Pressure and Temperature Relief (PTR) Valve

A combination PTR valve is supplied with the water heater� It is an important safety device and 

MUSTBE

 fitted in 

all installations before the water heater is operated�

DONOT

 use the valve if the sensing probe has been bent or it is damaged in some other way�

The PTR valve is to be screwed to the connection marked “PTR Valve” at the top of the water heater�
The thread 

MUSTBE

 sealed with an approved sealing tape� Make sure the sealing tape does 

NOT

 hang over 

the end of the thread of the valve as this may block the waterway and prevent the valve from operating properly�

To screw the valve into the water heater connection use a wrench on the spanner flats and 

NOT

 the valve body�  

Leave the valve outlet pointing downwards� A copper drain pipe 

MUSTBE

 fitted to the valve outlet in accordance 

with the section "Relief Valve Drain Lines" on the bottom of page 17.

The valve body 

MUST BE

 insulated in accordance with local regulatory requirements and AS/NZS 3500.4 to 

optimise performance and energy efficiency. Insulation 

MUSTBE

 applied in a manner that ensures it does 

NOT

 

interfere with the operation of the valve�  Insulation material 

MUSTBE

 weatherproof and UV resistant if exposed� 

Expansion Control Valve (ECV)

In areas of scaling water an ECV 

MUSTBE

 fitted on the cold water line between the non-return valve and the 

connection to the water heater to protect the PTR valve and the water heater, as per the diagrams under “Installation 

Configurations”. It 

MUSTBE

 the last valve on the cold inlet before the water heater�

Local regulatory authorities may require that an ECV be fitted. The ECV is to be supplied and fitted by the installer.  

Refer to the section Water Quality for more information on scaling water�
A copper drain pipe 

MUSTBE

 fitted to the valve outlet in accordance with the section "Relief Valve Drain Lines" 

on the bottom of page 17�
The valve body 

MUST BE

insulated in accordance with local regulatory requirements and AS/NZS 3500.4 to 

optimise performance and energy efficiency. Insulation 

MUSTBE

 applied in a manner that ensures it does 

NOT

 

interfere with the operation of the valve�  Insulation material 

MUSTBE

weatherproof and UV resistant if exposed�

Pressure Limiting Valve (PLV)

A PLV is to be fitted if the supply pressure exceeds the limits shown in Table 2 “Ratings & Other Specifications" 

on page 11 as per the diagrams under “Installation Configurations”. The PLV is to be supplied and fitted by the 

installer�

Relief Valve Drain Lines

Copper drain lines of size DN15 

MUSTBE

 fitted to the ECV (if fitted) and the PTR valve. Use disconnection unions 

to connect drain lines to the valves�

The configuration of drain lines 

MUSTBE

 in accordance with local regulatory requirements and the requirements 

of AS/NZS3500�4�
The length should be as short as possible on a continuous downward slope with no restrictions�   Length should 

NOT

 exceed 9 metres with no more than three 45° bends. If a drain line discharges into a tundish, the drain line 

from the tundish 

MUSTNOT

 be less than DN20� The drain line from a tundish 

MUST

 meet the same requirements 

as drain lines from relief valves�

The drain lines from the PTR valve and ECV (if fitted) from an individual water heater may be interconnected 

subject to local regulatory authority requirements and AS/NZS3500.4. The termination point 

MUST

 also comply 

with local regulatory requirements and  AS/NZS3500.4. Drain lines 

MUSTNOT

 discharge into a safe tray�

The outlet of drain lines 

MUSTNOT

 be obstructed and be positioned so that they are readily discernible but 

NOT

 

cause injury, damage or nuisance.
In areas where water pipes are prone to freezing, drain lines 

MUSTBE

insulated and 

NOT

 exceed 300mm in 

length� In this case the drain line 

MUST

 discharge into a tundish through an air gap of between 75mm and 150 mm�

INSTALLATION

Содержание QRESS315L336

Страница 1: ...Quick Recovery Electric QRE Operation Installation Manual Models QRESS80L336 QRESS80L348 QRESS315L336 QRESS315L348 QRESS315L360...

Страница 2: ...3000 AS NZS 3500 4 Local Regulations and Municipal Building Codes including local OH S requirements This appliance must be installed maintained and removed by an Authorised Person For continued safet...

Страница 3: ...Dimensions 11 Table 2 Ratings Other Specifications 11 Installation Configurations 12 Hot Water Plumbing System Example Multiple Installation 12 Hot Water Plumbing System Example No TLD 13 Hot Water Pl...

