Rinnai 15
HW_GI_FM10 OIM
APPLIANCE FLUE TERMINAL
Ref.
ef.
Min clearances mm
Natural draught
a
Belo w eaves, balconies and other projections:
For
appliance
s up to 50 MJ/h input
300
For
appliance
s over 50 MJ/h input
500
b
From the ground, above a balcony or other surface *
300
c
From a return w all or external corner *
500
d
From a
gas meter
(M) (see Note 5)
(see Clause 5.11.5.9 for vent terminal location of regulator)
(see Table 6.7 for Ne w Zealand requirements)
1 000
e
From an electricity meter or fuse box (P)
†
(see Note 5)
500
f
From a drain pipe or soil pipe
150
g
Horizontally from any building structure * or obstruction facing a
terminal
500
h
From any other
flue terminal
, co wl, or combustion air intake *
500
j
Horizontally from an openable windo w, door, non-mechanical air inlet, or any other opening
into a building with the exception of sub-floor ventilation:
Appliance
s up to 150 MJ/h input*
500
Appliance
s over 150 MJ/h input up to 200 MJ/h input*
1 500
Appliance
s over 200 MJ/h input up to 250 MJ/h input*
1 500
Appliance
s over 250 MJ/h input*
1 500
All
fan-assisted
appliance
s, in the direction of discharge
—
k
From a mechanical air inlet, including a spa blo wer
1 500
n
Vertically below an openable windo w, non-mechanical air inlet, or any other opening into a
building with the exception of sub-floor ventilation:
For
space heaters up to 50 MJ/h input
150
For
other
appliance
s up to 50 MJ/h input
500
For
appliance
s over 50 MJ/h input and up to 150 MJ/h input
1 000
For
appliance
s over 150 MJ/h input
1 500
*
†
Unless
appliance
is
certified
for closer installation.
Prohibited area belo w electricity meter or fuse box extends to ground level.
NOTES:
1
Where dimensions
c, j
or
k
cannot be achieved an equivalent horizontal distance measured
diagonally from the nearest discharge point of the terminal to the opening may be deemed by
the
Technical Regulator
to comply.
2
See Clause 6.9.4 for restrictions on a
flue terminal
under a covered area.
3
See Figure J3 for minimum clearances required from a
flue terminal
to an
LP Gas
cylinder
. A
flue terminal
is considered to be a source of ignition.
4 For
minimum clearances
not addressed above acceptance should be obtained from the
Technical Regulator
.
5
Minimum clearances
d
and
e
also apply to any combustion air intake openings of appliances.
FIGURE 6.2 (in part) LOCATION OF FLUE TERMINALS OF BALANCED FLUE,
ROOM-SEALED, FAN-ASSISTED OR OUTDOOR APPLIANCES
Flue terminal
Fan assisted flue appliance only
Gas meter
Electricity meter or fuse box
Mechanical air inlet
FLUEING
Содержание FM10LA
Страница 1: ...Gas Instantaneous Water Heater Operation Installation Manual Models FM10NA FM10LA...
Страница 10: ...Rinnai 10 HW_GI_FM10 OIM This page is intentionally blank...
Страница 21: ...Rinnai 21 HW_GI_FM10 OIM NOTES...
Страница 22: ...Rinnai 22 HW_GI_FM10 OIM NOTES...
Страница 23: ...Rinnai 23 HW_GI_FM10 OIM...