6 Operations and Functions

 

6-1. Gas alarm activation 

 
 

 

- 34 - 

 

 
 
 
 

Operations and Functions 

 
 
 
 

6-1. Gas alarm activation 

 
Gas alarm: Triggered when the concentration of detected gas reaches or exceeds the alarm setpoint value. 
<<Auto-Reset>> 
 

NOTE 

The alarm setpoint is factory-set. Although the alarm delay time (standard: 2 seconds) works in the 
detector to prevent a false activation, it can be cancelled if not needed. 
 
 

<Display Operation> 

 

Gas Concentration Display 

In case of over the detection range (Over Scale), "

∩∩∩∩

" is displayed on the LED. 

 

Power Indicator Lamp (POWER: Green) 

During operation, this lights up continuously. 
 

Alarm Indicator Lamp (ALM: Red) 

It lights up when the alarm setpoint value is reached to or exceeded. 
 
 

<Alarm Activation> 

It lights up when the gas concentration reaches or exceeds the alarm setpoint value. (only when the alarm is 
used) 
The alarm activation is reset automatically when the gas concentration drops below the alarm setpoint 
value. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Alarm delay time (2 seconds) 

Alarm lamp (ALM) 

Alarm setpoint 

C

onc

en

tr

ation
 

Time 

Содержание SD-1D-AS

Страница 1: ...PT2E 2894 Smart Transmitter Gas Detector Head SD 1D AS TYPE GP H TYPE NC H Operating Manual PT2E 161 PT2 161...

Страница 2: ...an alarm setting below our standard alarm setpoint may trigger a false alarm 3 If use in safety unit the analog signal output of the detector must be used for an indicator or external recorder If the...

Страница 3: ...Operate 26 5 1 Preparation for start up 26 5 2 Basic operating procedures 27 5 3 How to start the detector 28 5 4 Modes 29 5 5 Maintenance mode User 30 5 6 Flow Rate Adjustment 33 5 7 How to exit 33 6...

Страница 4: ...he alarm activation when the gas concentration is over the setting value This detector is a safety unit not an analyzer or densitometer which performs quantitative qualitative analysis measurement for...

Страница 5: ......

Страница 6: ......

Страница 7: ......

Страница 8: ......

Страница 9: ......

Страница 10: ......

Страница 11: ...ct Components 3 1 Main unit and standard accessories 9 3 Product Components 3 1 Main unit and standard accessories Main Unit including a cable gland or an adapter ATEX IECEx Specification TIIS Specifi...

Страница 12: ......

Страница 13: ......

Страница 14: ...switch menus or change a value DOWN 5 Power lamp Power lamp Detection mode It lights up in green Maintenance mode It blinks in green 6 Alarm lamp Alarm lamp It lights up in red when the alarm setpoin...

Страница 15: ......

Страница 16: ......

Страница 17: ......

Страница 18: ......

Страница 19: ...ning is impossible the following protective measures can be taken Protection against lightning Take appropriate measures in accordance with the importance of the facilities and the environment Provide...

Страница 20: ......

Страница 21: ......

Страница 22: ......

Страница 23: ......

Страница 24: ......

Страница 25: ......

Страница 26: ......

Страница 27: ......

Страница 28: ...ector Connect the detector to a grounding circuit Check that the wiring is connected to external device properly Check that the power supply voltage is compliant with the specifications Check that the...

Страница 29: ......

Страница 30: ......

Страница 31: ......

Страница 32: ......

Страница 33: ......

Страница 34: ......

Страница 35: ......

Страница 36: ...ay Operation Gas Concentration Display In case of over the detection range Over Scale is displayed on the LED Power Indicator Lamp POWER Green During operation this lights up continuously Alarm Indica...

Страница 37: ...d Access the gas leak point equipped with a protective gear to avoid dangers caused by possibly remaining gases and check whether gases remain or not by using a portable gas detector Check that the po...

Страница 38: ......

Страница 39: ......

Страница 40: ...ntain the performance as a safety unit Maintenance item Maintenance content Daily mainte nance Monthly mainte nance Regular mainte nance Power supply check Check that the power lamp lights up Concentr...

Страница 41: ...ow rate by using an external flow meter to verify the correctness of the flow rate indicator on the detector If the flow rate is incorrect performs the flow rate adjustment Filter check Checks the dus...

Страница 42: ......

Страница 43: ......

Страница 44: ...ous Electrical Settings Display Display various electrical settings This is not used by the user 2 6 Enter the factory mode This is not used by the user 2 7 Return to the user mode rET is displayed Pr...

Страница 45: ......

Страница 46: ......

Страница 47: ......

Страница 48: ......

Страница 49: ......

Страница 50: ......

Страница 51: ......

Страница 52: ......

Страница 53: ......

Страница 54: ......

Страница 55: ......

Страница 56: ......

Страница 57: ...nsulation transformer Cable abnormalities open circuit not connected short circuit Check the wiring of detector and related devices around it Abnormal operations Disturbances by sudden surge noise etc...

Страница 58: ...mpletely For information on actions such as removal filter please contact RIKEN KEIKI Disturbance by noise Turn off and restart the detector If such a symptom is observed frequently take appropriate m...

Страница 59: ...gas than alarm setpoint value without piping delay time Gas alarm type Single alarm H Gas alarm display ALM lamp lighting red Gas alarm pattern Auto recover Fault alarm self diagnosis System failure...

Страница 60: ...n rapidly vary Operating humidities Below 95 RH non condensing Structure Wall mounting sampling unit Cu Specification or SUS Specification Explosion protected construction Flame proof structure Explos...

Страница 61: ...ystem Two wire analog transmission digital transmission HART communication or Three wire analog transmission in common with power supply power supply signal common Transmission specifications 4 20 mA...

Страница 62: ...10 Product Specifications 10 1 List of specifications 60 Outline Drawings SD 1D...

Страница 63: ...ion system Two wire analog transmission digital transmission HART communication or Three wire analog transmission in common with power supply power supply signal common Transmission specifications 4 2...

Страница 64: ...Auto recover Transmission system Two wire analog transmission digital transmission HART communication or Three wire analog transmission in common with power supply power supply signal common Transmis...

Страница 65: ......

Страница 66: ...element with a mixture of gas inert alumina and glass sintered on it When a combustible gas comes into contact with the surface of the detecting element with new ceramic oxidation catalyst sintered on...

Страница 67: ...mit LEL of the combustible gas to be detected is set to 100 ppm A concentration unit that means part per million of the combustible gas to be detected Calibration Adjusts the readings to the calibrati...

Страница 68: ...details Issue date 0 First issue 10 4 2019 1 Declaration of Conformity 12 23 2019 2 Declaration of Conformity 4 1 2020 3 Safety information Declaration of Conformity 8 1 2020 4 Safety information Decl...

Страница 69: ......