Infinity REU-V2632FFUG / HD200i REU-VM2632FFUC
- 33 -
Issue 1 - 16/12/09 ©Rinnai
9)
Removal of
outgoing water thermistor
a. Remove thermistor fixing screw.
b. Remove 2 pin connection outgoing water thermistor
Heat Exchanger Thermistor
10)
Removal of
heat exchanger thermistor
a. Remove thermistor holder
b. Remove 2 pin connector
11)
Removal of
air intake thermistor
a. Remove fan motor
b. Remove 2 pin connector of inlet thermistor
c. Remove inlet thermistor (care with O-ring)
d. Thermistor
12)
Removal of
Bypass Servo
a. Remove fan motor (Refer to 14)
b. Remove 3 pin connector
c. Remove 2 pin connector
d. Remove 6 pin connector and 5 pin connector
e. Remove bracket for water connection tube.
f. Removal of
inlet water connection
g. Remove bypass servo and water flow servo
h. Remove fitting screws of bypass servo
Содержание REU-V2632FFUG
Страница 1: ...DRDAFT SERVICE MANUAL To Suit Models Does NOT Suit Other Models REU V2632FFUG REU VM2632FFUC...
Страница 13: ...Infinity REU V2632FFUG HD200i REU VM2632FFUC 8 Issue 1 16 12 09 Rinnai 6 Operational Flow Chart...
Страница 14: ...Infinity REU V2632FFUG HD200i REU VM2632FFUC 9 Issue 1 16 12 09 Rinnai Operational Flow Chart Continued...
Страница 15: ...Infinity REU V2632FFUG HD200i REU VM2632FFUC 10 Issue 1 16 12 09 Rinnai 7 Cutaway Diagram...
Страница 33: ...Infinity REU V2632FFUG HD200i REU VM2632FFUC 28 Issue 1 16 12 09 Rinnai...
Страница 47: ...Infinity REU V2632FFUG HD200i REU VM2632FFUC 42 Issue 1 16 12 09 Rinnai...
Страница 48: ...Infinity REU V2632FFUG HD200i REU VM2632FFUC 43 Issue 1 16 12 09 Rinnai...
Страница 49: ...Infinity REU V2632FFUG HD200i REU VM2632FFUC 44 Issue 1 16 12 09 Rinnai...