Installation
Install the Detector in the location, where the quality of communication
is appraised «excellent» or «good».
Install the base at the chosen place. Insert the Detector into the base
and fix it by turning clockwise.
Maintenance
The operability of the Detector should be checked at least annually.
The Detector should be cleaned from dust if the Detector generates
«Fault» or «Optical Smoke Chamber Dustiness» message. For this
purpose, sweep the optical system of the Detector by air under 0.3–0.5
kg/cm
2
pressure.
In order to prevent the optical smoke chamber dustiness, depending
on the operating conditions and according to statistical data, it is
recommended to carry out periodical technical maintenance of all
Detectors logged in the fire alarm system.
Attention!
For the power supply battery life safe-energy, do not leave
the Detector energized with the repeater powered off for a long time.
Storage and Transportation
The Detectors in original package may be transported by any means
of transportation in closed vehicles over any distances in compliance
with the existing shipping rules concerning the respective means of
transportation.
Storage conditions of the Detectors: storage premises should not
contain any current-conducting dust, acid and alkali fumes, as well as
corrosive gases or those destroying insulation.
Manufacturer’s Guarantees
The manufacturer guarantees conformity of the Detector to the
Technical Specifications requirements provided the transportation,
storage, installation and operation conditions are observed.
The guaranteed shelf life of the Detector is 42 months since the
date of manufacture.
The guaranteed useful life is 36 months since the day of putting into
operation within the guaranteed shelf life.
The Detectors that are found non-conforming to the Technical
Specifications requirements shall be repaired by the manufacturer,
provided the installation and operation rules have been complied with.
Note
- Warranty obligations are not applied to the power supply
batteries.
Packing Certificate
Wireless smoke detector «Ladoga PD-RK» has been manufactured
in accordance with current technical documentation is classified as
fit for operation and is packed by «RIELTA» JSC.
Packing date _______________________________
month, year
Installing the Detector
When choosing the place of installation for the Detector, take
into account the fact that the Detector refers to fire Detectors with
operability control and therefore, a single Detector may be installed
in the monitored premise.
All other conditions being equal, the location chosen for the
installation of the Detector should meet the following requirements:
- prevention of water ingress from the front side and the base side;
- minimum vibrations of building structures;
- minimum illumination
- maximum distance from sources of electromagnetic interference
and infrared radiation (heating units);
- maximum convenience of installation, checking and removal of
the Detector.
Transmission quality may differ from premise to premise; therefore,
it is advisable to apprise a communication quality before the Detector
is finally installed.
Communication Quality Appraising
The Detector should be installed within the radio coverage zone of the
CP; therefore, it is recommended to check the messages transmission
from the presumed installation place and to appraise the quality of
the communication.
After removal from its base (tamper contact is released), the Detector
transmits the «Tamper» message and then displays the quality of
communication as per Table 4.
Table 4
LED Indication
Communication
Quality
Appraisal
Recommendations
Color
Mode
Green
Three
blinks
Excellent
Install the Detector at
this place
Green
Two blinks
Good
Green
One blink
Communication
established
Choose another place
for installation or use
a repeater*)
Red
Four
blinks
No
communication
*) - «Ladoga BRSS-RK-RTR»
Operability Test
Push the operability test button (5) and hold it during not less than 5
s, until the red LED indicator starts blinking. Make sure that «Fire» alarm
message at correspondent zone is received and logged in CP.
Feed testing spray or introduce the reflector (needle, clip, wire with
maximal thickness 1 mm) into the optical smoke chamber opening. To
restart the Detector after the fire «Alarm» message generation, «Set On»
command by the wirelwss two-way communication «Rielta-Contact-R»
protocol from the CP is required.
Rev. 8 of 26.07.2018
№Э00443
v.10.2
Made in Russia
«RIELTA» JSC, www.rielta.com
Chapaeva Str. 17, Saint Petersburg, Russia, 197101, [email protected]
Tel./fax: +7 (812) 233-0302, 703-1360
Technical support, tel.: +7 (812) 233-29-53, 703-13-57, [email protected]