Note
–
In this mode the alarm message generated in compliance
with the adjusted sensitivity mode is not displayed by LED indication.
In the motion absence in the detection zone the LED indicator must
not light. Upon the expiry of 5 minutes check procedure, the detector
transfers to normal mode. If DIP-switch is in position «2» – «ON»,
generation of alarm message is displayed by LED-indicator lighting
for the 3 sec period.
2) Sensitivity mode adjustment
DIP-switches position: «1» – «ON», «2» – «ON». The mode is intended
for detector sensitivity appraisal (the distance, which is possible to pass
through the detection zone up to the point, where the movement is
detected, and alarm message is generated). The LED indicator blinks
for 0.25
period under the condition of detection zone beam crossing,
and for 3 sec during alarm message generation.
Stop after each alarm message generation and wait until the LED
indicator is disabled for 8 – 10 sec and more, then continue movement
through the detection zone.
Note
– If the detector does not identify movement within the
detection zone, it is necessary to change detector position by means
of swivel bracket (in case of wall mounting the horizontal turning angle
of the detector on swivel bracket – ±45
0
, vertical – not less than 20
0
).
12 LED Indication Disabling
For the detector operation masking, the LED indication disabling
mode is available. DIP-switch «2» – «OFF».
In this mode the LED indicator is lighting for only one minute after
detector energizing, as well as in «Alarm Memory» and «Malfunction»
modes.
13 Alarm Memory Mode
DIP-switch «3» – «ON». The LED indicator is lighting green in
5 min after alarm memory generation. Duration of indication – 15 min.
14 Self-Test Mode
The detector provides self-testing of the following parameters:
amplifier operability, input voltage, ambient temperature. If the
ambient temperature range is close to 36
о
С, the sensitivity threshold
changes, the level of sensitivity is automatically adjusted, what leads
to detectability enhance (temperature compensation).
In case of self-test failure (amplifier malfunction, voltage drop lower
than 9
-1
V, ambient temperature out of permissible temperature range),
«Malfunction» message is generated by opening the relay output
contacts repeated by alternate LED indicator blinking red and green.
«Malfunction» message duration – 15 min. After elimination of
malfunction, the detector turns to self-test mode.
ATTENTION!
The detector must be checked at least once annually
for functional testing.
15 Storage and Transportation
The detectors in their original packing may be shipped by any
transport means in covered vehicles (in railway, cars, trucks, sealed
heated compartments of aircraft, ship cargo holds, etc). The storage
room should be free from current-conducting dust, acid vapors, alkali
and gases that cause corrosion and destroy insulation.
16 Manufacturer’s Guarantees
The Manufacturer guarantees conformity of the detector to it’s
Technical Specifications if conditions of transportation, storage,
assembling and operation are observed. The guaranteed storage
period is 63 months since the date of manufacturing the detector.
The guaranteed period of operation is 60 months since the date of
commissioning within the storage period guaranteed.
The detectors that are found to non-conforming to it’s Technical
Requirements shall be repaired by the Manufacturer, provided the
installation and operation rules have been complied with.
17 Acceptance and Packing Certificate
Passive infrared detector
«Foton-10M»
«Foton-10M-01»
batch №___________________
manufactured in accordance with current technical documentation
is classified as fit for operation and is packed by «RIELTA» JSC.
Person responsible for acceptance and packing
QC representative_________________ __________________.
Date, month, year
Figure 3
Table 3
Mode
DIP-switch
DIP-switch Position
«ON»
«OFF»
Sensitivity
«1»
TEST
«SENS» (Sensitivity
determination)
«ZONE» (Detection
zone determination)
Testing
«2»
IND
«IND» (ON)
«OFF» (LED indicator is
disabled)
Indication
Disabling
«3»
MEM
«MEM» (Alarm
memory ON)
«OFF» (Alarm memory
OFF)
9 LED Indication
The Led indicator located at the front of the cover displays the
detector mode.
Table 3
Message
Led Indicator
Color
LED Indication State
«Warm-up Time»
RED
Blinking with 1 Hz frequency during
60 sec
«Norm»
-
LED Indication is OFF
«Alarm»
RED
LED Indication is on during 3 sec
«Malfunction»
RED
GREENN
Alternate switching during 15 min
«Alarm Memory»
GREENN
LED Indication is ON during 15 min
10 Functional Check
After energizing of the detector, the self-testing process is realized
during one minute. It ensures control of the following parameters:
input voltage, ambient temperature, operation capacity of the amplifier
channel. During the procedure, the LED indicator is blinking red
(irrespective of the DIP-switch «2» position), relay contacts are opened.
11 Testing Mode
Upon the expiry of the warm-up time, the detector turns to standby
mode and is able to generate alarm message. During the process
within 5 minutes it is possible to check the detector parameters. The
checking procedure provides two modes.
1) Detection zone position location
DIP-switches position:
«1» – «OFF», «2» – «ON». The mode is
intended for each beam of detection zone positioning in the secured
premises. Under the condition of each beam crossing the LED indicator
switches for 0.25 sec. Optimized speed of movement at maximal
distance – 0.5 m/sec.
Rev. 2 of 26.01.15
№00108
Circuit
Cont.
1
2
3
4
5
6
+12V
-12V
AL
AL
Taper
Taper
To power
source
R
term1
Detector
To CP
а)
Taper-
control
AL
Security
AL
R
term1
Circuit
Cont.
To power
supply unit
R
term1
Detector
1
2
3
4
5
6
+12V
-12V
AL
AL
Taper
Taper
«RIELTA» JSC, www.rielta.ru,
Chapaeva Str. 17, Saint Petersburg, Russia, 197101, [email protected],
Tel./fax. +7 (812) 233-0302, 703-1360,
Technical support, tel. +7 (812) 233-29-53, 703-13-57, [email protected].
b)
Table 2
Installation height
Detector tilt
Distance to the wall, L, mm
2 – 3 m
3 – 4 m
4 – 5 m
0°
5°
9°
35
28
22
Notes:
1 The tilt and the distance values listed in Table 2 are reference
data. Final distance L value is defined in accordance with the test
pass results.
2 The detector base turning horizontally would change the distance
(L) from the wall to the inclined detector base. The change depends
on the turning angle. Thus, it is necessary to adjust the detector tilt.
8 Connection
- The terminals for the detector connection are located at the top
of PCB.
- Fulfill connections in accordance with the Figure 3a (for single
alarm loop connection) and with Figure 3b (with alarm loop and tamper
connection).
- Install the DIP-switches in accordance with application conditions.
- Put the detector cover on it’s place.
- Install DIP-Switches «1», «2», «3» in accordance with application
conditions.
- Put the detector cover on it’s place.