PT1E-0930
22
5-5-2.Confirmation of alarm level
This section is used to check preset alarm level.
UP switch ON DOWN switch ON
5-5-3.Change of alarm level
This section is used to change alarm levels.
①Press UP switch in detector mode, and the 1
st
alarm
level (AL1) is shown.
Press DOWN switch in detection mode, and the 2
nd
alarm level (AL2) is shown.
PW/TR AL2
■ □
SKIP AL1
□ □
PW/TR AL2
■ □
SKIP AL1
□ □
CAUTION
Gas alarm is not triggered except in detection mode.
When leave it alone on maintenance mode, this returns to
detection mode automatically after 10 hours.
①Press MODE switch for over 3 seconds, and
maintenance mode starts.
②Select 「1-2」 with UP/DOWN switch.
③When press SET switch, 1
st
alarm level (AL1) can
be checked. When press it again, 2
nd
alarm level
(AL2) can be checked.
④To change alarm levels (AL1, AL2), adjust them with
UP/DOWN switch and then, press SET switch.
⑤To return detection mode, press MODE switch for
over 3 seconds.
SKIP mode light turns off which shows detection
mode.
PW/TR AL2
■ □
SKIP AL1
◎ □
PW/TR AL2
■ □
SKIP AL1
◎ □
PW/TR AL2
■ □
SKIP AL1
◎ ◎
PW/TR AL2
■ ◎
SKIP AL1
◎ □
SET
switch
PW/TR AL2
■ ◎
SKIP AL1
◎ □
PW/TR AL2
■ □
SKIP AL1
□ □