and Operation Manual NOTES...

Страница 54: ...54 HE Series Infrared Gas Heater Installation and Operation Manual NOTES...

Страница 55: ...55 HE Series Infrared Gas Heater Installation and Operation Manual NOTES...

Страница 56: ......

Отзывы: