37 

20151674

GB

Operation, indications, diagnostic

8.3

Resetting of burner control

When a lockout occurs, the burner control can be immediately re-
leased by pressing the “RESET” button.

NOTE:

For  the  meaning  of  the  diagnostic  codes  and  errors,  see  the 
chapter “Error code list with operation via the control box control 
panel” on page 36.

8.3.1

Diagnostics of the cause of the fault

After the lockout, the faults indicator lamp stays on fixed. Under 
these conditions, it is possible to activate the visual diagnostic of 
the cause of the fault based on the table of colour codes by keep-
ing the reset button pressed for more than 3 seconds (info but-
ton). 
Press the reset button again (info button) for at least 3 seconds 
to activate the diagnostics interface. 
If the diagnostic interface is started accidentally, a condition sig-
nalled by the blinking red indicator light, it can be deactivated by 
pressing the reset button again (info button) for > 3 seconds. 
The switching moment is indicated by a pulse of yellow light.

Tab. Y

During the diagnosis of the cause of the fault, the outputs of the 
controls are disabled

The burner stays off

Indication of external fault (alarm) on the clamp X2-03, foot 3 
on fixed

At the outlet of the diagnostic of the cause of the fault the burner 
is switched on again by resetting the burner control. 
Press the reset button (info button) for about 1 second (< 3 sec-
onds).

Error code table
Red blink code 

fault indicator light

Possible cause

2 blinks

No flame at the end of the safety time

Fuel valves dirty or defective

Flame detector dirty or defective

Burner not adjusted correctly, no fuel

Ignition device defective

4 blinks

Extraneous light at burner start-up

7 blinks 

Too many flame losses during operation (limitation of repetitions)

Fuel valves dirty or defective

Flame detector dirty or defective

Burner adjustment incorrect

8 blinks 

Free

9 blinks

Free

10 blinks 

Wiring error or internal error, outlet contacts, other faults

12 blinks 

Valve test

Fuel valve 1 leak

13 blinks 

Valve test

Fuel valve 2 leak

14 blinks 

POC error valve closure control

15 blinks 

Error code 

15 (e.g. according to the type of program module)

error code 20: Min gas pressure switch fault
error code 22: Safety loop error

Содержание RX 150 S/PV

Страница 1: ...Installation use and maintenance instructions 20151674 1 05 2018 Premix gas burner Modulating operation CODE MODEL TYPE 20139726 RX 150 S PV 904T2 GB...

Страница 2: ...Translation of the original instructions...

Страница 3: ...ecks 17 5 4 Operating position 18 5 5 Preparing the boiler 18 5 5 1 Boring the boiler plate 18 5 5 2 Head length 18 5 6 Position of probe and electrode RX 150 S PV 19 5 7 Securing the burner to the bo...

Страница 4: ...ontrol sequence in the event of a fault 35 8 2 Error code list with operation via the control box control panel 36 8 3 Resetting of burner control 37 8 3 1 Diagnostics of the cause of the fault 37 8 3...

Страница 5: ...nce with the following Technical Standards EN 12100 EN 676 and according to the European Directives MD 2006 42 EC Machine Directive LVD 2014 35 UE Low Voltage Directive EMC 2014 30 UE Electromagnetic...

Страница 6: ...ed out correctly may cause damage to the ma chine and or injury to people DANGER DANGER LIVE COMPONENTS This symbol indicates operations which if not car ried out correctly lead to electric shocks wit...

Страница 7: ...of damage to things or injury to people if such damage injury was due to any of the following causes incorrect installation start up use and maintenance of the burner improper incorrect or unreasonab...

Страница 8: ...e Only those parts envisaged by the manufacturer can be replaced 3 2 Personnel training The user is the person body or company that has acquired the machine and intends to use it for the specific purp...

Страница 9: ...f parameters using the AZL 21 display kit page 44 4 2 Burner equipment Gas valve flange screws No 1 Insulating gasket No 1 4 pin plug 7 pin plug No 1 Screws and nuts for fixing the flange to the boile...

Страница 10: ...ot have a replaceable internal fuse Model RX 150 S PV Type 904T4 Head assembly Supplied with head assembled Power 1 Delivery 1 min max min max kW Mcal h 25 145 21 5 124 7 Fuels Natural gas G20 methane...

Страница 11: ...ensions of the burner are given in Fig 1 Bear in mind that in order to inspect the combustion head the burner must be removed from the boiler door Tab C Tab D H L D T P TX E Fig 1 20144071 mm H L P T...

