Infinity REU-V2626W / HD200E REU-V2632WC
- 40 -
Issue 1 -
10/10/03
©Rinnai
Pressure Setting
① Remove pressure test point sealing screw
from gas control
② Connect digital manometer with test
point
③ Turn ON 240V power supply
④ Turn ON remote controller switch
⑤ Turn ON main gas valve fully
⑥ Change Dipswitch No. 7 for low combustion
⑦ Turn ON outgoing water tap
⑧ Set pressure low with solenoid valve
adjustment
Low Capacity
(kPa)
N.G.
0.14
Prop.G
0.22
Содержание HD200E REU-V2632WC
Страница 13: ...Infinity REU V2626W HD200E REU V2632WC 8 Issue 1 10 10 03 Rinnai 4 Dimensions...
Страница 18: ...Infinity REU V2626W HD200E REU V2632WC 13 Issue 1 10 10 03 Rinnai 6 Cutaway Diagram...
Страница 19: ...Infinity REU V2626W HD200E REU V2632WC 14 Issue 1 10 10 03 Rinnai 7 Operational Flow Chart...
Страница 20: ...Infinity REU V2626W HD200E REU V2632WC 15 Issue 1 10 10 03 Rinnai 8 Operation Principles REU V2626W REU V2632WC...
Страница 25: ...Infinity REU V2626W HD200E REU V2632WC 20 Issue 1 10 10 03 Rinnai 11 Wiring Diagram REU V2626W...
Страница 26: ...Infinity REU V2626W HD200E REU V2632WC 21 Issue 1 10 10 03 Rinnai REU V2632WC...
Страница 44: ...Infinity REU V2626W HD200E REU V2632WC 39 Issue 1 10 10 03 Rinnai Change Gas Type Switch on PCB...
Страница 56: ...Infinity REU V2626W HD200E REU V2632WC 51 Issue 1 10 10 03 Rinnai 20 Exploded Diagram...
Страница 57: ...Infinity REU V2626W HD200E REU V2632WC 52 Issue 1 10 10 03 Rinnai...
Страница 58: ...Infinity REU V2626W HD200E REU V2632WC 53 Issue 1 10 10 03 Rinnai...
Страница 59: ...Infinity REU V2626W HD200E REU V2632WC 54 Issue 1 10 10 03 Rinnai...
Страница 67: ...Infinity REU V2626W HD200E REU V2632WC Issue 1 10 10 03 Rinnai Notes...
Страница 68: ......