Model
CHS199100CU
Appliance Type
Commercial Hybrid Water Heating System Consisting of Condensing Tankless
Water Heater, Insulated Storage Tank, Pump and Controller
Installation Type
Internal (Indoor) Commercial Applications
Category
Category IV
Ignition System
Direct Electronic Ignition
Product Weight
431 lb (195 kg)
Gas Consumption Btu/h (kW/h)
Minimum: 15,000 (4.3) Maximum: 199,000 (58.3)
Water Supply Pressure
150 PSI (Maximum)
Temperature Setting
98° F (37° C) to 185° F (85° C)
Tank Volume
119 Gallons (450 Liters)
First Hour Delivery*
317 Gallons (1,200 Liters)
Sound Level
49 dB
Electrical Data
Normal
265 W
Standby
44 W
Freeze Protection
148 W
Max Current
5.5 A
Fuse
Tankless Water Heater Engine: 10 Amps, Controller: 10 Amps
Gas Supply Pressure**
Natural
3.5
-
10.5 in. w.c.
Propane
8.0
-
13.5 in. w.c.
By
-
Pass Flow Control
Electronic
Connections
Gas Supply Inlet: 3/4 in. MNPT Hot Water Outlet: 1
-
1/2 in. MNPT
Cold Water Inlet: 1
-
1/2 in. MNPT
Electric Connections
Appliance: AC 120 Volts, 60Hz.
Integrated Temperature Controller: DC 12 Volts (Digital)
Water Temperature Control
Simulation Feed Forward and Feedback
Commercial Energy Star Certified (CU199i)
Yes
Complies with South Coast Air Quality
Management District 14 ng/J or 20 ppm NOx
Emission Levels (CU199i)
Yes
Product
Number
Gas
Type
Input
Thermal
Efficiency
U.S. Gallon / HR Liters / HR at Temperature Rise Indicated
Tank
Capacity
°F
30°F
40°F
50°F
60°F
70°F
80°F
90°
100°F
110°F
120°F
130°F
140°F
BTU/HR
kW
°C
17°C
22°C
28°C
33°C
39°C
44°C
50°C
56°C
61°C
67°C
72°C
78°C
CHS199100CU
NG/
LP
199,000
58
97%
119 U.S.
Gals.
GPH
780
585
468
390
334
292
260
234
213
195
180
167
450
LPH
2,953
2,214
1771
1476
1264
1105
984
886
806
738
681
632
Recovery Capabilities
Specifications
* First Hour Delivery Rating is a theoretical calculation based on 70% usable tank capacity (Tank Capacity x .70 + (recovery) = First Hour Rating
** The maximum gas supply pressure must not exceed the value specified by the manufacturer.
Rinnai products are continually being updated and improved; therefore, specifications are subject to change without prior notice.