4. Water Controllers
A
l
l
water controllers must be installed in accordance with the relevant operation/installation instructions supplied with the
water heater or controllers.
Troubleshooting
Water Controller not showing display - (Wired Water Controllers)
• Check that the correct number and combination of co ntrollers have b een installed for the specific model
Infinity. Refer to controller compatibility table below.
• Check water controller is turned ON.
• Check there is 12VDC power supply available to the controller from the Ezi-connect terminals.
• If there is 12VDC available from the Ezi Connect but no controller display, check wiring between Ezi-connect
and controller is sound.
• If there is no power from the Ezi-connect terminals, but the hot water functions correctly, replace PCB.
Error Code 12 as soon as hot water tap is turned ON.
• Check 12VDC internal wiring to Ezi-connect terminal is not crushed or shorted.
• Rectify wiring and re-close Ezi-connect cover carefully.
Water Controller not showing display - (Wireless Water Controllers)
• Ensure transceiver module is mounted in the correct location, as per wireless controller installation instructions.
• Ensure 2 x AA batteries are in good working order and installed with the correct polarity within the wireless
controller. (Battery polarity details on rear of wireless controller)
• Ensure distance between wireless controller and transceiver does not exceed 50 metres.
• Ensure channel has been allocated to each wireless controller.
• Ensure w ireless co ntroller has been pro grammed to the transceiver correctly , as per wireless controller
installation instructions.
Water Controller Compatibility Table
Care should be taken to ensure power supply to the Infinity is isolated when connecting /
disconnecting controller wiring or transponder on wireless controllers. Failure to isolate
power supply may result in damage to the appliance PCB.
Care should be taken when closing the Ezi-connect access panel, to ensure internal wiring
for controllers is not shortened or crushed.
Wireless Only
Installation
A maximum of 4 wireless water controllers can be fitted with the following limitation:
Only
ONE
MC-502RC
/ MC-503RC
can be set as the Master Controller.
Wired &
Wireless
Installations
A maximum of 4 water controllers can be fi tted. Any combination of delux e, universal and
wireless controllers can be used with the following limitation:
Only ONE master controller can be installed. This can be a MC-100V, a MC-91Q (when
programmed as a master controller) or a MC-502RC/MC-503RC water controller.
Up to TWO BC-100V water controllers can be installed.
The FOURTH water controllers in any installation MUST BE a MC-502RC / MC-503RC
or a MC91Q.
NOTE
Содержание REU-V2632FFUG
Страница 1: ...DRDAFT SERVICE MANUAL To Suit Models Does NOT Suit Other Models REU V2632FFUG REU VM2632FFUC...
Страница 13: ...Infinity REU V2632FFUG HD200i REU VM2632FFUC 8 Issue 1 16 12 09 Rinnai 6 Operational Flow Chart...
Страница 14: ...Infinity REU V2632FFUG HD200i REU VM2632FFUC 9 Issue 1 16 12 09 Rinnai Operational Flow Chart Continued...
Страница 15: ...Infinity REU V2632FFUG HD200i REU VM2632FFUC 10 Issue 1 16 12 09 Rinnai 7 Cutaway Diagram...
Страница 33: ...Infinity REU V2632FFUG HD200i REU VM2632FFUC 28 Issue 1 16 12 09 Rinnai...
Страница 47: ...Infinity REU V2632FFUG HD200i REU VM2632FFUC 42 Issue 1 16 12 09 Rinnai...
Страница 48: ...Infinity REU V2632FFUG HD200i REU VM2632FFUC 43 Issue 1 16 12 09 Rinnai...
Страница 49: ...Infinity REU V2632FFUG HD200i REU VM2632FFUC 44 Issue 1 16 12 09 Rinnai...