Страница 4: ...TR Valve 17 Expansion Control Valve ECV 17 Pressure Limiting Valve PLV 17 Relief Valve Drain Lines 17 Electrical Connections 18 Commissioning 19 Wiring Diagram 80L 19 Wiring Diagram 315L 20 To fill tu...

Страница 5: ...le materials near this appliance This appliance is NOT suitable for use as a spa pool or swimming pool heater WARNING NOTICE TO VICTORIAN CONSUMERS This appliance MUST BE installed by a person license...

Страница 6: ...is too hot Always Test the temperature of the water with your elbow before placing your child in the bath also carefully feel water before bathing or showering yourself Supervise children whenever th...

Страница 7: ...son It is normal for the PTR valve to release a small quantity of water through the drain pipe during heating If the valve dribbles or leaks continuously try easing the valve gear for a few seconds Th...

Страница 8: ...ds and a volume of water sufficient for daily usage is heated during the set period and stored The Off Peak supply is usually cheaper Electricity supply types and tariffs vary according to the local e...

Страница 9: ...riction in the hot tap or failure of the cold water supply to the heater Check for water flow at the other hot taps and that the cold water isolation valve is fully open High electricity bills If you...

Страница 10: ...t 3 6kW Includes Gasket 80 or 315 L 95110046 Element 4 8kW Includes Gasket 10003735 Element 6 0kW Includes Gasket 315 L only 10003743 3 Terminal Block 80 or 315 L 26401708 4 Thermostat R SH ADJ 60 80...

Страница 11: ...A Cylinder Rated Pressure kPa PTR Valve Rated Pressure kPa ECV Rated Pressure kPa ECV Fitted Fit PLV if mains pressure exceeds kPa Recommended PLV pressure rating kPa QRESS315L336 3 6 15 850 850 700...

Страница 12: ...equal length and plumbed see example figure above to ensure pressure drops are balanced For multiple systems and tanks ensure the connecting pipework is configured to balance system pressure drop B B...

Страница 13: ...ating Valve Isolating Valve PLV ECV OR WATER HEATER Non return Valve COLD SUPPLY Non return Valve Non return Valve WATER HEATER Temperature Limiting Device TLD Non return Valve PTR VALVE Supplied TO D...

Страница 14: ...RETURN PIPE WORK WITH TLD COLD SUPPLY Isolating Valve ECV TO DRAIN Non return Valve PLV KITCHEN LAUNDRY NON TEMPERED SUPPLY BATHROOM ENSUITE TO DRAIN PTR VALVE Supplied WATER HEATER Not Supplied Non r...

Страница 15: ...result of water leakage the water heater MUST BE installed with a safe tray overflow tray and drain Construction installation and draining of the safe tray MUST comply with local regulatory requiremen...

Страница 16: ...Installation Configurations WARNING Valves with pressure ratings other than specified MUST NOT be used An isolation valve and non return valve MUST BE fitted in the cold water supply to the water hea...

Страница 17: ...ve outlet in accordance with the section Relief Valve Drain Lines on the bottom of page 17 The valve body MUST BE insulated in accordance with local regulatory requirements and AS NZS 3500 4 to optimi...

Страница 18: ...cal cable connections to the water heater Electrical cable entry to the water heater is via a 25mm hole provided beneath the front cover fitting of an approved M25 weatherproof cable gland at the elec...

Страница 19: ...Single Number of Throws Single Dial Colour Pink Temp Range 60 to 80 C Dial Set At 70 C Cut Off 60 C 3 Differential 8 C 4 Reset Manual 3 1 4 5 2 ST1205113 RESET 3 1 4 5 2 ST1205113 RESET 3 1 4 5 2 ST12...

Страница 20: ...3 RESET 3 1 4 5 2 ST1205113 RESET L1 L2 L3 N 1 2 3 Active Neutral Active Active Neutral Earth Neutral Thermostat Specifications ST1205113 Number of Poles Single Number of Throws Single Dial Colour Pin...

Страница 21: ...now be forced out of the taps 3 Close each tap when water runs freely without air bubbles 4 Check all plumbing connections and pipe work for water leaks 5 Connect the water heater to the electricity s...

Страница 22: ...Rinnai 22 SS QRE HW IM NOTES...

Страница 23: ...Rinnai 23 SS QRE HW IM NOTES...

Страница 24: ...0 340 Cost of a local call higher from mobile or public phones For further information visit www rinnai com au or email enquiry rinnai com au Rinnai has a Service and Spare Parts network with personne...

Отзывы: