Design of the Detector

The Detector outside view is shown in Figure1.
The Detector is enclosed in a plastic case (1).  Two LED indicators (2) 

are located on the face side of the case. The operability of the Detector 
is checked by means of the introduction of a reflector (needle, clip, wire 
with maximal thickness 1 mm) through the opening (3) located  on the 
case (1). The PCB comprises tamper contacts (4), the operability test 
button (5), the main power supply battery holder (6) and the backup 
power supply battery holder (7), «RESET» contacts (8).

   

LED Indication

Table 3

Detector Status

Indication

«Norm» mode

LED indicator lights green (once per  

15 seconds)

Mode «Binding»

LED indicator blinks green intermittently

«Fire»

LED indicator blinks red alternately at 1 Hz 

frequency

«Communication 
Quality Appraisal»

see Table 4

«Identification» 

indication is on

LED indicator blinks red and green 

alternately

No communication 

with the CP

LED indicator blinks red (once per 15 

seconds)

Binding with the CP 

The «Binding» procedure is intended for logging of the connected 

Detector in the CP/Repeater, and for the reception of communication 
parameters by the Detector.

1. Install the reserve battery first and then the main battery (battery 

type CR123A) or remove the insulators.

2. Close «Reset» contacts on the PCB  in order to reset the Detector.
3. The green LED blinking displayes the Detector operation in the 

«Binding» mode.

4. After a successful binding with the CP, the red LED indicator 

lights for 2 seconds.

5. The time during which the Detector operates in the «Binding» 

mode is limited to 100 sec., after what the Detector changes to the 
sleep mode. The «Binding» mode may be resumed.

Note

 - A Detector supplied by the manufacturer is ready for the 

binding procedure and does not require an additional contacts closing.

Introduction

The wireless smoke Detector «Ladoga PD-RK» (hereinafter, the Detector) 

is intended for detecting ignition accompanied by smoke, generating and 
sending a «Fire» message within the 433.05 to 434.79 MHz frequency 
range via a two-way communication by the «Rielta-Сontaсt-R» 
exchange protocol. 

The Detector is designed for operation as a component of any control 

panel (hereinafter, CP) supporting the «Rielta-Contact-R» wireless 
exchange protocol.

The mode of operation of the Detector is based on the detection of 

the optical radiation reflected from smoke particles.

Features

The Detector has the following features:
- Received command «Set On» from the CP by the wirelwss two-way 

communication «Rielta-Contact-R» protocol is the obligatory condition 
of the Detector restart after the fire «Alarm» message generation;

- The Detector comprises built-in functional testing module;
- Failure message is generated by the Detector in case of circuit 

layout failure or sensitivity decrease for more than 2.5 times; 

- The Detector provides compensation of the optical smoke chamber 

dust content. Upon reaching the dust concentration threshold, the 
«Optical Smoke Chamber Dustiness» message is generated by the 
Detector;

- Alarm messages in case of wall or cover tampering and removal 

the detector from the base are generated by the Detector; 

- The Detector provides automatical switch to a backup operating 

frequency in case of an imperfect interference situation at the main one;

-  «Identification» LED indication is switched on and disabled by the 

relevant command from CP;

- The Detector is powered by two lithium batteries CR123A type. 

One is the main battery the other is the reserve battery;

- The Detector ensures not less than three years of standby operation 

under main battery power supply  and not less than two months under 
the backup one.

Features

Table 1

Parameter Name

Value

Threshold of sensitivity

0.14 dB/m;

Detector response delay

maximum 5 s

Broadcast period

10 sec to 10 min

Operating temperature 

from minus 20 to +55 °С

Dimensions

maximum 

Ø

125 x 70 mm

Weight (without batteries)

maximum 0.2 kg

IP rating

IP30

Scope of delivery

The Detector scope of delivery is referenced in Table 2.
Table 2

Description

QNT

Wireless smoke Detector «Ladoga PD-RK»
Screw 3-3х40.016 
Screw plug «SORMAT» NAT 5x25
CR123A lithiun power supply battery
Wireless smoke Detector «Ladoga PD-RK». Installation Guide

1 pc.

2 pcs.
2 pcs.

2 pc.

1 copy

 

Informativity

The Detector ensures transmission and indication of the following 

messages:

- «Fire» - in case the optical density of the environment exceeds 

the threshold of sensitivity;

- «Tamper» - in case the Detector is resumed from its base;
- «Fault» - in case of the Detector system fault or its sensitivity drops 

more than 2.5 times;

- «Norm» - in case there are no other messages;
- «Main low-battery» - upon power voltage drops below 2.4 ±0.2 

during a communication session;

- «Backup low-battery» – upon  power voltage drops below 2.4 ±0.2 

during a communication session;

WIRELESS SMOKE DETECTOR 

«Ladoga PD-RK»

Installation Guide 

Figure 1

5

6

1

2

3

Reset

4

7

Backup

Main

- «Binding» mode - during logging of the Detector in the system;
- «Identification» - upon receipt of a relevant command from the CP;
- Communication quality appraising.