20/60
7 Communication Settings
7-1
Using the system with a local connection
IP addresses must be set for the product, the PC used to view and operate the system
screen, and the individual gas detectors before using the system. The following figure shows
an example in which gas detector information is displayed at position [GD_001] on the Chart
(list screen). The IP addresses shown are examples when the product IP address is left at
the default value. The following description is based on this example.
NOTE
•
Choose the IP address settings aaa.bbb.ccc based on your particular system setup.
ddd should be set to a value in the range 97 to 254, and should differ from the value for
eee. For more information on setting procedures, refer to ‘
7-3 Configuring various settings
p. 37
•
For more information on the system screen layout, refer to ‘
p. 41
GADMS-L01
IP: aaa.bbb.ccc.ddd
(Default: 192.168.100.101)
Gas detector
IP: aaa.bbb.ccc.1
(Example:
192.168.100.1)
PC
IP: aaa.bbb.ccc.eee
(Example:
192.168.100.190)
PoE hub
Ethernet
Содержание GADMS Lite
Страница 32: ...31 60 Enter an Ewon name optional then click Next Click Create Click Launch Setup Wizard for USB SD Card...
Страница 33: ...32 60 Select Ethernet Click Next...
Страница 50: ...49 60 8 4 Summary History alarm summary and history Displays the status of alarms that have occurred...
Страница 52: ...51 60 8 5 Settings setting information screen Displays the status of alarms that have occurred...