Страница 12: ...ion head with metal mesh 8 Ignition transformer 9 Electrodes 10 Probe 11 Fan motor relay 12 Programming diagram 13 Sockets for electrical connection 1 3 6 7 9 5 8 2 10 4 11 12 13 20144072 Fig 3 WARNIN...

Страница 13: ...make sure that the en tire control box is perfectly dry Failure to do this will lead to the risk of electrocution Static charges must be avoided since they can damage the control box s electronic comp...

Страница 14: ...e capacitive reactance of the line reduces the magnitude of the flame signal use a separate cable Respect the permitted lengths for the cables of the detectors see Technical Data The ionisation probe...

Страница 15: ...Cos 0 4 Alarm output X2 03 3 Nominal voltage Nominal current Power factor AC 230 V 50 60 Hz 1A Cos 0 6 Ignition transformer X4 02 foot 3 Nominal voltage Nominal current Power factor AC 230 V 50 60 Hz...

Страница 16: ...N Can be parameterized t1 TSA 4 3 2 7 5 2 6 2 2 0 6 2 5 2 2 9 5 2 Relay contact Function outputs SK X3 04 Pin 1 X5 03 Pin 1 X5 03 Pin 3 X65 Pin 1 X5 03 Pin 2 X65 Pin 1 X3 02 Pin 1 X5 01 Pin 2 X2 02 Pi...

Страница 17: ...ermostat SV Safety valve V1 Fuel valve V2 Fuel valve V2a Fuel valve W Limit pressure switch or thermostat Z Ignition transformer C C controller Input output 1 signal ON Input output 2 signal ON Input...

Страница 18: ...time without flame simulation test Part 2 pre purging time with flame simulation test 2 1 seconds 36 Stabilisation time at ignition speed 38 Spark pre ignition time 40 Post ignition time parameter 257...

Страница 19: ...ommended to carry out cleaning and maintenance more frequently WARNING The handling operations for the burner can be highly dangerous if not carried out with the great est attention keep any unauthori...

Страница 20: ...ction must allow the blast tube to be taken out WARNING The burner is designed to work only in the posi tions 1 2 3 4 and 5 Installation 1 is preferable as it is the only one that allows the maintenan...

Страница 21: ...een Fig 12 WARNING Before installing the burner on the boiler make sure the probe and electrode have been posi tioned correctly as in Fig 11 Do not turn the electrode position it as shown in Fig 11 Pl...

Страница 22: ...ammable source Precautions avoid knocking attrition sparks and heat Make sure the fuel interception tap is closed be fore performing any operation on the burner WARNING The fuel supply line must be in...

Страница 23: ...valve Remove the protection screw and act on the intern screws with a hex key To increase the output turn the screw clockwise tighten To reduce the output turn the screw anticlockwise unscrew NOTE Th...

Страница 24: ...n series to TL to stop the burner at least once every 24 hours Refer to the wiring diagrams The electrical safety of the device is obtained only when it is correctly connected to an efficient earthing...

Страница 25: ...speed can be regulated through an adjustment of the control box The adjustments take place via the keys and display on the con trol box and are carried out using the following parameters START ignitio...

Страница 26: ...rn the min imum gas valve screw clockwise to increase the gas flow In case of ignition failure after the set attempts the burner goes into lockout Loc 07 Press the info button for 1 3 seconds un lock...

Страница 27: ...ay LoA and 41 The relative value 41 of the current position or current speed is displayed Current speed 0 rpm 0 display The current speed corresponds to the nominal load speed 100 display The actual v...

Страница 28: ...he normal operation mode Keep the but ton A pressed together with the button or 5 sec onds to return to the manual operation Press buttons or together ESC function to exit the manual operation and act...

Страница 29: ...yed Display PrC Press and to display parameter bAC Display bAC Run appears during the download backup procedure in the program sequence The display shows End and bAC alternately The display shows the...

Страница 30: ...sure the gas delivery on the counter to precisely establish the burnt output Using a smoke analyser measure the value of the CO2 or the O2 in order to optimise the burner calibration The correct value...

Страница 31: ...onditions of maximum safety i e with gas deliv ery at the minimum D9714 Fig 14 No Parameter OEM preset Value 1 pre purging time 30 Seconds 2 Safety time 3 Seconds 3 Flame stabilisation time 10 Seconds...

Страница 32: ...um pressure switch knob to the mini mum end of scale position where present The burner must stop in lockout Turn off the burner and cut off the power Disconnect the minimum gas pressure switch connect...

