7 — English
SYMBOLS
ELECTRICAL
EXTENSION CORD CABLE SIZE
Refer to the table below to ensure the cable size of the extension cords you use are capable of carrying the required load.
Inadequate size cables can cause a voltage drop, which can damage the appliance and overheat the cord.
Current in
Amperes
Load in Watts
Maximum Allowable Cord Length
At 120V
At 240V
#8 Wire
#10 Wire
#12 Wire
#14 Wire
#16 Wire
2.5
300
600
1000 ft.
600 ft.
375 ft.
250 ft.
5
600
1200
500 ft.
300 ft.
200 ft.
125 ft.
7.5
900
1800
350 ft.
200 ft.
125 ft.
100 ft.
10
1200
2400
250 ft.
150 ft.
100 ft.
50 ft.
15
1800
3600
150 ft.
100 ft.
65 ft.
20
2400
4800
175 ft.
125 ft.
75 ft.
25
3000
6000
150 ft.
100 ft.
30
3600
7200
125 ft.
65 ft.
40
4800
9600
90 ft.
Operation of this equipment may create sparks that can start fires
around dry vegetation. A spark arrestor may be required. The operator should contact
local fire agencies for laws or regulations relating to fire prevention requirements.
WARNING
AVERTISSEMENT
L’utilisation de cet équipement peut créer des étincelles
susceptibles d’enflammer la végétation sèche. Il peut être nécessaire d’utiliser un
pare-étincelles. L’utilisateur doit communiquer avec le service local d’incendie pour
connaître toutes les lois et tous les règlements portant sur les exigences en matière
de prévention des incendies.
940947003-03
ADVERTENCIA
El uso de este equipo puede producir chispas propensas a
iniciar incendios cerca de vegetación seca. Es posible que se necesite un parachis-
pas. El operador debe ponerse en contacto con las agencias contra incendios locales
para conocer las leyes y regulaciones relacionadas con los requisitos de prevención
de incendios.
FUEL WARNING
No smoking when filling with gasoline. Do not overfill. Full
level is 1 in. below the top of the fuel neck. Stop the engine
for five minutes before refueling to avoid the heat from the
muffler igniting fuel vapors.
ENGINE LUBRICANT WARNING
You must add lubricant before first operating the generator.
Always check the lubricant level before each operation. The
lubricant level should always register between the hatched
areas on the dipstick. The unit is equipped with a sensor
which will automatically shut off the engine if the lubricant
level falls below a safe limit.
GROUNDING WARNING
National Electric Code requires
generator to be grounded to an
approved earth ground.
CLEARANCE WARNING
While operating and storing, keep at least 3 feet of clearance
on all sides of this product, including overhead. Allow a mini-
mum of 30 minutes of “cool down” time before storage. Heat
created by muffler and exhaust gases could be hot enough
to cause serious burns and/or ignite combustible objects.
SPARK ARRESTOR
Operation of this equipment may create sparks that can start
fires around dry vegetation. A spark arrestor may be required.
The operator should contact local fire agencies for laws or
regulations relating to fire prevention requirements.