June 2017 Digital Network Adapter DNA100
ACTIVITY LOG PRINTER
A serial RS232C printer can be attached to a DNA100 to provide a complete activity log of system. All stations to
be logged must have the printer defined in their
SAR
. The DNA100 must be configured to drive a printer by
setting SW3-7 off and SW3-8 on. The printer must have a RS232C serial interface. The standard print format is
80 columns, 66 lines per page.
Figure C16
shows a sample printed page of the Crisis Alert Activity Log Printer.
Description of Status Headings :
DATE
The D
ATE
this page was printed. If the date changes before the page is full a new page is printed
with events for the new date.
TIME
The actual time the event on each line occurred.
PRI
P
RIORITY
of the incoming event.
STATUS
Status of each event (C
ALL
, F
AULT
, C
ONNECT
, P
ARK
, C
ANCEL
, R
ESET
, A
LARM
).
EXT
The dial number of the station generating the event.
LOCATION DESCRIPTION
Written description of the location or device stated under the EXT heading.
CONNECTED TO
Indicates the station connected to the device generating the event.
Description of Status :
CALL
C
ALL
to annunciator. This only indicates a call condition was placed from type 1 sub station or
type 3 sub-master station.
CONNECT
Indicates an event being handled in accordance with the annunciator display through Crisis
Alert. (See H
ANDLING
A
N
E
VENT
earlier in this Chapter or in Chapter D - DAD104)
FAULT Indicates a hardware problem for the location printed and sent to the annunciator five seconds after the
fault occurs. The time delay is due to a noise filter in the DXC901 that only records solid faults.
PARK
An event that was placed in P
ARK
. A new C
ONNECT
message will be generated when this event is
retrieved again.
CANCEL
Indicates a disconnection of two devices that were previously connected. For example, a
master station that presses the ‘X’ key on the terminal keyboard using a DNA100 will generate a C
ANCEL
event.
ALARM A
LARM
to annunciator. This indicates that an alarm condition was placed from a type 3 sub-master
station.
PWRFAIL
The CB901 has detected loss of Power. It is now running on battery backup.
ACKNOWL
An event has been acknowledged by a DAD104 (such as PWRFAIL).