Страница 33: ...ster some valves are fitted with light signals or closure opening position indicators that are activated when the electrical supply arrives 7 2 3 Checking and cleaning Combustion head Open the burner...

Страница 34: ...mum calibration of the burner requires an analysis of the flue gases Significant differences with respect to the previous measure ments indicate the points where more care should be exercised during m...

Страница 35: ...r electronic cam if present 10 years or 250 000 operation cycles Oil valve solenoid if present 10 years or 250 000 operation cycles Oil regulator if present 10 years or 250 000 operation cycles Oil pi...

Страница 36: ...nents SIX MONTHLY Check of system components for detecting flame fault SIX MONTHLY Check of firing rate command SIX MONTHLY Check of piping and cabling of all the lockouts and shut off valves SIX MONT...

Страница 37: ...ted 8 Operation indications diagnostic Causes Answer Mains voltage interruption Restart Voltage below the undervoltage threshold Safety switch off Voltage above the undervoltage threshold Restart Extr...

Страница 38: ...internal error outlet contacts other faults Loc 12 Valve test Fuel valve 1 leak Loc 13 Valve test Fuel valve 2 leak Loc 14 POC error POC error valve closure control Loc 20 Min gas pressure switch ope...

Страница 39: ...Tab Y During the diagnosis of the cause of the fault the outputs of the controls are disabled The burner stays off Indication of external fault alarm on the clamp X2 03 foot 3 on fixed At the outlet...

Страница 40: ...witching the mains ON OFF The display shows run during the download reset process of the program sequence The display shows rSt and End alternately The display shows the end of the data exchange After...

Страница 41: ...download restore process of the program sequence At the end of the reset process the unit is automatically in a lockout position LOC 138 and need to be released in order to work After 2 minutes the un...

Страница 42: ...d the settings in the internal memory could be overwritten 8 4 2 Reset Tab AC NOTE For the meaning of the diagnostic and error codes see the chap ter Error code list with operation via the control box...

Страница 43: ...ay contact K11 Reading only 0 999999 1 0 mode 170 02 Switching cycles relay contact K2 Reading only 0 999999 1 0 mode 170 03 Switching cycles relay contact K1 Reading only 0 999999 1 0 mode 171 Max re...

Страница 44: ...ation UDS status 0 PC tool mode 1 PWM mode 2 actuator mode 3 internally 4 internally 5 internally Reading only 0 5 1 0 SO 559 PWM mode 0 open loop control 1 PID control 2 safety mode PWM limits Modifi...

Страница 45: ...nterval for constant time PT1 Lower speed interval threshold Modification 800 rpm 9000 rpm 10 rpm 2000 rpm SO OEM 700 Error history 701 00 Current error Error code Reading only 2 255 1 mode 701 01 Cur...

Страница 46: ...parameters To display the diagnostics proceed as follows connect the kit supplied separately to the appropriate socket on the control box Reading of the information begins when the software programme...

Страница 47: ...ctrical panel layout Index of layouts 2 Indication of references 3 Functional diagram 4 Functional diagram 5 Functional diagram 6 Functional diagram 7 Electrical wiring that the installer is responsib...

Страница 48: ...20151674 46 GB Appendix Electrical panel layout 0 1 0 0 1 0 RX 150 S PV...

Страница 49: ...47 20151674 GB Appendix Electrical panel layout...

Страница 50: ...20151674 48 GB Appendix Electrical panel layout...

Страница 51: ...49 20151674 GB Appendix Electrical panel layout 0 0 0 1 1...

Страница 52: ...87 A5 76 789 7 76 78 B 6 6 6C 8 7C 7 7 A5 796 789 7 79 78 6 C 6 D 6 C E6 96 C 7 8 F 7 C A5 G6 789 7 78 6 H 8 6 8 6 6 9 8 9 I 9 69 4 A5 1 1 2 79 9 1 555 J 1 K 2 2 2 K 2 2 2 K 2 2 L 2 K 2 2 2 K 2 2 2 K...

Страница 53: ...y IN Burner external ON OFF switch ION Ionisation probe MV Fan motor Q2 Auxiliary switches RS Burner external reset button TA Ignition transformer TL Limit thermostat pressure switch TR Adjustment the...

Страница 54: ......

Страница 55: ......

Страница 56: ...Subject to modifications RIELLO S p A I 37045 Legnago VR Tel 39 0442 630111 http www riello it http www riello com...

Отзывы: